82585499-Dig-Silent
-
Upload
jcrodriguez83 -
Category
Documents
-
view
24 -
download
0
Transcript of 82585499-Dig-Silent
DIgSILENT GridCode:
LVRT in Spain with
DIgSILENT GridCode
DIgSILENT Ibérica Madrid, 15 February 2012
DIgSILENT Ibérica S.L. 2
Spanish Study Case
Grid Code in Spain, published by the TSO Red Eléctrica de España:
“PROCEDIMIENTO DE OPERACIÓN 12.3: REQUISITOS DE RESPUESTA FRENTE A HUECOS DE TENSIÓN DE LAS INSTALACIONES EÓLICAS”
In revision:
“PROCEDIMIENTO DE OPERACIÓN 12.2: INSTALACIONES CONECTADAS A LA RED DE TRANSPORTE: REQUISITOS MÍNIMOS DE DISEÑO, EQUIPAMIENTO, FUNCIONAMIENTO Y SEGURIDAD Y PUESTA EN SERVICIO”
The document can be found at the website:
http://www.ree.es/operacion/procedimientos_operacion.asp
New version Nr 10 of the Spanish Wind Energy Association document (PVVC_v10) is published in response to the revision of the Spanish Grid Code (P.O.12.3 and draft version of P.O.12.2):
“PROCEDIMIENTOS DE VERIFICACIÓN, VALIDACIÓN Y CERTIFICACIÓN DE LOS REQUISITOS DEL P.O.12.3 SOBRE LA RESPUESTA DE LAS INSTALACIONES EÓLICAS Y FOTOVOLTAICAS ANTE HUECOS DE TENSIÓN”
The document can be found at the website:
http://www.aeeolica.org/
DIgSILENT Ibérica S.L. 3
Example of Dynamic Simulation Testing Procedure
Example of Dynamic Simulation Testing Procedure
STEP 1: Building the Wind farm dynamic model in DIgSILENT PowerFactory 14.1.2
NOTE: this example is built using templates in the global library;
Doubly Fed Induction Generators rated 6MW DFIG_WTG_6MW
Wind Farm Rated Power: 60MVA
Wind Farm Rated Voltage: 220kV
DIgSILENT Ibérica S.L. 4
Example of Dynamic Simulation Testing Procedure
STEP 2: Simulation of LVRT events according to the Spanish Grid Code:
EMT simulation - 10kHz time step
Voltage dip location: at the Wind Farm PCC, 220kV side
Voltage dip depth: 20% (3PH), 60% (2PH)
Voltage dip length: 500ms
DIgSILENT Ibérica S.L. 5
Example of Dynamic Simulation Testing Procedure
STEP 3: Export required signals from Plots in PowerFactory:
Ua(t), Ub(t), Uc(t) kV
Ia(t), Ib(t), Ic(t) kA
Textfile, white space/tab separated format
Voltage dip 60% (2PH) Voltage dip 20% (3PH)
DIgSILENT Ibérica S.L. 6
Example of Dynamic Simulation Testing Procedure
STEP 4: Analysis with DIgSILENT GridCode, checking for compliance.
STEP 4.1: File Types & Channels to read the results file.
DIgSILENT Ibérica S.L. 7
Example of Dynamic Simulation Testing Procedure
STEP 4: Analysis with DIgSILENT GridCode, checking for compliance.
STEP 4.1: File Types & Channels to read the results file.
STEP 4.2: Input of base values 60MVA and 220kV
DIgSILENT Ibérica S.L. 8
Example of Dynamic Simulation Testing Procedure
STEP 4: Analysis with DIgSILENT GridCode, checking for Grid Code compliance.
STEP 4.1: File Types & Channels to read the results file.
STEP 4.2: Input of base values 60MVA and 220kV
STEP 4.3: With the GridCode Editor, add the new procedure in the Spanish Grid Code (PVVC_v10_general).
DIgSILENT Ibérica S.L. 9
Example of Dynamic Simulation Testing Procedure
STEP 4: Analysis with DIgSILENT GridCode, checking for Grid Code compliance.
STEP 4.1: File Types & Channels to read the results file.
STEP 4.2: Input of base values 60MVA and 220kV
STEP 4.3: With the GridCode Editor, add the new procedure in the Spanish Grid Code (PVVC_v10_general).
