b = 10.00 cm d = 17.00 cm f'c = 210.00 kg/cm² fy = 4200.00 kg/cm² Mu = 0.44 Tn.m RESULTADOS w = 0.085 p = 0.0042 As Calculado = 0.72 cm² AS min = 0.31 cm² USAMOS = 0.72 cm² VARILLAS A USAR TRAMO 1 - 2 # varillas Diametro ARA 1 1/2 pulg 1.27 1.27 VERDADERO Apoyo 1 1 Ø 3/8" Tramo 1 - 2 1 Ø 1/2" Apoyo 2 1 Ø 1/2" Tramo 2 - 3 1 Ø 1/2" Apoyo 3 1 Ø 1/2" Tramo 3 - 4 1 Ø 1/2" Apoyo 4 1 Ø 1/2" Tramo 4- 5 1 Ø 1/2" Apoyo 4 1 Ø 3/8" Diseño Losa Aligerada
-
Upload
anthony-villegas-calero -
Category
Documents
-
view
229 -
download
0
Transcript of losa aligerada 2.pdf
-
b = 10.00 cmd = 17.00 cmf'c = 210.00 kg/cmfy = 4200.00 kg/cmMu = 0.44 Tn.m
RESULTADOSw = 0.085p = 0.0042
As Calculado = 0.72 cmAS min = 0.31 cmUSAMOS = 0.72 cm
VARILLAS A USAR TRAMO 1 - 2 # varillas Diametro ARA
1 1/2 pulg 1.271.27 VERDADERO
Apoyo 1 1 3/8"Tramo 1 - 2 1 1/2" Apoyo 2 1 1/2"Tramo 2 - 3 1 1/2" Apoyo 3 1 1/2"Tramo 3 - 4 1 1/2" Apoyo 4 1 1/2"Tramo 4- 5 1 1/2" Apoyo 4 1 3/8"
Diseo Losa Aligerada
-
EJE DE REFERENCIA DEL PLANO
1 2 3 4 5METRADO DE CARGAS
tn/m2 m tn/mpeso propio aligerado 0.3 0.4 0.12
piso terminado 0.1 0.4 0.04CM 0.16
Wcv (departamentos) 0.2 0.4 0.08CV 0.08
Wu= 0.36 tn/m