    2/4

    NIVELES DE CONTAMINACION AMBIENTAL Y DISTANCIAS DE FUGA

    NORMA IEC 815:

    GUIDE FOR THE SELECTION OF INSULATORS IN RESPECT OF POLLUTED CONDITIONS

    TABLE I

    Pollution Level

    1)

    Distances from sea coast depend on the topography of the coastal area and on the extreme wind conditions.

    TABLE II

    1 I. Very Light 12 MUY BAJO

    2 II. Light 16 BAJO

    3 III. Mdium 20 MEDIO

    4 IV. Heavy 25 PESADO

    5 V. Very heavy 31 MUY PESADO1)

    2)

    Notes

    TABLE III

    Specific

    cree a e distances(see column 2 Table II) Salt fog method S.D.D.

    1) Layer Conductivity

    [mm/kV] [kg/m3] [gr/cm

    3] [S]

    16 5 to 14 0.03 to 0.06 15 to 20

    20 14 to 40 0.10 to 0.20 24 to 35

    25 40 to 112 0.30 to 0.60 36

    31 > 160 - -

    1)S.D.D. Salt Deposit Density.

    Examples of typical enviroaments

    Areas with high density of industries and suburbs of large cities with high density of heating plants producing pollution.

    Areas close to the sea or in say case exposed to relatively strong winds form the sea2)

    Areas generally of moderate extent, subjected to conductive dusts and to industrial smoke producing particularty thick

    conductive depposits.

    Areas generally of moderate extent, very close to the coast and exposed to sea-sprig or to very strong and poluting winds

    from the sea.

    Areas with high density of houses and/or industries but subjected to frequent winds and/or rainfall.

    Areas exposed to wind from the sea but not too close to the coast ( least several kilometres distant)2)

    All those areas shall be situated at leas: 10 km to 20 km from the sea and shall not be exposed to winds directly from the sea2)

    Areas with industries not producing particularty polluting smoke and/or with average density of houses equipped with

    heating plants.

    Areas without industries and with low density of houses equipped with heating plants.

    I. Light

    II. Mdium

    III. Heavy

    IV. Very heavy

    Desert areas, characterited by no rain for long periods exposed to strong winds carring sand and salt, and subjected to

    regular condensation.

    Areas with low density of industries or houses but subjected fruquent winds and/or rainfall.

    Agricultural areas1)

    Mountainous areas

    Severity withstand values it the phase to earth voltaje

    Solid la er methods

    Artificial Pollution Test

    Use of fertilzens b s ra in , or the burain of cro

    Pollution Level

    For the actual creepage distance, the especified manufacturing tolerances are aplicable (see IEC Publication 273: Dimensions of Indoor and

    Outdoor Post Insulators and Post Insutator Units for for Systems with Nominal Voltajes Greater than 1000 V, IEC Publication 305:

    Charasteristics of String Insulator Units of the Cap and Pin Type. IEC Publication 433: Characteristics of String Insulator Units of the Long

    Rod Type, and IEC Publication 720: Characteristics of Line Post Insulators).

    2 . In the case of exceptional pollution severity, a especific nominal creepage distance of 31 mm/kV may not be adequate.

    Depending on service experience and/or on laboratory test results, a higher value of specific creepage distance can be used,

    but in some instances tha practicability of washing or greasing (see Appendix B) may have to be considered.

    Ratio leakage distance measured between phase and earth over the r.m.s. phase value of the highest voltge for the equipment ( see IEC

    publication 71-1)

    Pollution Level

    1. In very lightly polluted areas, specific nominal creepage distances lower than 16 mm/kV can be used depending on

    service experience 12 mm/kV seems to be a lower limit.

    [mm/kV2)

    ]

    Minimum nominal specific creepage distance1)

  • 8/13/2019 Anexo 3 - Coordinacin de aislamiento

    3/4

    CARACTERISTICAS DE LOS AISLADORES

    AISLADORES TIPO PINVoltaje de Flameo de Baja Frecuencia Voltaje de Flameo Crtico Longitud de Mnima Tensin

    Clase a Frecuencia de Servicio Al Impulso Lnea de Fuga Perforacin a

    ANSI Seco Hmedo Positivo Negativo Frec. de Servicio

    [kVrms] [kVrms] [kVpico] [kVpico] [mm] [kVrms]

