Last rev.130GD05: 12/08/99 L.Z. document.xls 1/2
PROYECTO XXXXXXXX CALCULÓ: X.X
CLIENTE XXXXXXXX REVISÓ: X.X
ESTRUCTURA XXXXXXXX APROBÓ: X.X
PLANCHA BASE DE COLUMNA -ASD FECHA: XX/XX/XX
1. Materiales
Esfuerzo de cedencia del acero Plancha : 2530 kg/cm2
Resistencia de Concreto a 28 d.Concreto: 280 kg/cm2
2. Geometría de los componentes
COLUMNA PERNOS DE CONEXIÓN
ELEMENTO DESIG. CANTIDAD
COLUMNA CP 400x55 17.5 12.5 1.2 0.6 1.9 8 7.92
PLANCHA BASE
GEOMETRIA PLANCHA
VALORES SUGERIDOS 35 35 5 3.75 8.75 11.25
PEDESTAL
40 40
3. Solicitaciones actuantes
Caso de Carga: 0,75*( DL + W )
Corte : V = 0 kg
Carga Vertical: P = 10000 kg
Momento: M = 500000 kg-cm (Moment)
4. Excentricidad
e= 50.00 cm e > B/2, CASO 4
Fy =
f'c =
d (cm) bf (cm) tf (cm) tw (cm) DIA. (cm) Ab (cm2)
A (cm) B (cm) C (cm) D (cm) E (cm) F (cm)
bx (cm) by (cm)
Mx
DISEÑO DE CONEXIONES
C D C
F
F
A
P
Mx
Vx
B
DE E
bf
Last rev.130GD05: 12/08/99 L.Z. document.xls 2/2
Last rev. 130GD05: 12/08/99 L.Z. document.xls 2/2
PROYECTO XXXXXXXX CALCULÓ: X.X
CLIENTE XXXXXXXX REVISÓ: X.X
ESTRUCTURA XXXXXXXX APROBÓ: X.X
PLANCHA BASE DE COLUMNA -ASD FECHA: XX/XX/XX
CASE 1 - e=0 THIS SHEET IS NOT VALID. SEE CASE 4
35*35 = 1225 cm2
40*40 = 1600 cm2
fp max = 0,70*f'c = 196 kg/cm2
112 kg/cm2 < 0,70*f'c OK
fp (allowed) = 112 kg/cm2
fp = 10000 / 1225 8.16 kg/cm2 OK
0,95d = 16.63 cm 0,8bf = 10.00 cm
m = 9.19 cm n = 12.50 cm
345 kg-cm 638 kg-cm
M max = 638 kg-cm
Fb = 0,75*Fy = 1898 kg/cm2
THICKNESS PLATE IS BIG !
tp = 14 mm
A1 =
A2 =
fp (allowed) = 0,35*f'c*(A2/A1)0,5 = 0,35*f'c*(A2/A1)0,5 =
M1 = fp*m2/2 = M2 = fp*n2/2 =
tp = Ö 6M /(0,75Fb*b) =
Moment Diagram (x)
0,8bf
fp = P/A
M2 M2
Moment Diagram (y)
PP
0,95d
fp = P/A
M1 M1
mn
DISEÑO DE CONEXIONES
Last rev. 130GD05: 12/08/99 L.Z. document.xls 2/2
last rev. 130GD05: 12/08/99, L.Z. document.xls Rev. A0 2/2
PROYECTO XXXXXXXX CALCULÓ: X.X
CLIENTE XXXXXXXX REVISÓ: X.X
ESTRUCTURA XXXXXXXX APROBÓ: X.X
PLANCHA BASE DE COLUMNA -ASD FECHA: XX/XX/XX
CASE 2 - e <= B/6 THIS SHEET IS NOT VALID. SEE CASE 4
a= 9.1875 cm (Critical section)
f1= 78.13 £ 0,70*f'c0
f2= -61.81
f3= 41.40
2781 kg-cm (on critical section)
30 mm
kg/cm2
kg/cm2
kg/cm2
Mpl=
tpl=
Critical section
M
P
f1
a
B
f2 f3
DISEÑO DE CONEXIONES
DISEÑO DE CONEXIONES
last rev. 130GD05: 12/08/99, L.Z. document.xls Rev. A0 2/2
LAST REV. 130GD05: 12/08/99 L.Z. document.xls Rev. A0 2/2
PROYECTO XXXXXXXX CALCULÓ: X.X
CLIENTE XXXXXXXX REVISÓ: X.X
ESTRUCTURA XXXXXXXX APROBÓ: X.X
PLANCHA BASE DE COLUMNA -ASD FECHA: XX/XX/XX
CASE 3 - B/6 < e <= B/2 THIS SHEET IS NOT VALID. SEE CASE 4
N= -97.5 cm
f1= -5.86 OK £ 0,70*f'c 00
f2= -6.41
a= 9.19 cm (Critical section)
-255 kg-cm (on critical section)
Err:502 mm Err:502Err:502
kg/cm2
kg/cm2
Mpl=
tpl=
Critical section
M
P
f1
a
N
B
f2
DISEÑO DE CONEXIONES
DISEÑO DE CONEXIONES
LAST REV. 130GD05: 12/08/99 L.Z. document.xls Rev. A0 2/2
LAST REV. 130GD05: 12/08/99 L.Z. document.xls Rev. A0 2/2
PROYECTO XXXXXXXX CALCULÓ: X.X
CLIENTE XXXXXXXX REVISÓ: X.X
ESTRUCTURA XXXXXXXX APROBÓ: X.X
PLANCHA BASE DE COLUMNA -ASD FECHA: XX/XX/XX
CASE 4 - e > B/2 "VALID CASE FOR DESIGN"
N'= 12.50 cm
B'= 30 cm
fp= 98 OK £ 0,70*f'c 00
N= 14.48 cm
a= 9.2 cm (critical section)
3261 kg-cm (critical section)
33 mm THICKNESS PLATE IS BIG ! USE STIFFENER
T= 14827 kg Resultant force in the anchor bolts
kg/cm2
Mpl=
tpl=
M
P
Critical section
fpT
a
N
B'
B
N'
DISEÑO DE CONEXIONES
DISEÑO DE CONEXIONES
LAST REV. 130GD05: 12/08/99 L.Z. document.xls Rev. A0 2/2
PROYECTO XXXXXXXX CALCULÓ: X.X
CLIENTE XXXXXXXX REVISÓ: X.X
ESTRUCTURA XXXXXXXX APROBÓ: X.X
PLANCHA BASE DE COLUMNA -ASD FECHA: XX/XX/XX
CASE 5 - Pu < 0 (UPLIFT) THIS SHEET IS NOT VALID. SEE CASE 4
g = 10.00 cm
tpl = 15 mm
DISEÑO DE CONEXIONES
C EED D C
B
F
bf
F
AP
d
g
DISEÑO DE CONEXIONES