PROYECTO INSTALACIÓN ELÉCTRICA DE BAJA TENSIÓN
INSTALACIÓN ALUMBRADO EXTERIOR URBANIZACIÓN TANATORIO BENICÀSSIM (CASTELLÓN)
1 V12/007-ALUM
1 MEMORIA.................................................................................................................... 3
1.1 EE-7 LOCALES (EXCLUIDOS LOS DESTINADOS A USOS INDUSTRIALES Y A
VIVIENDAS).......................................................................................................................... 3
1.2 OBJETO DEL PROYECTO..................................................................................... 5
1.3 PROMOTOR DE LA INSTALACION ...................................................................... 5
1.4 REGLAMENTACION Y NORMAS TECNICAS CONSIDERADAS......................... 5
1.5 EMPLAZAMIENTO DE LAS INSTALACIONES ..................................................... 7
1.6 POTENCIA PREVISTA ........................................................................................... 7
1.7 DESCRIPCION DEL LOCAL .................................................................................. 7
1.8 DESCRIPCION DE LAS INSTALACIONES DE ENLACE ...................................... 7
1.9 DESCRIPCION DE LA INSTALACIÓN INTERIOR............................................... 10
1.10 SUMINISTROS COMPLEMENTARIOS................................................................ 18
1.11 ALUMBRADO DE EMERGENCIA........................................................................ 18
1.12 EQUIPOS DE CONEXIÓN DE ENERGÍA REACTIVA ........................................................ 18
1.13 SISTEMA DE SEÑALIZACIÓN, ALARMA, CONTROL REMOTO Y COMUNICACIÓN. ............ 19
1.14 LINEA DE PUESTA A TIERRA............................................................................. 19
1.15 RED DE EQUIPOTENCIALIDAD.......................................................................... 21
1.16 INSTALACIÓN CON FINES ESPECIALES .......................................................... 21
2 CALCULOS JUSTIFICATIVOS................................................................................. 22
2.1 TENSIÓN NOMINAL Y CAIDA DE TENSIÓN MÁXIMA ADMISIBLE.-................. 22
2.2 FORMULAS UTILIZADAS.................................................................................... 23
2.3 POTENCIAS ......................................................................................................... 25
2.4 CÁLCULOS LUMINOTÉCNICOS......................................................................... 25
2.5 CÁLCULOS ELÉCTRICOS: ALUMBRADO Y FUERZA MOTRIZ.-...................... 26
2.6 CÁLCULO DEL SISTEMA DE PROTECCIÓN CONTRA CONTACTOS
INDIRECTOS.- .................................................................................................................... 32
PROYECTO INSTALACIÓN ELÉCTRICA DE BAJA TENSIÓN
INSTALACIÓN ALUMBRADO EXTERIOR URBANIZACIÓN TANATORIO BENICÀSSIM (CASTELLÓN)
2 V12/007-ALUM
2.7 CÁLCULO DEL AFORO DEL LOCAL EN RELACION CON LA ITC-BT-28 ........ 35
3 ANEXOS.................................................................................................................... 37
3.1 CALCULOS LUMINOTECNICOS. ........................................................................ 37
4 PLIEGO DE CONDICIONES ..................................................................................... 39
4.1 CONDICIONES DE LOS MATERIALES............................................................... 39
4.2 NORMAS DE EJECUCIÓN DE LAS INSTALACIONES.-..................................... 56
4.3 PRUEBAS REGLAMENTARIAS.- ........................................................................ 61
4.4 CONDICIONES DE USO, MANTENIMIENTO Y SEGURIDAD.-........................... 62
4.5 CERTIFICADOS Y DOCUMENTACIÓN ............................................................... 63
4.6 LIBRO DE ÓRDENES........................................................................................... 64
5 PRESUPUESTO........................................................................................................ 65
5.1 MEDICIONES........................................................................................................ 65
5.2 PRESUPUESTO ................................................................................................... 69
5.3 RESUMEN DEL PRESUPUESTO ........................................................................ 73
6 PLANOS .................................................................................................................... 75
PROYECTO INSTALACIÓN ELÉCTRICA DE BAJA TENSIÓN
INSTALACIÓN ALUMBRADO EXTERIOR URBANIZACIÓN TANATORIO BENICÀSSIM (CASTELLÓN)
3 V12/007-ALUM
1 MEMORIA
1.1 EE-7 LOCALES (EXCLUIDOS LOS DESTINADOS A USOS INDUSTRIALES Y A VIVIENDAS)
EE-7 LOCALES (EXCLUIDOS LOS DESTINADOS A USOSINDUSTRIALES Y A VIVIENDAS)
1. MEMORIA
A TITULARAPELLIDOS Y NOMBRE O RAZÓN SOCIAL
DNI-NIF
DOMICILIO (calle o plaza y número)
CP
MUNICIPIO
PROVINCIA
TELÉFONO
FAX
B EMPLAZAMIENTO Y USO DE LA INSTALACIÓNEMPLAZAMIENTO
MUNICIPIO
PROVINCIA
CP
TELÉFONO
USO AL QUE SE DESTINA (ITC-BT-04 / 3.1 )
CONTRATO DE MANTENIMIENTO SI NO
POTENCIA PREVISTA (Kw)
SUPERFICIE (m2)/AFORO /
C MEMORIA DESCRIPTIVA (MARQUE Y CUMPLIMENTE SOLO LAS CASILLAS DE AQUELLOS ELEMENTOS CUYA INSTALACIÓN SE VAYA AEJECUTAR EN BASE A LA PRESENTE MEMORIA TÉCNICA DE DISEÑO)
C-1 CAJA GENERAL DE PROTECCIÓNEMPLAZAMIENTO
ACOMETIDAAÉREA
ACOMETIDASUBTERRÁNEA
MONTAJESUPERFICIAL
NICHOENPARED
ESQUEMA NORMALIZADO TIPO
INTENSIDADNOMINAL CGP A INTENSIDAD
FUSIBLES AC-2 LÍNEA GENERAL DE ALIMENTACIÓN
CABLES: DENOMINACIÓN,CONDUCTOR Y SECCIONES
CONDUCTOR DE PROTECCIÓN
SISTEMA DE INSTALACIÓN
DIMENSIONES DE:TUBO, CANAL OCONDUCTO
C-3 CONTADORES
COLOCACIÓN EN FORMAINDIVIDUAL
EN CAJA DE PROTECCIÓNY MEDIDA (CPM)
EN OTRO LUGAR
COLOCACIÓN EN FORMACONCENTRADA EN LOCAL EN ARMARIO
NÚMERO DECENTRALIZACIONES DE
CONTADORES NÚMERO TOTAL DE
CONTADORES
INTERRUPTOR GENERALDE MANIOBRA
INTENSIDADNOMINAL A EXTINTOR
MÓVILEFICACIA DEL EXTINTOR MÓVIL
C-4 DERIVACIONES INDIVIDUALES (DESCRIBIR LAS CARACTERÍSTICAS DE LOS DISTINTOS TIPOS)
SISTEMAS DE INSTALACIÓN
DIMENSIONES DE:TUBOS, CANALESO CONDUCTOS
Derivación GRADO DE ELECTRIFICACIÓN O USO CABLES: TIPO O DENOMINACIÓN UNE, MATERIAL DEL CONDUCTOR Y SECCIONES FUSIBLES DE
Individual DEL LOCAL / INSTALACIÓN (1)(POTENCIA PREVISTA) CONDUCTORES ACTIVOS CONDUCTOR DE PROTECCIÓN
SEGURIDAD (A)
LOCAL 1
LOCAL 2
OTROS USOS
C-5 RELACIÓN DE INSTALACIONES ESPECIFICAS
ASCENSORES
BOMBAS DEAGUA
OTROS
OTROS
C-6 PRESUPUESTO TOTAL
Servici Territorial d’Indústria
CONSELLERIA D'ECONOMIA, INDÚSTRIA I COMERÇ
PROYECTO INSTALACIÓN ELÉCTRICA DE BAJA TENSIÓN
INSTALACIÓN ALUMBRADO EXTERIOR URBANIZACIÓN TANATORIO BENICÀSSIM (CASTELLÓN)
5 V12/007-ALUM
1.2 OBJETO DEL PROYECTO
El Urbanizador de la Urbanización del Tanatorio de Benicàssim, desea dotar de alumbrado
público las aceras y zona de aparcamiento objeto de dicha urbanización, por lo que se
redacta el presente proyecto técnico, que servirá de base para definir las especificaciones
técnicas y las condiciones de ejecución para conseguir una iluminación adecuada así como
la legalización de las citadas instalaciones.
El suministro eléctrico se realizara desde la hornacina prevista para tal fin en el Proyecto de
Urbanización, situada junto al centro maniobra.
1.3 PROMOTOR DE LA INSTALACION
El promotor de la obra señalada anteriormente será:
Titular Ajuntament de Benicàssim
Dirección Calle Médico Segarra nº 4
12.560 - Benicàssim
NIF P-1202800-G
1.4 REGLAMENTACION Y NORMAS TECNICAS CONSIDERADAS
El presente proyecto se ajustará en su contenido a lo dispuesto en la resolución de 20 de
junio de 2003, por el que se modifican los anexos de las ordenes de 17 de julio de 1989 y de
12 de febrero de 2001, de la Consellería de Industria, Comercio y Turismo por la que se
establece un contenido mínimo en proyectos de industrias e instalaciones industriales, así
como a la legislación que se detalla a continuación:
• Reglamento Electrotécnico para Baja Tensión e Instrucciones Técnicas
Complementarias (Real Decreto 842/2002 de 2 de Agosto de 2002).
• Real Decreto 1890/2008, de 14 de noviembre, por el que se aprueba el Reglamento de
Eficiencia Energética en Instalaciones de Alumbrado Exterior y sus Instrucciones
Técnicas Complementarias EA-01 a EA-07.
• Instrucciones para Alumbrado Público Urbano editadas por la Gerencia de Urbanismo
del Ministerio de la Vivienda en el año 1.965.
PROYECTO INSTALACIÓN ELÉCTRICA DE BAJA TENSIÓN
INSTALACIÓN ALUMBRADO EXTERIOR URBANIZACIÓN TANATORIO BENICÀSSIM (CASTELLÓN)
6 V12/007-ALUM
• Normas Tecnológicas de la Edificación NTE IEE – Alumbrado Exterior (B.O.E. 12.8.78).
• Normas UNE 20.324 y UNE-EN 50.102 referentes a Cuadros de Protección, Medida y
Control.
• Normas UNE-EN 60.598-2-3 y UNE-EN 60.598-2-5 referentes a luminarias y proyectores
para alumbrado exterior.
• Real Decreto 2642/1985 de 18 de diciembre (B.O.E. de 24-1-86) sobre Homologación de
columnas y báculos.
• Real Decreto 401/1989 de 14 de abril, por el que se modifican determinados artículos del
Real Decreto anterior (B.O.E. de 26-4-89).
• Orden de 16 de mayo de 1989, que contiene las especificaciones técnicas sobre
columnas y báculos (B.O.E. de 15-7-89).
• Orden de 12 de junio de 1989 (B.O.E. de 7-7-89), por la que se establece la certificación
de conformidad a normas como alternativa de la homologación de los candelabros
metálicos (báculos y columnas de alumbrado exterior y señalización de tráfico).
• Real Decreto 1955/2000 de 1 de Diciembre, por el que se regulan las Actividades de
Transporte, Distribución, Comercialización, Suministro y Procedimientos de Autorización
de Instalaciones de Energía Eléctrica.