- Add the zones and edit them. Add the list of limits for the different series.
DIgSILENT Ibérica S.L. 10
Example of Dynamic Simulation Testing Procedure
STEP 4: Analysis with DIgSILENT GridCode, checking for Grid Code compliance.
STEP 4.1: File Types & Channels to read the results file.
STEP 4.2: Input of base values 60MVA and 220kV
STEP 4.3: With the GridCode Editor, add the new procedure in the Spanish Grid Code (PVVC_v10_general).
- Edit the voltage dip shape for balanced dips.
DIgSILENT Ibérica S.L. 11
Example of Dynamic Simulation Testing Procedure
STEP 4: Analysis with DIgSILENT GridCode, checking for Grid Code compliance.
STEP 4.1: File Types & Channels to read the results file.
STEP 4.2: Input of base values 60MVA and 220kV
STEP 4.3: With the GridCode Editor, add the new procedure in the Spanish Grid Code (PVVC_v10_general).
- Edit the voltage dip shape for unbalanced dips.
DIgSILENT Ibérica S.L. 12
Example of Dynamic Simulation Testing Procedure
STEP 4: Analysis with DIgSILENT GridCode, checking for Grid Code compliance.
STEP 4.1: File Types & Channels to read the results file.
STEP 4.2: Input of base values 60MVA and 220kV
STEP 4.3: With the GridCode Editor, add the new procedure in the Spanish Grid Code (PVVC_v10_general).
- Edit the voltage support requirements.
DIgSILENT Ibérica S.L. 13
Example of Dynamic Simulation Testing Procedure
STEP 4: Analysis with DIgSILENT GridCode, checking for Grid Code compliance.
STEP 4.1: File Types & Channels to read the results file.
STEP 4.2: Input of base values 60MVA and 220kV
STEP 4.3: With the GridCode Editor, add the new procedure in the Spanish Grid Code (PVVC_v10_general).
- Define the plots that you want display.
- Select “Checked” option to display it.
- Save the Grid Code.
DIgSILENT Ibérica S.L. 14
Example of Dynamic Simulation Testing Procedure
STEP 4: Analysis with DIgSILENT GridCode, checking for Grid Code compliance.
STEP 4.1: File Types & Channels to read the results file.
STEP 4.2: Input of base values 60MVA and 220kV
STEP 4.3: With the GridCode Editor, add the new procedure in the Spanish Grid Code (PVVC_v10_general).
STEP 4.4: Click Analyze
DIgSILENT Ibérica S.L. 15
Example of Dynamic Simulation Testing Procedure
RESULTS
In the second tab, a table summarizes the fulfillment of requirements in Zones A, B, C and D.
THE “OK?” OPTION ACTIVATED MEANS THAT THE REQUIREMENT IS FULFILLED
DIgSILENT Ibérica S.L. 16
Example of Dynamic Simulation Testing Procedure
RESULTS
The “REE Voltage Dip Shape” graph allows to check if the voltage dip is “inside” the voltage dip rms envelope the wind farm can not disconnect and must provide reactive current support.
Voltage dip 60% (2PH) Voltage dip 20% (3PH)
DIgSILENT Ibérica S.L. 17
Example of Dynamic Simulation Testing Procedure
RESULTS
The “Ir/Itot(Vrms) Zone B” graph allows to check if the wind farm is injecting or consuming reactive power and fulfilling the requirements established by REE on the reactive current during the dip.
Voltage dip 60% (2PH) Voltage dip 20% (3PH)
DIgSILENT Ibérica S.L. 18
Example of Dynamic Simulation Testing Procedure
RESULTS
The “Power” graph allows to check the restoration of active power of the wind farm after the voltage dip.
Voltage dip 60% (2PH) Voltage dip 20% (3PH)
DIgSILENT Ibérica S.L. 19
Example of Dynamic Simulation Testing Procedure
REPORTING
Results are reported in Word format.
DIgSILENT Ibérica S.L. 20
Example of Dynamic Simulation Testing Procedure
REPORTING
Results are reported in Word format.
21
DIgSILENT GridCode Contact
Ana Morales/Xavier Robe
DIgSILENT Ibérica S.L.
Ribera del Loira, 46
28042 Madrid – Spain
Phone: +34 911273723/24
Email:
Website:
www.digsilent.com