    1 55-1 35 20 50 70 102 50 37.5

    2 55-2 50 25 75 95 127 70 52.5

    3 55-3 65 35 100 130 178 90 67.5

    4 55-4 70 40 110 140 229 115 86.255 55-5 85 45 140 170 305 115 86.25

    6 56-1 95 60 150 190 330 130 97.5

    7 56-2 110 70 175 225 432 145 108.75

    8 56-3 125 80 200 265 533 165 123.75

    9 56-4 140 95 225 310 685 185 138.75

    10 56-5 175 125 275 340 864 225 168.75

    11 POLIM_12kV_C 70 50 115 160 300

    12 POLIM_12kV_L 70 50 115 160 372

    13 POLIM_15kV_C 75 50 120 170 375

    14 POLIM_15kV_L 75 50 120 170 465

    15 POLIM_24kV_C 80 70 120 170 600

    16 POLIM_28kV 130 100 225 265 620

    17 PR15/LP15 95 75 150 180 400

    18 PR35/LP35 115 90 190 225 555

    19 KL-138H-BS-31 460 375 735 3462

    20 KL-138H-BS-34 500 405 795 3795

    21 KL-138H-BS-37 540 440 860 4128

    22 KL-161H-BS-40 580 470 920 4460

    23 KL-161H-BS-43 625 510 990 4793

    24 KL-161H-BS-46 670 545 1055 5126

    25 KL-230H-BS-49 715 585 1120 5459

    26 KL-230H-BS-52 760 620 1185 5791

    27 KL-230H-BS-55 805 655 1250 6124

    AISLADORES TIPO SUSPENSION O ANCLAJEN Voltaje de Flameo de Baja Frecuencia Voltaje de Flameo Crtico Longitud de Mnima Tens in

    Clase de a Frecuencia de Servicio Al Impulso Lnea de Fuga Perforacin a

    ANSI Aisladores Seco Hmedo Positivo Negativo Frec. de Servicio

    [kVrms] [kVrms] [kVpico] [kVpico] [mm] [kVrms]

    1 52-3 /1U 1 80 50 125 130 292 110

    2 52-3 /2U 2 155 90 245 255 584 110

    3 52-3 /3U 3 215 130 341 355 876 110

    4 52-3 /4U 4

    5 52-4 /1U 1 80 50 125 130 292 110

    6 52-4 /2U 2 155 90 245 255 584 110

    7 52-4 /3U 3 215 130 345 355 876 110

    8 52-4 /4U 4

    9 52-4 /5U 5

    10 POLIM_12kV_C 1 28 60 300

    11 POLIM_12kV_L 1 28 75 372

    12 POLIM_17kV_C 1 38 75 427.5

    13 POLIM_17kV_L 1 38 95 542.5

    14 POLIM_24kV_C 1 50 95 600

    15 POLIM_28kV 1 130 100 225 265 620

    16 RP4 1 72 59 107 113 370

    17 RP10 1 125 105 240 250 900

    18 RP14 1 160 145 280 316 1300

    19 KL69HBS 13 1 215 170 355 1466

    20 KL69HBS 16 1 260 205 425 1798

    21 KL69HBS 19 1 300 235 485 2131

    22 KL-138V-BS-31 1 460 375 735 3462

    23 KL-138V-BS-34 1 500 405 795 3795

    24 KL-138V-BS-37 1 540 440 860 4128

    25 KL-161V-BS-40 1 580 470 920 4460

    26 KL-161V-BS-43 1 625 510 990 4793

    27 KL-161V-BS-46 1 670 545 1055 5126

    28 KL-230V-BS-49 1 715 585 1120 5459

    29 KL-230V-BS-52 1 760 620 1185 5791

    30 KL-230V-BS-55 1 805 655 1250 6124

    NOTAS: Aisladores CLASE ANSI 52-3, llamados Aisladores de Suspensin Tipo Cuenca y Bola ("Ball and Socket").

    Aisladores CLASE ANSI 52-1 y 52-4, llamados Aisladores de Suspensin Tipo Clevis.

    NIVELES BASICOS DE AISLAMIENTO NORMALIZADOS

    TENSION NOMINAL MAXIMA TENSION NIVEL BASICO DE AISLAMIENTO

    TRIFASICO DEL SISTEMA O TRIFASICA DEL EQUIPO ALTITUD REFERIDO AL NIVEL DEL MAR

    EQ. TRIFASICO DEL SISTEMA EQ. TRIFASICO DEL EQUIPO [m.s.n.m.] A FREC. DE SERVICIO AL IMPULSO[kVrms] [kVrms] [kVrms] [kVpico]