• Normas particulares y de normalización de la Cía. Suministradora de Energía Eléctrica.
• Ley 31/1995, de 8 de noviembre, de Prevención de Riesgos Laborales.
• Real Decreto 1627/1997 de 24 de octubre de 1.997, sobre Disposiciones mínimas de
seguridad y salud en las obras.
• Real Decreto 485/1997 de 14 de abril de 1997, sobre Disposiciones mínimas en materia
de señalización de seguridad y salud en el trabajo.
• Real Decreto 1215/1997 de 18 de julio de 1997, sobre Disposiciones mínimas de
seguridad y salud para la utilización por los trabajadores de los equipos de trabajo.
• Real Decreto 773/1997 de 30 de mayo de 1997, sobre Disposiciones mínimas de
seguridad y salud relativas a la utilización por los trabajadores de equipos de protección
individual.
PROYECTO INSTALACIÓN ELÉCTRICA DE BAJA TENSIÓN
INSTALACIÓN ALUMBRADO EXTERIOR URBANIZACIÓN TANATORIO BENICÀSSIM (CASTELLÓN)
7 V12/007-ALUM
• Recomendaciones del Comité Internacional para el Alumbrado y del Ministerio de
Fomento.
1.5 EMPLAZAMIENTO DE LAS INSTALACIONES
La instalación esta situada en la Calle Santa Agueda, a la altura del tanatorio municipal,
nº 101 (junto al cementerio municipal), situada en el término municipal de Benicàssim.
1.6 POTENCIA PREVISTA
El interruptor de cabecera tiene un poder de corte de 25 amperios para una tensión de
400 V, por lo que la potencia máxima admisible por densidad de corriente del interruptor
general, es de 17,32 Kw.
1.7 DESCRIPCION DEL LOCAL
1.7.1 Características
La instalación, alumbrado exterior, esta situada en la Calle Santa Agueda, a la altura del
tanatorio municipal, nº 101 (junto al cementerio municipal), situada en el término municipal
de Benicàssim, dotando de alumbrado las aceras y zonas de aparcamiento de los alrededores
del tanatorio municipal.
1.8 DESCRIPCION DE LAS INSTALACIONES DE ENLACE
1.8.1 Centro de transformación
Dadas las necesidades previstas no será necesario instalar un Centro de Transformación,
realizándose el suministro de energía a partir de las redes de Iberdrola S.A. a la tensión de
servicio de 400/230 V
1.8.2 Caja general de protección
El origen de la instalación será la Caja General de Protección, cuyas características
constructivas estarán de acuerdo con la normativa particular de la empresa suministradora
de energía eléctrica.
Dentro de la Caja y como parte de la misma se instalarán los conductores de fase de los
correspondientes cortocircuitos fusibles de Intensidad y poder de corte adecuados a las
PROYECTO INSTALACIÓN ELÉCTRICA DE BAJA TENSIÓN
INSTALACIÓN ALUMBRADO EXTERIOR URBANIZACIÓN TANATORIO BENICÀSSIM (CASTELLÓN)
8 V12/007-ALUM
corrientes de servicios, así mismo se dispondrá de los bornes de conexión de neutro y de
puesta a tierra, dicha caja se ubicará en la hornacina, homologada y precintable.
1.8.3 Equipos de medida
Se instalara un contador monofasico equipado con fusible de seguridad para el conductor de
fase, con la adecuada capacidad de corte y precintados por la empresa suministradora.
1.8.4 Línea general de alimentación / Derivación individual
Para un solo abonado con un solo contador, la línea repartidora y la derivación individual se
identifican confundiéndose en una misma línea, que en este caso adopta las funciones de
derivación individual. Esta línea se protegerá mediante los correspondientes fusibles
situados en la Caja General de Protección que cumplirán la función de fusibles de
seguridad.
Normalmente enlazará la Caja General de Protección con el equipo de medida, en este caso
por tratarse de un único abonado coincidirán con la derivación individual. Será lo más corta y
rectilínea posible.
En el caso que nos ocupa esta línea enlazará la centralización de contadores con los
dispositivos privados de mando y protección de la instalación, situados en el Cuadro General
de Distribución.
1.8.4.1 Descripción: longitud, sección, diámetro y tubo Los conductores de la acometida son del tipo 3X240+1*150 mm2 RV.
Los conductores de la línea general de alimentación / derivación individual son del tipo
4x10 mm2 RV Z1.
1.8.4.2 Canalización.- La acometida será subterránea con cables aislados, y se realizará de acuerdo con las
prescripciones particulares de la compañía suministradora, aprobadas según lo previsto en
este Reglamento para este tipo de instalaciones.
La acometida finalizará en la caja general de protección y a continuación de la misma se
dispondrá el equipo de medida.
PROYECTO INSTALACIÓN ELÉCTRICA DE BAJA TENSIÓN
INSTALACIÓN ALUMBRADO EXTERIOR URBANIZACIÓN TANATORIO BENICÀSSIM (CASTELLÓN)
9 V12/007-ALUM
1.8.4.3 Conductores.- Esta línea está realizada con conductores de cobre, no propagadores del incendio y con
emisión de humos y opacidad reducida, y con nivel de aislamiento de 0’6/1 kV. La sección
de los conductores (según se desprende de los cálculos) es de 10 mm2 para fases.
1.8.4.4 Tubos protectores Se utilizaran tubos de 110 mm de diámetro.
El control y la maniobra se realizaran desde un cuadro general de distribución, situado junto
a la hornacina de contadores, y este a su vez junto a la caja general de protección, situados
en el lugar indicado en los planos.
1.8.4.5 Conductor de protección El conductor de protección será igualmente de cobre con el mismo aislamiento y sección
que los conductores activos hasta una sección de estos de 16 mm2.
Para conductores activos entre 25 y 35 mm2, el de protección será de 16 mm2 y la mitad de
la sección que en activos para secciones mayores de 35 mm2.
Irá instalado en el interior del mismo tubo protector que los conductores activos.
PROYECTO INSTALACIÓN ELÉCTRICA DE BAJA TENSIÓN
INSTALACIÓN ALUMBRADO EXTERIOR URBANIZACIÓN TANATORIO BENICÀSSIM (CASTELLÓN)
10 V12/007-ALUM
1.9 DESCRIPCION DE LA INSTALACIÓN INTERIOR
El sistema de iluminación adoptado es acorde con el entorno, siguiendo las directrices
marcadas por los técnicos municipales a pero cumpliendo con el Real Decreto 1890/2008,
de 14 de noviembre, por el que se aprueba el Reglamento de Eficiencia Energética en
Instalaciones de Alumbrado Exterior y sus Instrucciones Técnicas Complementarias
La iluminación se realizará mediante luminarias Indalux, modelo IQV, con lámparas de
VSAP de 100 W sobre columnas de poliéster reforzado con fibra de vidrio, de 7 metros de
altura
Se ha optado por emplear lámparas de vapor de sodio de alta presión de 100 W de
potencia, y equipos de encendido de alto factor con dos niveles de potencia.
1.9.1 Clasificación y características de las instalaciones según riesgo de las dependencias de los locales
1.9.1.1 Locales de pública concurrencia (ITC-BT-28). Según la Instrucción ITC-BT-28 del Reglamento Electrotécnico de Baja Tensión, esta
actividad no se encuentra sujeta a esta clasificación.
1.9.1.2 Locales con riesgo de incendio o explosión (ITC-BT-29). Según la Instrucción ITC-BT-28 del Reglamento Electrotécnico de Baja Tensión, esta
actividad no se encuentra sujeta a esta clasificación.
1.9.1.3 Locales húmedos (ITC-BT-30) Según la Instrucción ITC-BT-30 del Reglamento Electrotécnico de Baja Tensión, esta
actividad cumplirá las prescripciones para locales húmedos.
1.9.1.4 Locales mojados (ITC-BT-30) Según la Instrucción ITC-BT-30 del Reglamento Electrotécnico de Baja Tensión, los aseos y
las instalaciones a la intemperie se encuentran clasificados como local “mojado” por lo que
seguirá lo indicado en dicha Instrucción en lo referente a condiciones particulares.
Las canalizaciones serán estancas utilizándose, para terminales, empalmes y conexión de
las mismas, sistemas ó dispositivos que presenten el grado de protección correspondiente a
las proyecciones de agua, IPX4. Sus cubiertas y las partes accesibles de los órganos de
accionamiento no serán metálicas.
PROYECTO INSTALACIÓN ELÉCTRICA DE BAJA TENSIÓN
INSTALACIÓN ALUMBRADO EXTERIOR URBANIZACIÓN TANATORIO BENICÀSSIM (CASTELLÓN)
11 V12/007-ALUM
Los tubos para alojamiento de los conductores serán estancos, preferentemente aislantes y
en caso de ser metálicos deberán estar protegidos contra la corrosión. Se colocarán en
montaje superficial y los tubos metálicos se dispondrán, como mínimo, a 2 cm de las
paredes.
Los receptores de alumbrado tendrán sus piezas metálicas bajo tensión, protegidos contra
las proyecciones de agua. La cubierta de los portalámparas será en su totalidad de materia
aislante hidrófuga, salvo cuando se instalen en el interior de cubiertas estancas destinadas a
los receptores de alumbrado.
Las tomas de corriente serán del tipo protegido contra las proyecciones de agua o bien se
instalarán en el interior de cajas que les proporcionen una protección equivalente.
Los conductores serán rígidos, aislados, de 750V de tensión nominal, como mínimo, bajo
tubos protectores o bien conductores rígidos aislados armados de 1000V de tensión
nominal, como mínimo, fijados directamente sobre las paredes o colocados en el interior de
huecos de la construcción.
1.9.1.5 Locales con riesgo de corrosión (ITC-BT-30) Según la Instrucción ITC-BT-30 del Reglamento Electrotécnico de Baja Tensión, esta
actividad no se encuentra sujeta a esta clasificación.
1.9.1.6 Locales polvorientos sin riesgo de incendio o explosión (ITC-BT-29) Según la Instrucción ITC-BT-30 del Reglamento Electrotécnico de Baja Tensión, esta
actividad no se encuentra sujeta a esta clasificación.
1.9.1.7 Locales a temperatura elevada (ITC-BT-30) Según la Instrucción ITC-BT-30 del Reglamento Electrotécnico de Baja Tensión, esta
actividad no se encuentra sujeta a esta clasificación.
1.9.1.8 Locales a muy baja temperatura (ITC-BT-30) Según la Instrucción ITC-BT-30 del Reglamento Electrotécnico de Baja Tensión, esta
actividad no se encuentra sujeta a esta clasificación.
1.9.1.9 Locales en los que existan baterías de acumuladores (ITC-BT-30) Según la Instrucción ITC-BT-30 del Reglamento Electrotécnico de Baja Tensión, esta
actividad no se encuentra sujeta a esta clasificación.
PROYECTO INSTALACIÓN ELÉCTRICA DE BAJA TENSIÓN
INSTALACIÓN ALUMBRADO EXTERIOR URBANIZACIÓN TANATORIO BENICÀSSIM (CASTELLÓN)
12 V12/007-ALUM
1.9.1.10 Estaciones de servicio o garajes (ITC-BT-29) Según la Instrucción ITC-BT-29 del Reglamento Electrotécnico de Baja Tensión, esta
actividad no se encuentra sujeta a esta clasificación.
