CONTROL SYSTEMS
8/13/2019 04 Sundyne Presentation Fscontrol System
2/27
INTRODUCTION
General, pump curve - System curve
Parallel operation
Series operation
Compressor control
Pump control bulletin
8/13/2019 04 Sundyne Presentation Fscontrol System
3/27
GENERAL DISCUSSION
Are recurring problems a responsibility of maintenance?
Controls/procedures may result in equipment failure
May need coordination with process group
8/13/2019 04 Sundyne Presentation Fscontrol System
4/27
CURVE SHAPES
120
100
80
60
40
00 20 40 60 80 100 120 140 160
Flow (Percent)
Head
(Percent)
Full EmissionConcentric Bowl & ETADouble Log Spiral
Z Series
8/13/2019 04 Sundyne Presentation Fscontrol System
5/27
TOTAL SYSTEM HEAD
Capacity, Q
Head, H
System static head
System friction head
System head
8/13/2019 04 Sundyne Presentation Fscontrol System
6/27
IMPACT OF VALVE THROTTLING
Capacity, Q
Head, H
8/13/2019 04 Sundyne Presentation Fscontrol System
7/27
OPERATING SYSTEM
Capacity, Q
Head, H
Q2 Q1
8/13/2019 04 Sundyne Presentation Fscontrol System
8/27
BY-PASS REQUIRED?
Capacity, Q
Head, H
Bypass Flow
8/13/2019 04 Sundyne Presentation Fscontrol System
9/27
INTERSECTION OF PUMP AND SYSTEMCURVES
Capacity, Q
Head, H
Under-sized pump
Properly sized pump
8/13/2019 04 Sundyne Presentation Fscontrol System
10/27
IMPACT OF WEAR
Over a period of time, system and pump characteristics getdeteriorated
After 15 years, friction losses in pipe are 60% more important!
To be taken in account in the choice of the pump
Minor loss for pump performances
8/13/2019 04 Sundyne Presentation Fscontrol System
11/27
MINIMUM FLOW
2 Types of Minimum flow phenomena:
At start-up
During normal operation
8/13/2019 04 Sundyne Presentation Fscontrol System
12/27
MINIMUM FLOWat start-up
Start-up shock wave
Water Hammering
8/13/2019 04 Sundyne Presentation Fscontrol System
13/27
MINIMUM FLOWduring operation
Minimum Continuous stable flow
Minimum Continuous thermal flow
8/13/2019 04 Sundyne Presentation Fscontrol System
14/27
MINIMUM FLOWFlow surging
May happen if a air/gas pocket is located in the downstream line
Can be seen as a simple spring-mass system
Need a excitation to happen
Can be reduced / solved by having a flow control valve close from thepump discharge
Predominent for compressors
8/13/2019 04 Sundyne Presentation Fscontrol System
15/27
MINIMUM FLOWSurging reduction
Control valve within 3m of discharge
Flexible lines only after control valve
A straight pipe of at least 10 times diameter length on the discharge
Choose correct size of valve
Install low flow by pass
Eliminate air and gasses trapped
Operate at higher flow
8/13/2019 04 Sundyne Presentation Fscontrol System
16/27
MINIMUM FLOWMinimum flow control
S FS
8/13/2019 04 Sundyne Presentation Fscontrol System
17/27
MINIMUM FLOWPhenomenon
8/13/2019 04 Sundyne Presentation Fscontrol System
18/27
8/13/2019 04 Sundyne Presentation Fscontrol System
19/27
MAXIMUM FLOWPhenomenon
8/13/2019 04 Sundyne Presentation Fscontrol System
20/27
8/13/2019 04 Sundyne Presentation Fscontrol System
21/27
CONTROLLING
120
100
80
60
40
00 20 40 60 80 100 120 140 160
Flow (Percent)
Head
(Perc
ent)
Full EmissionConcentric Bowl & ETADouble Log SpiralZ Series
8/13/2019 04 Sundyne Presentation Fscontrol System
22/27
8/13/2019 04 Sundyne Presentation Fscontrol System
23/27
PARALLEL OPERATION
Always use discharge check valve.
Need differential to open check valve
Low gravity fluid may vaporize - Pump deadheaded.
Unstable operation results in equipment damage
Always use bypass control valve.
8/13/2019 04 Sundyne Presentation Fscontrol System
24/27
PARALLEL OPERATION WITH FLOW
CONTROLLED BYPASS ON EACH PUMP
FLOW SENSOR
CONTROLLER
BLOCK
CHECK
BYPASS
CONTROL
VALVE
CONTROLLER
FLOW SENSOR
BLOCK
CHECK
BYPASSCONTROL
VALVE
THROTTLE
CONTROL
VALVE
A
B
STARTUP SEQUENCE
1. SET EACH BYPASS FORMIN. ALLOWABLE FLOW
2. CLOSE PROCESS FLOW
CONTROL VALVE3. START PRE-LUBE PUMPS
IF APPLICABLE4. START A AND STABILIZE
START B AND STABILIZE5. SET DESIRED PROCESS
FLOW RATE
PARALLEL OPERATION
8/13/2019 04 Sundyne Presentation Fscontrol System
25/27
SERIES OPERATION
Capacity, Q
Head, H
PUMP A OR B
PUMP A AND B
SYSTEM HEAD CURVE
8/13/2019 04 Sundyne Presentation Fscontrol System
26/27
SERIES OPERATION
Requires extra measure of care (for second unitespecially)
Pre-lube normally advisable on 2nd unit.
Tandem seal & suitable buffer probably required.
Flange rating to be reviewed
Thurst bearing capacity to be increased
8/13/2019 04 Sundyne Presentation Fscontrol System
27/27
STARTUP SEQUENCE1. SET BYPASS FOR MIN. ALLOWABLE FLOW2. CLOSE PROCESS FLOW CONTROL VALVE3. START PRE-LUBE PUMPS IF APPLICABLE
4. START 1ST UNIT AND STABILIZE5. START 2ND UNIT AND STABILIZE6. SET DESIRED PROCESS FLOW RATE
BYPASS FLOW
CONTROL
SENSOR CHECK
CHECKCONTROLLER
PROCESS FLOW
CONTROL VALVE
SERIES OPERATION - PREFERRED