    1 LP.RP. NIVELES BASICOS DE AISLAMIENTO NORMALIZADOS DE REDES DE DISTRIBUCION

    2 0.38 a 0.44 1 0000 - 4500 2.5 -

    3 7.62 12 0000 - 1000 28 75

    4 10 12 0000 - 1000 28 75

    5 13.2 14.5 0000 - 1000 38 95

    6 22.9 25 0000 - 1000 50 125

    7 33 36 0000 - 1000 70 170

    8 L.S.T. NIVELES BASICOS DE AISLAMIENTO PARA LINEAS DE TRANSMISION

    9 44 52 0000 - 1000 95 250

    10 50 52 0000 - 1000 95 250

    11 60 72.5 0000 - 1000 140 325

    L

    I

    N

    E

    A

    S

    D

    E

    T

    R

    A

    N

    S

    M

    I

    S

    I

    O

    N

    L

    I

    N

    E

    A

    S

    D

    E

    T

    R

    A

    N

    S

    M

    I

    S

    I

    O

    N

    L

    I

    N

    E

    A

    S

    D

    E

    D

    I

    S

    T

    R

    I

    B

    U

    C

    I

    O

    N

    L

    I

    N

    E

    A

    S

    D

    E

    D

    I

    S

    T

    R

    I

    B

    U

    C

    I

    O

    N

  • 8/13/2019 Anexo 3 - Coordinacin de aislamiento

    4/4

    1

    MINISTERIO DE ENERGIA Y MINAS Consorcio Grupo 12DIRECCION GENERAL DE ELECTRIFICACION RURAL ANEXO 04 -

    ELECTRIFICACION RURAL GRUPO 12 EN 11 DEPARTAMENTOSSELECCION DEL NIVEL DE AISLAMIENTO Y DE AISLADORES PARA

    LINEAS Y REDES PRIMARIAS EN 22.9 KV

    CONDICIONES DE OPERACIN DEL SISTEMA ELECTRICO

    Tensin nominal de servicio entre fases [kV] 22.9

    Tensin mxima de servicio entre fases [kV] 25

    Punto ms alto de la zona de Proyecto [m.s.n.m.] 4200

    Temperatura media [C] 10

    Nivel de contaminacin ambiental [Nivel] MUY BAJO

    Tipo de Conexin del Neutro [Tipo] Neutro Aterrado

    Nivel Cerunico [Torm./Ao] 40

    1. SELECCION DEL NIVEL DE AISLAMIENTO

    NIVEL BASICO DE AISLAMIENTO NORMALIZADO A NIVEL DEL MARTENSION NOMINAL MAXIMA TENSION NIVEL BASICO DE AISLAMIENTO

    TRIFASICO DEL SISTEMA O TRIFASICA DEL EQUIPO ALTITUD REFERIDO AL NIVEL DEL MAR EQ. TRIFASICO DEL SISTEMA EQ. TRIFASICO DEL EQUIPO A FRECUENCIA DE SERVICIO AL IMPULSO

    [kVrms] [kVrms] [m.s.n.m.] [kVrms] [kVpico]

    22.9 25 0 - 1000 50 125

    FACTORES DE CORRECCIONFACTORES DE CORRECCION FACTOR

    Norma IEC 137 DE CORRECCIONm.s.n.m. POR ALTITUD POR TEMPERATURA RESULTANTE

    ### I 2400 1.14 1.00 1.14

    ### II 2700 1.17 1.00 1.17

    ### III 3000 1.20 1.00 1.20

    ### IV 3600 1.25 1.00 1.25

    ### V 4800 1.35 1.00 1.35

    2. CRITERIOS PARA LA SELECCION DE AISLADORESA). SOBRETENSIONES EXTERNAS (NORMA I.E.C. 71-1)

    NIVEL BASICO DE AISLAMIENTO AISLADORES AISLADORESALTITUD A FRECUENCIA AL IMPULSO TIPO PIN TIPO SUSPENSION

    DE SERVICIO POSITIVO Clase ANSI POSITIVO POLIMERICO

    m.s.n.m. [kVeficaz] [kVpico] [kVpico] 8 [kVpico] 15

    I 2400 57 143 200 OK 225 OKII 2700 59 146 200 OK 225 OKIII 3000 60 150 200 OK 225 OKIV 3600 63 156 200 OK 225 OK

    V 4800 68 169 200 OK 225 OK

    B). SOBRETENSIONES INTERNAS (NORMA ALEMANA VDE)

    VDE AISLADORES AISLADORESALTITUD TENSION DISRUPTIVA BAJO TIPO PIN TIPO SUSPENSION

    LLUVIA A 60 Hz CALCULADO POSITIVO Clase ANSI POSITIVO POLIMERICO

    m.s.n.m. [kVeficaz] [kVeficaz] 8 [kVpico] 15

    I 2400 65 80 OK 100 OKII 2700 67 80 OK 100 OKIII 3000 68 80 OK 100 OKIV 3600 71 80 OK 100 OKV 4800 75 80 OK 100 OK

    NOTA: La Tensin Disruptiva Bajo Lluvia a Frecuencia de Servicio que debe tener un aislador, no deber ser menor a : UC= 2.1(U*FC+ 5) ... [kV]

    C). CONTAMINACION AMBIENTAL (NORMA I.E.C. 815)

    Minima Distancia de Fuga Especfica Nominal: MUY BAJO 12 [mm/kV]

    LONGITUD DE LINEA DE FUGA POR AISLADORES AISLADORESALTITUD CONTAMINACION AMBIENTAL CALCULADO TIPO PIN TIPO SUSPENSION

    1 LINEA DE FUGA Clase ANSI LINEA DE FUGA POLIMERICO

    m.s.n.m. [mm/kV] [mm] [mm] 8 [mm] 15

    ### I 2400 12 342 533 OK 620 OK### II 2700 12 351 533 OK 620 OK### III 3000 12 360 533 OK 620 OK### IV 3600 12 375 533 OK 620 OK### V 4800 12 405 533 OK 620 OK

    NOTA: En la zona de proyecto, se tiene un nivel de contaminacin del tipo III, Segn la Tabla II, de la Norma IEC-815al cual le corresponde una mnima distancia de fuga especfica nominal de: 12 [mm/kV]