1.9.1.11 Locales de características especiales (ITC-BT-30) Según la Instrucción ITC-BT-30 del Reglamento Electrotécnico de Baja Tensión, esta
actividad no se encuentra sujeta a esta clasificación.
1.9.1.12 Instalaciones con fines especiales (ITC-BT-31, 32, 33, 34, 35, 38, 39) Según las Instrucciones ITC-BT-31, 32, 33, 34, 35, 38, 39 del Reglamento Electrotécnico de
Baja Tensión, esta actividad no se encuentra sujeta a esta clasificación.
1.9.1.13 Instalaciones a muy baja tensión (ITC-BT-36) Según las Instrucciones ITC-BT-36 del Reglamento Electrotécnico de Baja Tensión, esta
actividad no se encuentra sujeta a esta clasificación.
1.9.1.14 Instalaciones a tensiones especiales (ITC-BT-37) Según la Instrucción ITC-BT-37 del Reglamento Electrotécnico de Baja Tensión, esta
actividad no se encuentra sujeta a esta clasificación.
1.9.1.15 Instalaciones generadoras de baja tensión (ITC-BT-40) Según la Instrucción ITC-BT-40 del Reglamento Electrotécnico de Baja Tensión, esta
actividad no se encuentra sujeta a esta clasificación.
1.9.2 Cuadro general de distribución
1.9.2.1 Características y composición.- El cuadro general de distribución alojado en el interior de un armario y se ubica tal y como
se observa en el plano de planta, sobre cada uno de los interruptores, en el cuadro se
colocará una placa indicadora del circuito al que pertenece.
En ellos se situarán los dispositivos de mando y protección preceptivos según la Instrucción
ITC-BT-17.
Se montarán en cada salida o línea de alimentación directa a los interruptores
magnetotérmicos y los diferenciales necesarios para la protección de la línea contra
sobrecargas, cortocircuitos y corrientes de defecto.
PROYECTO INSTALACIÓN ELÉCTRICA DE BAJA TENSIÓN
INSTALACIÓN ALUMBRADO EXTERIOR URBANIZACIÓN TANATORIO BENICÀSSIM (CASTELLÓN)
13 V12/007-ALUM
Dichos dispositivos son de tipo modular para montaje sobre bastidores, sus características
en cuanto a sensibilidad, número de polos y líneas que protegen, queda reflejado en el
documento correspondiente a cálculos y en el esquema de la instalación.
1.9.2.2 Cuadros secundarios y composición.- No existe ningún cuadro secundario de distribución.
1.9.3 Líneas de distribución y canalización
1.9.3.1 Sistema de instalación elegido Conductores activos:
Los conductores a emplear en la instalación serán de Cu, unipolares, tensión asignada 0,6/1
KV, con aislamiento XLPE y cubierta de PVC, enterrados bajo tubo.
La sección mínima a emplear en redes subterráneas, incluido el neutro, será de 6 mm². Los
empalmes y derivaciones deberán realizarse en cajas de bornes adecuadas, situadas dentro
de los soportes de las luminarias, y a una altura mínima de 0,3 m sobre el nivel del suelo o
en una arqueta registrable, que garanticen, en ambos casos, la continuidad, el aislamiento y
la estanqueidad del conductor.
La instalación de los conductores de alimentación a las lámparas se realizará en Cu,
bipolares, tensión asignada 0,6/1 kV, de 2x2,5 mm² de sección (fase y neutro), protegidos
por c/c fusibles calibrados de 6 A.
Las líneas de alimentación a puntos de luz con lámparas o tubos de descarga estarán
previstas para transportar la carga debida a los propios receptores, a sus elementos
asociados, a las corrientes armónicas, de arranque y desequilibrio de fases. Como
consecuencia, la potencia aparente mínima en VA, se considerará 1,8 veces la potencia en
vatios de las lámparas o tubos de descarga.
Las secciones de todos los conductores han sido determinadas de tal forma que la c.d.t.
(caída de tensión máxima) sea de un 3% en el punto más desfavorable todo ello conforme
con el vigente reglamento electrotécnico de baja tensión.
Conductores de protección:
Los conductores de protección serán igualmente de cobre con el mismo aislamiento y
sección que los conductores activos hasta una sección de estos de 16 mm2.
PROYECTO INSTALACIÓN ELÉCTRICA DE BAJA TENSIÓN
INSTALACIÓN ALUMBRADO EXTERIOR URBANIZACIÓN TANATORIO BENICÀSSIM (CASTELLÓN)
14 V12/007-ALUM
Para conductores activos entre 25 y 35 mm2, los de protección serán de 16 mm2 y la mitad
de la sección que en activos para secciones mayores de 35 mm2.
Irán instalados en el interior del mismo tubo protector que los conductores activos.
Canalizaciones fijas
Se emplearán sistemas y materiales análogos a los de las redes subterráneas de
distribución reguladas en la ITC-BT-07. Los cables se dispondrán en canalización enterrada
bajo tubo, con unas dimensiones variables en función al número de cables a instalar según
planos de detalle.
El tubo irá envuelto por una capa de hormigón HM-20/B/20 de 31 cm de espesor y apoyado
sobre una cama de 5 cm. El resto de la zanja se completará con 19 cm de relleno
seleccionado y se colocará una cinta de señalización, que advierta de la existencia de
cables, una distancia mínima del nivel del suelo de 0,10 m y a 0,25 m por encima del tubo.
En los cruzamientos de calzadas, la canalización, además de entubada, irá hormigonada
con HM-20/B/20 y se instalará como mínimo un tubo de reserva.
No se instalará más de un circuito por tubo. Los tubos serán de doble capa de 110 mm. de
diámetro con resistencia al impacto normal y al a la compresión de 450 N y serán conformes
a lo establecido en la norma UNE-EN 50.086 2-4.
A fin de hacer completamente registrable la instalación, cada uno de los soportes llevará
adosado una arqueta de fábrica de hormigón HM-20/B/20 con paredes de 15 cm de espesor
y suelo de grava, con tapa de fundición de 40x40 cm. Éstas se ubicarán también en cada
uno de los cruces, derivaciones y cambios de dirección.
Además de todo lo descrito, la instalación en todo caso, se ajustará por el vigente
reglamento electrotécnico de baja tensión.
Luminarias
Las luminarias utilizadas en el alumbrado exterior serán conformes la norma UNE-EN
60.598 -2-3 y la UNE-EN 60.598 -2-5 en el caso de proyectores de exterior.
Todas las luminarias irán claramente marcadas con la tensión nominal, frecuencia nominal,
potencia máxima y tipo de lámparas con que pueden ser utilizadas.
PROYECTO INSTALACIÓN ELÉCTRICA DE BAJA TENSIÓN
INSTALACIÓN ALUMBRADO EXTERIOR URBANIZACIÓN TANATORIO BENICÀSSIM (CASTELLÓN)
15 V12/007-ALUM
Equipos eléctricos de los puntos de luz
Los equipos eléctricos para montaje exterior poseerán un grado de protección mínima IP54,
según UNE 20.324 e IK 8 según UNE-EN 50.102, e irán montados a una altura mínima de
2,5 m sobre el nivel del suelo, las entradas y salidas de cables serán por la parte inferior de
la envolvente. Cada punto de luz deberá tener compensado individualmente el factor de
potencia para que sea igual o superior a 0,90; asimismo deberá estar protegido contra
sobreintensidades.
Aparatos de maniobra y protección
Los aparatos de maniobra son los interruptores y conmutadores, que cortarán la corriente
máxima del circuito en que están colocados, sin dar lugar a la formación de arco
permanente, abriendo y cerrando los circuitos sin posibilidad de tomar una posición
intermedia, serán del tipo cerrado y material aislante.
Las dimensiones de las piezas de contacto serán tales que la temperatura en ningún caso
pueda exceder de 65ºC en ninguna de sus piezas.
Su construcción será tal que permita realizar un número de maniobras de apertura y cierre,
del orden de 10.000, con su carga nominal a la tensión de trabajo.
Llevarán marcada su intensidad y tensiones nominales y estarán probadas a una tensión de
500 a 1.000 voltios.
Los aparatos de protección, son los disyuntores eléctricos, fusibles e interruptores
diferenciales.
Los disyuntores serán de tipo magneto térmicos de accionamiento manual, y podrán cortar
la corriente máxima del circuito en que están colocadas sin dar lugar a la formación de arcos
permanentes, abriendo y cerrando los circuitos sin posibilidad de tomar una posición
intermedia.
Su capacidad de corte, para la protección del corto circuito, estará de acuerdo con la
intensidad de corto circuito que pueda presentarse en un punto de su instalación y para la
protección contra el calentamiento de las líneas se regulará para una temperatura inferior a
los 60ºC.
Llevarán marcada la intensidad y tensión nominal de funcionamiento, así como el signo
indicador de su desconexinado.
PROYECTO INSTALACIÓN ELÉCTRICA DE BAJA TENSIÓN
INSTALACIÓN ALUMBRADO EXTERIOR URBANIZACIÓN TANATORIO BENICÀSSIM (CASTELLÓN)
16 V12/007-ALUM
Tanto los disyuntores como los interruptores diferenciales, cuando no pueden soportar las
corrientes de corto circuito irán acoplados con fusibles calibrados.
Los fusibles empleados para proteger los circuitos secundarios, serán calibrados a la
intensidad del circuito que protegen. Se dispondrán sobre material aislante e incombustible y
estarán construidas de forma que no se pueda proyectar metal al fundirse. Se podrán
recambiar bajo tensión sin peligro alguno y llevarán marcada la intensidad y tensión
nominales de trabajo.
Sistema de protección contra contactos indirectos
El sistema elegido para la protección contra contactos indirectos consiste en el empleo de
interruptores diferenciales y puesta a tierra de las masas. La resistencia a tierra de las
masas medida en cada punto de la instalación, no será superior al valor calculado.
Las luminarias serán de Clase I o de Clase II.
Las partes metálicas accesibles de los soportes de luminarias estarán conectadas a tierra.
Se excluyen de esta prescripción aquellas partes metálicas que, teniendo un doble
aislamiento, no sean accesibles al público en general. Para el acceso al interior de las
luminarias que estén instaladas a una altura inferior a 3 m sobre el suelo o en un espacio
accesible al público, se requerirá el empleo de útiles especiales. Las partes metálicas de los
kioskos, marquesinas, cabinas telefónicas, paneles de anuncios y demás elementos de
mobiliario urbano, que estén a una distancia inferior a 2 m de las partes metálicas de la
instalación de alumbrado exterior y que sean susceptibles de ser tocadas simultáneamente,
deberán estar puestas a tierra.
Cuando las luminarias sean de Clase I, deberán estar conectadas al punto de puesta a tierra
del soporte, mediante cable unipolar aislado de tensión asignada 450/750V con
recubrimiento de color verde-amarillo y sección mínima 2,5 mm2 en cobre.
Protección contra sobrecargas y cortocircuitos
En el cuadro general de distribución se situarán los dispositivos de mando y protección
según la Instrucción ITC-BT-17.
Se montarán en cada salida o línea de alimentación directa, los interruptores magneto
térmicos y los interruptores diferenciales necesarios para la protección de las líneas contra
sobrecargas, cortocircuitos y corrientes de defecto.
PROYECTO INSTALACIÓN ELÉCTRICA DE BAJA TENSIÓN
INSTALACIÓN ALUMBRADO EXTERIOR URBANIZACIÓN TANATORIO BENICÀSSIM (CASTELLÓN)
17 V12/007-ALUM
Las características en cuanto a sensibilidad, número de polos y línea que protejan, queda
reflejado en el punto correspondiente del documento de cálculos y en el esquema de la
instalación.
Con el fin de poder desconectar la instalación ante cualquier emergencia se ha dotado a
este de un interruptor de corte omnipolar.
Tanto el cuadro general, como los cuadros secundarios y las tomas de corriente, cumplirán
con la prescripción de ser estancos a las fibras inflamables.
Protección contra armónicos, sobretensiones
En la presente instalación no se instalar ninguna protección contra armónicos y
sobretensiones.
1.9.3.2 Descripción: longitud, sección y diámetro del tubo Nº de línea Tramo de línea Longitud de tramo Sección del conductor Diámetro del tubo
LINEA PRINCIPAL Long 62,00 LINEA: 1
DERIVACION 1 Long 16,00 6 mm2 110 Ø
1.9.3.3 Numero circuitos, destinos y puntos de utilización de cada circuito.
CM: 1 LINEA: 1 LINEA PRINCIPAL Long 62,00 c.d.t. (%) 0,12
Ramal Sección (mm2)
Long (m) Pot (W) Pot (VA) Int (A) c.d.t. (v) Kw*m c.d.t.
(%)
c.d.t. (%) total
CM - 1 4 x 6 6 100 1.800 2,60 0,07 537,60 0,018 0,018 1 - 2 4 x 6 8 100 1.620 2,34 0,09 537,60 0,022 0,040 2 - 3 4 x 6 10 100 1.440 2,08 0,10 537,60 0,024 0,064 3 - 4 4 x 6 5 100 1.260 1,82 0,04 537,60 0,011 0,074 4 - 5 4 x 6 11 100 1.080 1,56 0,08 537,60 0,020 0,094 5 - 6 4 x 6 11 100 720 1,04 0,05 537,60 0,013 0,108 6 - 7 4 x 6 0 100 540 0,78 0,00 537,60 0,000 0,108 7 - 8 3 x 6 11 100 360 0,52 0,03 537,60 0,015 0,122 8 - 9 2 x 6 0 100 180 0,26 0,00 537,60 0,000 0,122
CM: 1 LINEA: 1 DERIVACION 1 Long 16,00 c.d.t. (%) 0,12
Ramal Sección (mm2)
Long (m) Pot (W) Pot (VA) Int (A) c.d.t. (v) Kw*m c.d.t.
(%)
c.d.t. (%) total
5 - 10 2 x 6 16 100 180 0,26 0,02 537,60 0,029 0,123
PROYECTO INSTALACIÓN ELÉCTRICA DE BAJA TENSIÓN
INSTALACIÓN ALUMBRADO EXTERIOR URBANIZACIÓN TANATORIO BENICÀSSIM (CASTELLÓN)
18 V12/007-ALUM
1.9.3.4 Conductor de protección Los conductores de protección serán igualmente de cobre con el mismo aislamiento y
sección que los conductores activos hasta una sección de estos de 16 mm2.
Para conductores activos entre 25 y 35 mm2, los de protección serán de 16 mm2 y la mitad
de la sección que en activos para secciones mayores de 35 mm2.
Irán instalados en el interior del mismo tubo protector que los conductores activos.
1.10 SUMINISTROS COMPLEMENTARIOS
1.10.1 Socorro
Por las características de la actividad, no le será de aplicación este tipo de suministro
indicados en el Artículo 10 del R.E.B.T.
1.10.2 Reserva
Por las características de la actividad, no le será de aplicación este tipo de suministro
indicados en el Artículo 10 del R.E.B.T.
1.10.3 Duplicado
Por las características de la actividad, no le será de aplicación este tipo de suministro
indicados en el Articulo 10del R.E.B.T.
1.11 ALUMBRADO DE EMERGENCIA
1.11.1 Seguridad
No es preceptivo en esta instalación el alumbrado de seguridad.
1.11.2 Reemplazamiento
No es preceptivo en esta instalación el alumbrado de reemplazamiento.
1.12 EQUIPOS DE CONEXIÓN DE ENERGÍA REACTIVA
La compensación de la energía reactiva, se realiza en cada luminaria, mediante
condensadores adecuados, consiguiéndose un factor de potencia mínimo de 0,90
PROYECTO INSTALACIÓN ELÉCTRICA DE BAJA TENSIÓN
INSTALACIÓN ALUMBRADO EXTERIOR URBANIZACIÓN TANATORIO BENICÀSSIM (CASTELLÓN)
19 V12/007-ALUM
1.13 SISTEMA DE SEÑALIZACIÓN, ALARMA, CONTROL REMOTO Y COMUNICACIÓN.
No se consideran, siendo los controles instalados por células fotoeléctricas e interruptores
horarios
1.14 LINEA DE PUESTA A TIERRA
La máxima resistencia de puesta a tierra será tal que, a lo largo de la vida de la instalación y
en cualquier época del año, no se puedan producir tensiones de contacto mayores de 24 V,
en las partes metálicas accesibles de la instalación (soportes, cuadros metálicos, etc.).
La puesta a tierra de los soportes se realizará por conexión a una red de tierra común para
todas las líneas que partan del mismo cuadro de protección, medida y control.
En las redes de tierra, se instalará como mínimo un electrodo de puesta a tierra cada 5
soportes de luminarias, y siempre en el primero y en el último soporte de cada línea.
Los conductores de la red de tierra que unen los electrodos deberán ser:
• Desnudos, de cobre, de 35 mm2 de sección mínima, si forman parte de la propia red de
tierra, en cuyo caso irán por fuera de las canalizaciones de los cables de alimentación.
• Aislados, mediante cables de tensión asignada 450/750V, con recubrimiento de color
verde-amarillo, con conductores de cobre, de sección mínima 16 mm2 para redes
subterráneas, y de igual sección que los conductores de fase para las redes posadas, en
cuyo caso irán por el interior de las canalizaciones de los cables de alimentación.
El conductor de protección que une de cada soporte con el electrodo o con la red de tierra,
será de cable unipolar aislado, de tensión asignada 450/750 V, con recubrimiento de color
verde-amarillo, y sección mínima de 16 mm2 de cobre.
Todas las conexiones de los circuitos de tierra, se realizarán mediante terminales, grapas,
soldadura o elementos apropiados que garanticen un buen contacto permanente y protegido
contra la corrosión.
PROYECTO INSTALACIÓN ELÉCTRICA DE BAJA TENSIÓN
INSTALACIÓN ALUMBRADO EXTERIOR URBANIZACIÓN TANATORIO BENICÀSSIM (CASTELLÓN)
21 V12/007-ALUM
1.15 RED DE EQUIPOTENCIALIDAD
En la presente instalación, no será necesario este sistema de protección.
1.16 INSTALACIÓN CON FINES ESPECIALES
En la presente instalación, no hay instalación con fines especiales.
Castellón, Julio 2012
Jorge Navarro Robledo Ing. Téc. Industrial Col. 545
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
22 V12/007-ALUM
2 CALCULOS JUSTIFICATIVOS
2.1 TENSIÓN NOMINAL Y CAIDA DE TENSIÓN MÁXIMA ADMISIBLE.-
Tensión nominal
La tensión será de 400V entre cada una de las fases y 230V entre estas y el neutro, con una
frecuencia de 50Hz.
Caída de tensión máxima admisible
Línea repartidora ITC-BT-14
• 1% Contadores individuales ó contadores por plantas.
• 0,5% Contadores totalmente concentrados.
La caída de tensión se entiende desde el punto de arranque de la derivación individual en
una línea repartidora hasta el punto de conexión del dispositivo privado de mando y
protección.
Derivación individual ITC-BT-15
• 0,5% Contadores individuales ó concentrados por plantas.
• 1% Para el caso de contadores totalmente concentrados.
• 1,5% Para el caso de derivaciones individuales en suministros para un único usuario en
el que no existe línea general de alimentación.
La caída de tensión se entiende desde el punto de arranque de la derivación individual en
una línea repartidora hasta el punto de conexión del dispositivo privado de mando y
protección.
Instalación interior ITC-BT-19
• 3% Para receptores de alumbrado.
• 5% Para receptores de los demás usos.
La caída de tensión se entiende entre el origen de la instalación y cualquier punto de la
instalación. Esta caída de tensión se calculará considerando alimentados todos los aparatos
de utilización susceptibles de funcionar simultáneamente.
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
23 V12/007-ALUM
2.2 FORMULAS UTILIZADAS
Intensidad de corriente
Se calcula por aplicación de las ecuaciones generales siguientes:
Circuitos monofásicos:
Ι = Pn x c x f
Vs x cosϕ x η
Circuitos trifásicos:
Ι = cos x V x 3
xcxfPn
ϕ
Siendo: Pn = Potencia del circuito en vatios; en el caso de motores Pn = 736 x Pc.v
Vs = Tensión simple = 230 V.
V = Tensión compuesta = 400 V. Cosϕ= Factor de potencia: para circuitos de alumbrado con equipo auxiliar en Alto Factor = 0,8. para circuitos de fuerza motriz = 0,85. para resistencias y otros usos = 1. F =Factor corrector de la potencia de alumbrado a efectos de cálculo del circuito: en caso de lámparas y tubos de descarga f = 1,8, en los demás casos f = 1. C =Coeficiente de sobredimensionamiento en el caso de motores, según ITC-BT-47. en los demás casos c = 1. cuando un circuito alimente a varios motores o a un motor y otros receptores,
deberán estar los conductores sobredimensionados para una intensidad no menor a la suma de 125% de la intensidad a plena carga del motor de mayor potencia, más la intensidad a plena carga de todos los demás motores o receptores.
η =Rendimiento mecánico global= 0,85 en caso de motores (en los demás casos η= 1). Caída de tensión
Las fórmulas empleadas para el cálculo de la caída de tensión al final de cada tramo son las
siguientes:
Circuitos monofásicos:
ΔV% = 2 x L x Pc
S x Vs x n x S’ x η + 2 x L x Pc x Xn x senϕ
1000 x Vs x n x η x cosϕ = voltios (V)
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
24 V12/007-ALUM
Circuitos trifásicos:
ΔV% = L x Pc
k x v x n x S x η + L x Pc x Xn x senϕ
1.000 x V x n x η x cosϕ = voltios (V)
Siendo: ΔV% = Caída de tensión en el circuito en %. L = Longitud del circuito en metros. ρ = Resistividad del conductor En caso de conductor de cobre ρ= 0,017 Ohm.mm2/m. En caso de conductor de aluminio ρ= 0,03 Ohm.mm2/m. Cosϕ= Factor de potencia: Para circuitos de alumbrado con equipo auxiliar en Alto Factor = 0,9. Para circuitos de fuerza motriz = 0,8. Para resistencias y otros usos = 1. S = Sección del conductor en mm2. Vs = Tensión simple en voltios = 230 V. Ιn = Intensidad que circula por el conductor. V = Tensión compuesta en voltios = 400V. Pc = Potencia de cálculo en vatios. n = nº de conductores por fase. η = rendimiento mecánico Xn = Reactancia por unidad de longitud en m Ω/m. K = Conductividad del conductor. En caso de conductor de cobre k = 56 En caso de conductor de aluminio k= 35
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
25 V12/007-ALUM
2.3 POTENCIAS
2.3.1 Relación de receptores de alumbrado con indicación de su potencia eléctrica.-
Pot (W) Pot (VA)
Línea 1 1000 1.800
Total 1000 1.800
• Línea 1 10 receptores de 100 W
2.3.2 Relación de receptores de fuerza motriz, indicando su potencia eléctrica
No existen receptores de fuerza motriz.
2.3.3 Relación de receptores de otros usos, indicando su potencia eléctrica
No existen receptores de otros usos.
2.3.4 Potencia total prevista
DESCRIPCION POT. (KW)
Alumbrado 1,00
Fuerza motriz 0,00
Otros usos 0,00
Total potencia (kW) 1,00
El interruptor de cabecera tiene un poder de corte de 25 amperios para una tensión de
400 V, por lo que la potencia máxima admisible por densidad de corriente del interruptor
general, es de 17,32 Kw.
2.4 CÁLCULOS LUMINOTÉCNICOS
2.4.1 Cálculos del numero de luminarias
Según anexo adjunto.
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
26 V12/007-ALUM
2.5 CÁLCULOS ELÉCTRICOS: ALUMBRADO Y FUERZA MOTRIZ.-
2.5.1 Cálculo de la sección de los conductores y diámetro de los tubos de canalización a utilizar en la línea de alimentación al cuadro general y secundarios
Descripción Características tubos S (mm2) L (m) P inst. (KW) Cos I max (A) U (V) U%
Derivación individual Tubo 110 mm diam. 10 1 17,321 1 25 0,04 0,01
2.5.2 Cálculo de la sección de los conductores y diámetro de los tubos o canalizaciones a utilizar en las líneas derivadas
Longitud, sección y diámetro del tubo
Nº de línea Tramo de línea Longitud de tramo Sección del conductor Diámetro del tubo
LINEA PRINCIPAL Long 62,00 LINEA: 1
DERIVACION 1 Long 16,00 6 mm2 110 Ø
Numero circuitos, destinos y puntos de utilización de cada circuito.
CM: 1 LINEA: 1 LINEA PRINCIPAL Long 62,00 c.d.t. (%) 0,12
Ramal Sección (mm2)
Long (m) Pot (W) Pot (VA) Int (A) c.d.t. (v) Kw*m c.d.t.
(%)
c.d.t. (%) total
CM - 1 4 x 6 6 100 1.800 2,60 0,07 537,60 0,018 0,018 1 - 2 4 x 6 8 100 1.620 2,34 0,09 537,60 0,022 0,040 2 - 3 4 x 6 10 100 1.440 2,08 0,10 537,60 0,024 0,064 3 - 4 4 x 6 5 100 1.260 1,82 0,04 537,60 0,011 0,074 4 - 5 4 x 6 11 100 1.080 1,56 0,08 537,60 0,020 0,094 5 - 6 4 x 6 11 100 720 1,04 0,05 537,60 0,013 0,108 6 - 7 4 x 6 0 100 540 0,78 0,00 537,60 0,000 0,108 7 - 8 3 x 6 11 100 360 0,52 0,03 537,60 0,015 0,122 8 - 9 2 x 6 0 100 180 0,26 0,00 537,60 0,000 0,122
CM: 1 LINEA: 1 DERIVACION 1 Long 16,00 c.d.t. (%) 0,12
Ramal Sección (mm2)
Long (m) Pot (W) Pot (VA) Int (A) c.d.t. (v) Kw*m c.d.t.
(%)
c.d.t. (%) total
5 - 10 2 x 6 16 100 180 0,26 0,02 537,60 0,029 0,123
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
27 V12/007-ALUM
2.5.3 Cálculo de las protecciones a instalar en las diferentes líneas generales y derivadas.-
2.5.3.1 Por sobrecarga Los disyuntores automáticos magnetotérmicos en cuanto a su calidad, se han seleccionado
con una In. inferior a la intensidad máxima admisible del circuito que protejan contra
sobrecargas.
2.5.3.2 Por cortocircuito El cortocircuito es un defecto franco (impedancia de defecto nula) entre dos partes de la
instalación a distinto potencial, y con una duración inferior a 5 segundos. Estos defectos
pueden ser motivados por contacto accidental o por fallo de aislamiento y pueden darse
entre fases, fase-neutro, fase-masa o fase-tierra.
Por tanto se produce una sobre intensidad con valores muy por encima de la intensidad
nominal que se establece en un circuito o línea, y puesto que la impedancia de defecto es
nula o despreciable, solo quedan limitados por la impedancia de las línea aguas arriba del
defecto.
A causa de las corrientes de cortocircuito, los aparatos y conductores experimentan un
esfuerzo térmico adicional, lo cual origina aumentos de la temperatura de los diversos
elementos, reduciendo así su vida útil. Es por esto por lo que en estos casos es necesario
interrumpir el cortocircuito lo más rápido posible (el tiempo dependerá del valor de la sobre
intensidad).
Así mismo en el origen de todo circuito se establecerá un dispositivo de protección contra
cortocircuitos cuya “capacidad de corte” estará de acuerdo con la intensidad de cortocircuito
que pueda presentarse en el punto de su instalación.
En el caso de cortocircuito además de los efectos térmicos producidos por las sobre
intensidades, al ser estas de valores muy elevados, se producen esfuerzos electrodinámicos
y es necesario dimensionar la instalación para que sea capaz de soportar estos esfuerzos
(Ej. embarrados de cuadros).
Tipos y clases de Cortocircuitos.-
En primer lugar, cabe reseñar que se consideran los cortocircuitos como defectos francos, o
sea, contactos directos (impedancia nula entre puntos bajo tensiones diferentes), ya que
este tipo de defectos, aunque menos frecuente, produce mayores intensidades de c.c. que
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
28 V12/007-ALUM
los producidos por medio de un arco eléctrico con el consiguiente desprendimiento de
energía (caso más frecuente).
En segundo lugar señalaremos, que en los circuitos trifásicos se pueden presentar
usualmente las siguientes clases de cortocircuitos.
a. Cortocircuito tripolar (simétrico)
b. Cortocircuito asimétrico entre fase y tierra.
c. Cortocircuito asimétrico entre dos fases (sin contacto a tierra)
d. Cortocircuito asimétrico entre fase-neutro (sin contacto a tierra)
Se analizarán los cortocircuitos en baja tensión con potencia en el lado de alta tensión
infinita, lo que significa que los elementos de la parte de alta no limitan la intensidad de c.c.
demandada en baja tensión; debido a esto se obtendrán mayores intensidades de c.c. Por
otra parte, cabe señalar que se analizarán los c.c. en un punto alejado del transformador, es
decir, se estudiaran en cualquier punto de la instalación proyectada y con ésta en vacío.
De todo lo anterior se concluye que la máxima intensidad de cortocircuito se establece para
un c.c. tripolar (trifásico-simétrico), y la menor para un c.c. fase-neutro.
También conviene señalar que el c.c. tripolar es muy poco frecuente, en cambio, el c.c. fase-
tierra constituye el 80% de los cortocircuitos, dando lugar éste, con los sistemas de
distribución utilizadas y las hipótesis simplificativas asumidas, iguales intensidades de
cortocircuito.
e. Cortocircuito tripolar o asimétrico
La intensidad permanente de cortocircuito vendrá dada de la siguiente manera:
Ipcc = U/ 3
Zt
Ipcc = UFZt
Siendo:
U: Tensión compuesta o de línea. UF: Tensión simple o de fase. Zt: Impedancia total de la instalación de baja tensión, hasta el punto de c.c.
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
29 V12/007-ALUM
Si estamos en bornes de un transformador la Zt será la impedancia de c.c. del transformador
y se puede expresar en función de la tensión de c.c. en tanto por ciento (Ucc %).
f. Cortocircuito asimétrico entre fase y tierra
Para analizar este tipo de cortocircuitos de forma coherente, se plantearán las ecuaciones
de defecto para los sistemas directo, inverso y homo polar, dando como resultado:
Ipcc = 3 UF
Zd + Zi + Zh
siendo:
Zd: Impedancia total sistema directo. Zi: Impedancia total sistema inverso. Zh: Impedancia total sistema homo polar.
De esta expresión se extraen las siguientes conclusiones:
1.- Si se utilizaran instalaciones eléctricas con el neutro no unido directamente a tierra, la
impedancia homo polar Zh=∞, y por lo tanto, según la expresión anterior Ipcc=0, o sea, no
tendrá ninguna corriente en el circuito. Ahora bien, la tensión simple UF, en las fases no
averiadas (no se ha producido defecto en ellas) pasarán a valor 3 UF, es decir, toman el
valor de la tensión compuesta, por lo tanto, habría que prever los aislamientos para esta
sobre tensión. Asimismo, se produciría una carga brusca en las capacidades parásitas de
las líneas, sobre todo en las aéreas, hecho que combinado con las inductancias de las
líneas puede provocar sobre tensiones capaces de ocasionar averías importantes en los
aislamientos de la paramenta eléctrica utilizada.
Estos inconvenientes, entre otros, hacen que se utilice el neutro unido directamente a tierra.
2.- Teniendo en cuenta la conclusión anterior y admitiendo que en los sistemas estáticos
(conductores) Zd=Zi=Zh, la intensidad de c.c. en la fase averiada será:
Ipcc = 3 UF3 Zt
Ipcc = UFZt
Igual a la producida en un cortocircuito tripolar.
g. Cortocircuito asimétrico entre dos fases (sin contacto a tierra)
Si se procede de forma análoga al caso anterior, se obtiene en las fases defectuosas,
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
30 V12/007-ALUM
Ipcc = U
2Zt
Ipcc = 3 UF2Zt
Puede observarse como, en este caso, la corriente de cortocircuito será 3 /2=0,866 veces
la corriente establecida en un cortocircuito tripolar (trifásico simétrico).
h. Cortocircuito asimétrico entre fase-neutro (sin contacto a tierra)
Si se procede de forma análoga al caso anterior, se tendrá,
Ipcc = UF2Zt
En este caso la corriente de cortocircuito será 0,5 veces la establecida en un tripolar.
Obtención de las intensidades de cortocircuito. Fórmula a emplear
Según el estudio realizado de las clases de cortocircuitos en baja tensión, asumiendo el
cortocircuito como un defecto franco (impedancia de defecto nula o despreciable),
considerando potencia de c.c. infinita en el lado de alta tensión y calculando la instalación en
vacío, se tendrá para cualquier línea o circuito de la instalación, una intensidad de c.c.
permanente:
Origen de circuito o línea.
Ipccl= Ct U3 Zt
siendo:
Ipccl: intensidad permanente, de c.c. en inicio en línea en kA. Ct: Coeficiente de tensión obtenido en condiciones generales de c.c. U: Tensión trifásica en V, obtenida de condiciones generales de proyecto. Zt: Impedancia total en mΩ, aguas arriba del punto de c.c. (sin incluir la línea
o circuito en estudio)
De esta forma se obtendrá la máxima intensidad de c.c. que puede presentarse en una
línea, determinada por un cortocircuito tripolar, según se ha visto, y en el origen de ésta, sin
estar limitada por la propia impedancia del conductor. Se necesita para la determinación del
poder de corte del elemento de protección a sobre intensidades situado en el origen de todo
circuito o línea eléctrica.
Final de circuito o línea
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
31 V12/007-ALUM
IpccF= Ct U F 2 Zt
siendo:
IpccF: Intensidad permanente de c.c. en fin de línea en kA. Ct: Coeficiente de tensión obtenido de condiciones generales de c.c. UF: Tensión monofásica en V, obtenida de condiciones generales de proyecto. Zt: Impedancia total en mΩ, incluyendo la propia de la línea o circuito (por tanto es igual a la
impedancia en origen mas la propia del conductor o línea
De esta forma se obtendrá la mínima intensidad de c.c. para una línea, determinada por un
cortocircuito fase-neutro y al final de la línea o circuito en estudio. Se necesita para
determinar si un conductor queda protegido en toda su longitud a c.c., ya que es condición
imprescindible que la Ipccf sea mayor o igual que la intensidad del disparador
electromagnético, para una curva determinada en interruptores automáticos con sistema de
corte electromagnético, o que sea mayor o igual que la intensidad de fusión de los fusibles
en 5s., cuando se utilizan estos elementos de protección a cortocircuito.
La impedancia total hasta el punto de cortocircuito será:
Zt = Rt2 + Xt2
siendo:
Rt: R1 + R2 + .......................... + Rn (suma de las resistencia de las líneas aguas arriba hasta el punto de c.c.).
Xt: X1 + X2 + .......................... + Xn (suma de las reactancias de las líneas aguas arriba hasta el punto de c.c.).
Asimismo, la resistencia (R) en mΩ, y la reactancia (X) en mΩ para una línea o circuito se
pueden expresar según las ecuaciones siguientes:
R = L . 1000 . CR
K . S . n mΩ,
X = Xu . L
. n mΩ,
R: Resistencia de la línea en mΩ. X: Reactancia de la línea en mΩ. L: longitud de la línea en m. CR: Coeficiente de resistividad, extraído de condiciones generales de c.c. K: Conductividad del metal; Kcu= 56, KAI = 35. S: Sección de la línea en mm2.
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
32 V12/007-ALUM
Xu: Reactancia de la línea, en mΩ, por unidad de longitud. n: nº de conductores por fase.
Cálculo y justificación de la instalación a cortocircuito
De las consideraciones anteriores se justifica a continuación la siguiente tabla resumen de
los cálculos efectuados conforme al sistema descrito.
Los resultados obtenidos se reflejan en las siguiente tabla:
Nº de línea Sección del conductor I (A) Prot. Térm. I. Mag. (A)
LINEA: 1 6 mm2 2,60 4 x 10
2.5.4 Armónicos
En el presente proyecto no se ha previsto ningún tipo de instalación para eliminar los
armónicos.
2.5.5 Sobretensiones
En el presente proyecto no se ha previsto ningun tipo de instalación para eliminar las
sobretensiones.
2.6 CÁLCULO DEL SISTEMA DE PROTECCIÓN CONTRA CONTACTOS INDIRECTOS.-
El sistema elegido para la protección de contactos indirectos consiste en el empleo de
interruptores diferenciales y puesta a tierra de las masas. La resistencia a tierra de las
masas, medidas en cada punto de la instalación, no será superior al valor de 80 ohmios,
puesto que:
R< 24 / Id = 24 / 0,3 = 80 ohmios
Teniendo en cuenta que el potencial de una masa cualquiera con respecto a una toma de
tierra eléctricamente distinta ha de ser en valor eficaz, 24V. y que la sensibilidad del
diferencial en el caso más desfavorable, es de 300mA.
Debidoa la clase de terreno:
• Tipo de terreno Arena arcillosa
• Resistividad del terreno 150 ohmios.m.
• Electrodos 1 piquetas de 1 metro por cada columna.
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
33 V12/007-ALUM
y el tipo de electrodo adoptado tendremos, siendo:
• ρ = Resistividad del terreno
• L = longitud del electrodo
• n = número de electrodos R= ρ / (N*L) = 150 / (1*7) = 21,4 ohmios
Dado el resultado obtenido, podemos considerar como válido el tipo de electrodo a emplear,
así como el número.
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
35 V12/007-ALUM
2.7 CÁLCULO DEL AFORO DEL LOCAL EN RELACION CON LA ITC-BT-28
La instalación que nos ocupa no esta en un local incluido en la ITC-BT-28 del RD 842/2002
de 2 de agosto de 2002.
Castellón, Julio 2012
Jorge Navarro Robledo Ing. Téc. Industrial Col. 545
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
37 V12/007-ALUM
3 ANEXOS
3.1 CALCULOS LUMINOTECNICOS.
Fecha: 07-06-2012 Nº de Proyecto:
Encendido 1
Cliente:
Instalación:
Todos los datos de Indalwin son cálculos exactos obtenidos por implantaciones precisas en relación al área objeto de estudio.Los valores fotométricos (rendimiento e intensidades) de las luminarias utilizadas en el proyecto están basados en ensayos tipo de laboratorio.En instalación los valores pueden sufrir desviación por tolerancias fabriles o de montaje en luminarias, lámparas y equipos auxiliares. Otros factores quepueden modificar los resultados exactos del proyecto son las características superficiales, temperatura ambiente y tensión de alimentación.
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 2
I N D I C E
Resumen del Proyecto
A / Planos y ubicación 3
B / Luminarias 4
C / Resultados 5
Desarrollo del Proyecto
D / Disposición del área a iluminar 6
* Vista 3D 6
* Planta 6
* Alzado 7
* Zonas de estudio 7
E / Descripción de la instalación 8
* Luminarias y lámparas del proyecto 8
* Potencia instalada 9
* Factor de mantenimiento 9
F / Resumen de los valores luminotécnicos en las zonas de estudio 10
G / Cálculos 11
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 3
Resumen del Proyecto
A / Planos y ubicación
Situación de proyecto: D1 Encendidos1 Encendido 1
Autor:
Descripción:
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 4
Resumen del Proyecto
B / Luminarias
Nº de modelo: 1Luminaria modelo: IQVLámpara: 1x100W SE E40Flujo: 10.20 klmTemperatura de color: 1950KDescripción: IQV 100W SE
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 5
Resumen del Proyecto
C / Resultados
Potencia instalada 1.04 W/m²Eficiencia energética: 30.5 m²·lux/WEficiencia energética mínima: 9.0 m²·lux/WEficiencia energética de referencia: 13.0 m²·lux/WIndice de eficiencia energética: 2.35Indice de consumo energético ICE: 0.43
Clasificación energética: A
Factor de utilización (fu): 0.49
Índice de deslumbramiento: D6 (20)
ULR (FHSinst): 0.03ULOR: 0.03
Clase Lmed Emed Emin Uo EscME1 -- 20.0 7.5 -- 5.0
TODO -- 31.6 1.9 0.06 5.6
-- OK X -- OK
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 6
Desarrollo del Proyecto
D / Disposición del área a iluminar
Vista 3D
Planta
X (m)
Y (m)
-10 0 10 20 30 40 50 60 70 80 90
0
5
10
15
20
25
30
35
40
45
50
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 7
Desarrollo del Proyecto
Alzado
Y (m)
Z (m)
-5 0 5 10 15 20 25 30 35 40 45 50 55
-10
-5
0
5
10
15
20
Zonas de estudio
X (m)
Y (m)
-20 0 20 40 60 80
05
101520253035404550
TODO
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 8
Desarrollo del Proyecto
E / Descripción de la instalación
Luminarias y lámparas del proyecto
Luminarias decorativas funcionales con cuatro versiones posibles de acoplamiento para fijar a columna brazo o pared y con dos tipos de cierre de policarbonato (IQC) o uno de vidrio (IQV) utilizando lámpara de vapor de mercurio (M) de 125 W o sodio alta presión (S) o halogenuros metálicos (H) hasta 150 W. Carcasa formada por una capota entallada y un aro soporte en aluminio inyectado pintada en color negro texturado o blanco RAL 9016 brillo. Bandeja abatible que soporta el reflector y el equipo eléctrico en acero galvanizado y pintada en blanco RAL 9016 brillo. Reflector de aluminio hidroconformado y anodizado. Cierre en policarbonato termoconformado y estabilizado a los rayos UV acabado texturado (modelos IQC-P1 e IQC-P2) o en vidrio sodo-cálcico templado y serigrafiado de 5 mm. (modelo IQV). IP-55(IQC). IP-65(IQV). IK08. Clase I. Clase II. Suministro sin lámpara. Nota: Para instalar las luminarias IQC e IQV es necesario utilizar uno de los cuatro accesorios de fijación indicados
Nº de modelo: 1Luminaria modelo: IQVLámpara: 1x100W SE E40Flujo: 10.20 klmTemperatura de color: 1950KDescripción: IQV 100W SE
Luminaria modelo: IQVTipo de lámpara: 1x100W SE E40Código fotométrico: 3061103sM2.tm
Rendimiento total hemisferio inferior: 74.9 %Rendimiento total hemisferio superior: 0.0 %
Intensidad en GM 80: 17.30 cd/klmIntensidad en GM 90: 0.70 cd/klmRelación I80/I88: 29.03Intensidad máxima: 310.50 cd/klmÍndice específico de la luminaria: 5.28
Alcance: CortoDispersión: EstrechaControl: IntensoClase de luminaria: Cut - off
Diagrama isocandelas (%) Representación fotométrica (cd/klm)
GM = 0 10102020
3030
4040
5050
6060
7070
8080
9090270 280 290 300 310 320 330 340 350 C = 0 10 20 30 40 50 60 70 80 90
Imax = 100%
90
80
60
60
40
40
302010 5
1 -90
-80
-70
-60
-50
-40 -30 -20 -10 10 20 30 40
60
70
80
90
GM = 0
50 100 150 200 250 300 350cd/klm
PLANO TRANSVERSALPLANO LONGITUDINALPLANO VERTICAL PRINCIPAL (C = 90.0)
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 9
Desarrollo del Proyecto
E / Descripción de la instalación
Potencia instalada
Encendido 1
Modelo Luminaria Mod. Lámpara W y tipo Uds Consumo Lámp.+Aux. 1 IQV 1x100W SE E40 9 1026 W
Potencia instalada para la superficie de proyecto: 1.04 W/m² 1026 W
Factor de mantenimiento
Modelo Luminaria Mod. Lámpara W y tipo Luminaria F. lámpara Conjunto 1 IQV 1x100W SE E40 0.87 0.90 0.89 0.70
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 10
Desarrollo del Proyecto
F / Resumen de los valores luminotécnicos en las zonas de estudio
Zona NombreZona 1 TODO
Tipo Zona 1Em(lux) 31.60
Ilum. Horizontal Um 0.06
Uex 0.03
Em(lux) 5.61
Semicilíndrica Um 0.00
Uex 0.00
GR
Lm(cd/m²)
Luminancia Uo
Ul
Todos los datos de Indalwin son cálculos exactos obtenidos por implantaciones precisas en relación al área objeto de estudio.Los valores fotométricos (rendimiento e intensidades) de las luminarias utilizadas en el proyecto están basados en ensayos tipo de laboratorio.En instalación los valores pueden sufrir desviación por tolerancias fabriles o de montaje en luminarias, lámparas y equipos auxiliares. Otros factores quepueden modificar los resultados exactos del proyecto son las características superficiales, temperatura ambiente y tensión de alimentación.
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 11
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación horizontal: Valores en servicio en lux
Y/X(m) -0.00 0.51 1.01 1.52 2.03 2.54 3.04 3.55 4.06 4.57 5.07 5.58 6.09 6.09 Ul
46.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.94
46.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.88
45.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.76
45.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.60
44.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.51
44.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.43
43.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.38
43.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.29
42.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.26
42.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.23
41.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.22
41.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.19
40.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.18
40.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.18
39.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.16
Ut --- 0.95 0.86 0.74 0.63 0.55 0.53 0.47 0.44 0.44 0.42 0.40 0.42
Y/X(m) 6.60 7.10 7.61 8.12 8.63 9.13 9.64 10.15 10.66 11.16 11.67 12.18 12.69 12.69 Ul
46.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.94
46.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.88
45.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.76
45.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.60
44.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.51
44.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.43
43.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.38
43.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.29
42.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.26
42.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.23
41.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.22
41.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.19
40.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.18
40.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.18
39.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.16
Ut 0.40 0.41 0.37 0.33 0.32 0.29 0.25 0.24 0.27 0.24 0.27 0.26 0.28
Y/X(m) 13.19 13.70 14.21 14.71 15.22 15.73 16.24 16.74 17.25 17.76 18.27 18.77 19.28 19.28 Ul
46.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.94
46.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.88
45.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.76
45.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.60
44.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.51
44.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.43
43.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.38
43.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.29
42.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.26
42.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.23
41.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.22
41.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.19
40.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.18
40.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.18
39.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.16
Ut 0.26 0.27 0.25 0.26 0.26 0.23 0.23 0.21 0.22 0.20 0.21 0.19 0.21
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 12
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación horizontal: Valores en servicio en lux
Y/X(m) 19.79 20.30 20.80 21.31 21.82 22.33 22.83 23.34 23.85 24.36 24.86 25.37 25.88 25.88 Ul
46.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.94
46.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.88
45.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.76
45.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.60
44.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.51
44.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.43
43.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.38
43.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.29
42.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.26
42.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.23
41.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.22
41.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.19
40.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.18
40.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.18
39.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.16
Ut 0.20 0.21 0.23 0.21 0.22 0.21 0.22 0.21 0.23 0.21 0.22 0.23 0.22
Y/X(m) 26.39 26.89 27.40 27.91 28.41 28.92 29.43 29.94 30.44 30.95 31.46 31.97 32.47 32.47 Ul
46.75 --- --- --- --- --- --- --- --- --- --- --- 7 6 0.94
46.25 --- --- --- --- --- --- --- --- --- --- --- 8 7 0.88
45.75 --- --- --- --- --- --- --- --- --- --- 9 9 8 0.76
45.25 --- --- --- --- --- --- --- --- --- 12 11 10 10 0.60
44.75 --- --- --- --- --- --- --- --- 14 13 13 12 11 0.51
44.25 --- --- --- --- --- --- --- 17 16 16 15 14 13 0.43
43.75 --- --- --- --- --- --- --- 20 19 18 17 16 15 0.38
43.25 --- --- --- --- --- --- 23 23 22 21 19 18 17 0.29
42.75 --- --- --- --- --- 27 26 25 25 23 22 20 19 0.26
42.25 --- --- --- --- 30 30 29 29 28 26 25 23 21 0.23
41.75 --- --- --- --- 33 33 33 32 31 29 27 25 23 0.22
41.25 --- --- --- 35 36 36 36 35 33 32 30 28 26 0.19
40.75 --- --- 37 38 38 38 38 37 36 35 33 30 28 0.18
40.25 --- 37 39 40 41 40 40 39 38 37 35 33 30 0.18
39.75 36 38 40 42 42 42 42 41 40 39 37 35 33 0.16
Ut 0.23 0.22 0.24 0.23 0.25 0.23 0.24 0.26 0.24 0.25 0.22 0.16 0.15
Y/X(m) 32.98 33.49 34.00 34.50 35.01 35.52 36.03 36.53 37.04 37.55 38.06 38.56 39.07 39.07 Ul
46.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.94
46.25 7 --- --- --- --- --- --- --- --- --- --- --- --- 0.88
45.75 8 7 --- --- --- --- --- --- --- --- --- --- --- 0.76
45.25 9 8 8 7 --- --- --- --- --- --- --- --- --- 0.60
44.75 10 9 9 8 7 --- --- --- --- --- --- --- --- 0.51
44.25 12 11 10 9 8 7 --- --- --- --- --- --- --- 0.43
43.75 13 12 11 10 9 8 7 --- --- --- --- --- --- 0.38
43.25 15 14 12 11 10 9 8 8 7 --- --- --- --- 0.29
42.75 17 15 14 13 11 10 9 8 8 7 --- --- --- 0.26
42.25 19 17 16 14 13 12 10 9 8 8 7 --- --- 0.23
41.75 21 19 18 16 14 13 12 10 10 9 8 7 --- 0.22
41.25 23 21 19 18 16 14 13 12 11 10 9 8 7 0.19
40.75 26 23 21 19 17 16 14 13 12 11 10 9 8 0.18
40.25 28 26 23 21 19 18 16 15 13 12 11 10 9 0.18
39.75 30 28 26 23 21 20 18 17 15 14 12 11 10 0.16
Ut 0.16 0.17 0.17 0.15 0.16 0.16 0.16 0.16 0.15 0.15 0.16 0.18 0.19
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 13
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación horizontal: Valores en servicio en lux
Y/X(m) 39.58 40.09 40.59 41.10 41.61 42.11 42.62 43.13 43.64 44.14 44.65 45.16 45.67 45.67 Ul
46.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.94
46.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.88
45.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.76
45.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.60
44.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.51
44.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.43
43.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.38
43.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.29
42.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.26
42.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.23
41.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.22
41.25 7 --- --- --- --- --- --- --- --- --- --- --- --- 0.19
40.75 8 7 --- --- --- --- --- --- --- --- --- --- --- 0.18
40.25 8 8 7 --- --- --- --- --- --- --- --- --- --- 0.18
39.75 10 9 8 7 7 --- --- --- --- --- --- --- --- 0.16
Ut 0.18 0.19 0.22 0.24 0.25 0.28 0.29 0.29 0.31 0.31 0.34 0.37 0.40
Y/X(m) 46.17 46.68 47.19 47.70 48.20 48.71 49.22 49.73 50.23 50.74 51.25 51.76 52.26 52.26 Ul
46.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.94
46.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.88
45.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.76
45.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.60
44.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.51
44.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.43
43.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.38
43.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.29
42.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.26
42.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.23
41.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.22
41.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.19
40.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.18
40.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.18
39.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.16
Ut 0.44 0.48 0.48 0.51 0.55 0.60 0.66 0.67 0.72 0.77 0.82 0.86 0.90
Y/X(m) 52.77 53.28 53.79 54.29 54.80 54.80 Ul
46.75 --- --- --- --- --- 0.94
46.25 --- --- --- --- --- 0.88
45.75 --- --- --- --- --- 0.76
45.25 --- --- --- --- --- 0.60
44.75 --- --- --- --- --- 0.51
44.25 --- --- --- --- --- 0.43
43.75 --- --- --- --- --- 0.38
43.25 --- --- --- --- --- 0.29
42.75 --- --- --- --- --- 0.26
42.25 --- --- --- --- --- 0.23
41.75 --- --- --- --- --- 0.22
41.25 --- --- --- --- --- 0.19
40.75 --- --- --- --- --- 0.18
40.25 --- --- --- --- --- 0.18
39.75 --- --- --- --- --- 0.16
Ut 0.95 0.97 0.98 0.99 ---
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 14
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación horizontal: Valores en servicio en lux
Y/X(m) -0.00 0.51 1.01 1.52 2.03 2.54 3.04 3.55 4.06 4.57 5.07 5.58 6.09 6.09 Ul
39.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.15
38.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.15
38.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.15
37.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
37.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
36.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
36.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
35.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
35.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.11
34.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.10
34.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.10
33.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.09
33.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.08
32.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.08
32.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.07
Ut --- 0.95 0.86 0.74 0.63 0.55 0.53 0.47 0.44 0.44 0.42 0.40 0.42
Y/X(m) 6.60 7.10 7.61 8.12 8.63 9.13 9.64 10.15 10.66 11.16 11.67 12.18 12.69 12.69 Ul
39.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.15
38.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.15
38.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.15
37.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
37.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
36.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
36.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
35.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
35.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.11
34.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.10
34.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.10
33.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.09
33.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.08
32.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.08
32.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.07
Ut 0.40 0.41 0.37 0.33 0.32 0.29 0.25 0.24 0.27 0.24 0.27 0.26 0.28
Y/X(m) 13.19 13.70 14.21 14.71 15.22 15.73 16.24 16.74 17.25 17.76 18.27 18.77 19.28 19.28 Ul
39.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.15
38.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.15
38.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.15
37.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
37.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
36.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
36.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
35.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
35.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.11
34.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.10
34.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.10
33.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.09
33.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.08
32.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.08
32.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.07
Ut 0.26 0.27 0.25 0.26 0.26 0.23 0.23 0.21 0.22 0.20 0.21 0.19 0.21
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 15
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación horizontal: Valores en servicio en lux
Y/X(m) 19.79 20.30 20.80 21.31 21.82 22.33 22.83 23.34 23.85 24.36 24.86 25.37 25.88 25.88 Ul
39.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.15
38.75 --- --- --- --- --- --- --- --- --- --- --- --- 35 0.15
38.25 --- --- --- --- --- --- --- --- --- --- --- 34 36 0.15
37.75 --- --- --- --- --- --- --- --- --- --- 32 34 36 0.13
37.25 --- --- --- --- --- --- --- --- --- --- 32 34 36 0.13
36.75 --- --- --- --- --- --- --- --- --- 30 32 34 36 0.13
36.25 --- --- --- --- --- --- --- --- 29 31 32 34 35 0.13
35.75 --- --- --- --- --- --- --- 29 30 32 33 34 35 0.13
35.25 --- --- --- --- --- --- 29 30 32 33 35 36 36 0.11
34.75 --- --- --- --- --- --- 31 32 34 35 36 36 37 0.10
34.25 --- --- --- --- --- 31 32 33 35 36 37 38 37 0.10
33.75 --- --- --- --- 32 33 34 35 36 37 38 38 38 0.09
33.25 --- --- --- 33 34 35 36 36 38 38 39 --- --- 0.08
32.75 --- --- 34 35 36 37 37 38 39 39 --- --- --- 0.08
32.25 --- --- 35 37 37 38 39 39 39 --- --- --- --- 0.07
Ut 0.20 0.21 0.23 0.21 0.22 0.21 0.22 0.21 0.23 0.21 0.22 0.23 0.22
Y/X(m) 26.39 26.89 27.40 27.91 28.41 28.92 29.43 29.94 30.44 30.95 31.46 31.97 32.47 32.47 Ul
39.25 37 39 41 43 44 44 44 43 42 41 39 37 35 0.15
38.75 38 40 42 44 45 45 44 44 43 42 41 39 37 0.15
38.25 39 41 42 44 45 45 45 45 44 43 42 40 39 0.15
37.75 39 --- 42 43 45 45 45 45 44 44 43 42 40 0.13
37.25 38 40 42 43 44 44 44 44 44 44 44 43 42 0.13
36.75 38 39 41 42 43 43 43 43 43 43 43 43 43 0.13
36.25 37 39 40 41 42 42 42 41 42 42 43 43 43 0.13
35.75 37 38 39 40 41 41 --- 40 40 41 42 43 43 0.13
35.25 37 37 38 39 39 39 39 38 38 39 40 41 42 0.11
34.75 37 37 37 38 38 38 37 37 37 37 38 39 41 0.10
34.25 37 37 37 36 36 36 36 35 35 35 36 38 39 0.10
33.75 37 36 36 35 35 34 34 33 33 34 35 --- 37 0.09
33.25 --- --- --- 34 33 33 32 32 32 33 34 35 37 0.08
32.75 --- --- --- --- --- 32 31 31 31 32 33 34 36 0.08
32.25 --- --- --- --- --- --- 30 30 30 31 32 34 36 0.07
Ut 0.23 0.22 0.24 0.23 0.25 0.23 0.24 0.26 0.24 0.25 0.22 0.16 0.15
Y/X(m) 32.98 33.49 34.00 34.50 35.01 35.52 36.03 36.53 37.04 37.55 38.06 38.56 39.07 39.07 Ul
39.25 32 30 28 25 24 22 20 18 17 15 14 13 12 0.15
38.75 35 32 30 28 26 24 22 20 19 17 16 15 13 0.15
38.25 37 34 32 30 28 26 24 23 21 19 18 17 15 0.15
37.75 38 37 35 33 31 29 27 25 24 22 20 19 17 0.13
37.25 40 39 37 35 33 31 30 28 26 24 23 21 19 0.13
36.75 42 41 39 37 36 34 32 31 29 27 25 24 22 0.13
36.25 43 42 41 39 38 36 35 33 32 30 28 26 24 0.13
35.75 43 43 43 41 40 39 38 36 34 33 31 29 27 0.13
35.25 43 43 43 43 42 41 40 39 37 35 33 31 29 0.11
34.75 42 42 43 43 43 42 42 41 39 38 36 34 32 0.10
34.25 40 41 42 43 44 43 43 42 41 40 38 36 34 0.10
33.75 39 40 42 43 44 44 44 44 43 41 40 38 35 0.09
33.25 38 40 41 43 44 45 45 45 44 43 41 39 37 0.08
32.75 38 39 41 43 44 45 46 46 45 44 42 40 38 0.08
32.25 38 40 41 43 44 45 46 46 46 44 43 41 --- 0.07
Ut 0.16 0.17 0.17 0.15 0.16 0.16 0.16 0.16 0.15 0.15 0.16 0.18 0.19
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 16
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación horizontal: Valores en servicio en lux
Y/X(m) 39.58 40.09 40.59 41.10 41.61 42.11 42.62 43.13 43.64 44.14 44.65 45.16 45.67 45.67 Ul
39.25 11 10 9 8 7 7 --- --- --- --- --- --- --- 0.15
38.75 12 11 10 9 8 7 7 --- --- --- --- --- --- 0.15
38.25 14 13 11 10 9 8 7 7 --- --- --- --- --- 0.15
37.75 16 14 13 12 10 9 8 7 7 6 --- --- --- 0.13
37.25 18 16 14 13 12 10 9 8 7 6 6 --- --- 0.13
36.75 20 18 16 15 13 11 10 9 8 7 6 6 --- 0.13
36.25 22 20 18 16 14 12 11 10 9 8 7 6 6 0.13
35.75 24 22 20 18 16 14 12 11 9 9 8 7 6 0.13
35.25 27 24 22 19 17 15 13 12 10 9 8 7 7 0.11
34.75 29 26 23 21 18 16 15 13 11 10 9 8 7 0.10
34.25 31 28 25 23 20 18 16 14 12 11 10 9 8 0.10
33.75 33 30 27 24 21 19 17 15 13 12 11 9 8 0.09
33.25 34 31 28 25 23 20 18 16 14 13 11 10 9 0.08
32.75 --- --- 29 27 24 22 19 17 15 14 12 11 10 0.08
32.25 --- --- --- --- 25 23 20 18 17 15 13 12 10 0.07
Ut 0.18 0.19 0.22 0.24 0.25 0.28 0.29 0.29 0.31 0.31 0.34 0.37 0.40
Y/X(m) 46.17 46.68 47.19 47.70 48.20 48.71 49.22 49.73 50.23 50.74 51.25 51.76 52.26 52.26 Ul
39.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.15
38.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.15
38.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.15
37.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
37.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
36.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
36.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
35.75 5 --- --- --- --- --- --- --- --- --- --- --- --- 0.13
35.25 6 5 5 --- --- --- --- --- --- --- --- --- --- 0.11
34.75 6 6 5 5 --- --- --- --- --- --- --- --- --- 0.10
34.25 7 6 5 5 4 --- --- --- --- --- --- --- --- 0.10
33.75 7 7 6 5 5 4 --- --- --- --- --- --- --- 0.09
33.25 8 7 6 6 5 4 4 4 --- --- --- --- --- 0.08
32.75 8 7 7 6 5 5 4 4 3 --- --- --- --- 0.08
32.25 9 8 7 6 6 5 5 4 4 3 --- --- --- 0.07
Ut 0.44 0.48 0.48 0.51 0.55 0.60 0.66 0.67 0.72 0.77 0.82 0.86 0.90
Y/X(m) 52.77 53.28 53.79 54.29 54.80 54.80 Ul
39.25 --- --- --- --- --- 0.15
38.75 --- --- --- --- --- 0.15
38.25 --- --- --- --- --- 0.15
37.75 --- --- --- --- --- 0.13
37.25 --- --- --- --- --- 0.13
36.75 --- --- --- --- --- 0.13
36.25 --- --- --- --- --- 0.13
35.75 --- --- --- --- --- 0.13
35.25 --- --- --- --- --- 0.11
34.75 --- --- --- --- --- 0.10
34.25 --- --- --- --- --- 0.10
33.75 --- --- --- --- --- 0.09
33.25 --- --- --- --- --- 0.08
32.75 --- --- --- --- --- 0.08
32.25 --- --- --- --- --- 0.07
Ut 0.95 0.97 0.98 0.99 ---
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 17
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación horizontal: Valores en servicio en lux
Y/X(m) -0.00 0.51 1.01 1.52 2.03 2.54 3.04 3.55 4.06 4.57 5.07 5.58 6.09 6.09 Ul
31.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.07
31.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.06
30.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.06
30.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.06
29.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.06
29.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.05
28.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.05
28.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.05
27.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.04
27.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.04
26.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.04
26.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.05
25.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.06
25.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.06
24.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.07
Ut --- 0.95 0.86 0.74 0.63 0.55 0.53 0.47 0.44 0.44 0.42 0.40 0.42
Y/X(m) 6.60 7.10 7.61 8.12 8.63 9.13 9.64 10.15 10.66 11.16 11.67 12.18 12.69 12.69 Ul
31.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.07
31.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.06
30.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.06
30.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.06
29.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.06
29.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.05
28.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.05
28.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.05
27.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.04
27.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.04
26.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.04
26.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.05
25.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.06
25.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.06
24.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.07
Ut 0.40 0.41 0.37 0.33 0.32 0.29 0.25 0.24 0.27 0.24 0.27 0.26 0.28
Y/X(m) 13.19 13.70 14.21 14.71 15.22 15.73 16.24 16.74 17.25 17.76 18.27 18.77 19.28 19.28 Ul
31.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.07
31.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.06
30.75 --- --- --- --- --- --- --- --- --- --- --- --- 32 0.06
30.25 --- --- --- --- --- --- --- --- --- --- --- 30 32 0.06
29.75 --- --- --- --- --- --- --- --- --- --- --- 30 32 0.06
29.25 --- --- --- --- --- --- --- --- --- --- 27 30 32 0.05
28.75 --- --- --- --- --- --- --- --- --- 25 27 30 33 0.05
28.25 --- --- --- --- --- --- --- --- 23 25 28 31 33 0.05
27.75 --- --- --- --- --- --- --- 21 23 26 29 32 34 0.04
27.25 --- --- --- --- --- --- --- 22 24 27 30 32 34 0.04
26.75 --- --- --- --- --- --- 21 23 25 27 30 32 34 0.04
26.25 --- --- --- --- --- 20 22 24 26 28 30 32 33 0.05
25.75 --- --- --- --- 20 21 23 25 27 28 30 32 33 0.06
25.25 --- --- --- 20 22 23 25 26 28 29 31 32 33 0.06
24.75 --- --- --- 22 24 25 26 28 29 30 32 32 33 0.07
Ut 0.26 0.27 0.25 0.26 0.26 0.23 0.23 0.21 0.22 0.20 0.21 0.19 0.21
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 18
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación horizontal: Valores en servicio en lux
Y/X(m) 19.79 20.30 20.80 21.31 21.82 22.33 22.83 23.34 23.85 24.36 24.86 25.37 25.88 25.88 Ul
31.75 --- 35 36 38 39 40 40 40 40 --- --- --- --- 0.07
31.25 34 36 37 39 40 41 41 40 --- --- --- --- --- 0.06
30.75 35 36 38 40 41 41 41 --- --- --- --- --- --- 0.06
30.25 35 37 39 40 41 41 --- --- --- --- --- --- --- 0.06
29.75 35 37 39 40 41 --- --- --- --- --- --- --- --- 0.06
29.25 35 37 39 40 40 --- --- --- --- --- --- --- --- 0.05
28.75 35 37 38 39 --- --- --- --- --- --- --- --- --- 0.05
28.25 35 37 38 --- --- --- --- --- --- --- --- --- --- 0.05
27.75 35 37 --- --- --- --- --- --- --- --- --- --- --- 0.04
27.25 35 36 --- --- --- --- --- --- --- --- --- --- --- 0.04
26.75 35 --- --- --- --- --- --- --- --- --- --- --- --- 0.04
26.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.05
25.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.06
25.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.06
24.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.07
Ut 0.20 0.21 0.23 0.21 0.22 0.21 0.22 0.21 0.23 0.21 0.22 0.23 0.22
Y/X(m) 26.39 26.89 27.40 27.91 28.41 28.92 29.43 29.94 30.44 30.95 31.46 31.97 32.47 32.47 Ul
31.75 --- --- --- --- --- --- --- 30 30 31 32 34 36 0.07
31.25 --- --- --- --- --- --- --- --- 30 30 32 33 35 0.06
30.75 --- --- --- --- --- --- --- --- --- --- 31 33 34 0.06
30.25 --- --- --- --- --- --- --- --- --- --- --- 32 34 0.06
29.75 --- --- --- --- --- --- --- --- --- --- --- 32 33 0.06
29.25 --- --- --- --- --- --- --- --- --- --- --- --- 33 0.05
28.75 --- --- --- --- --- --- --- --- --- --- --- --- 33 0.05
28.25 --- --- --- --- --- --- --- --- --- --- --- --- 33 0.05
27.75 --- --- --- --- --- --- --- --- --- --- --- 32 33 0.04
27.25 --- --- --- --- --- --- --- --- --- --- 31 32 34 0.04
26.75 --- --- --- --- --- --- --- --- --- 30 31 33 34 0.04
26.25 --- --- --- --- --- --- --- 28 30 31 32 33 35 0.05
25.75 --- --- --- --- --- 27 28 29 30 31 33 35 36 0.06
25.25 --- --- --- --- 28 28 28 29 31 32 34 36 38 0.06
24.75 --- --- 28 28 28 28 29 30 31 33 35 37 39 0.07
Ut 0.23 0.22 0.24 0.23 0.25 0.23 0.24 0.26 0.24 0.25 0.22 0.16 0.15
Y/X(m) 32.98 33.49 34.00 34.50 35.01 35.52 36.03 36.53 37.04 37.55 38.06 38.56 39.07 39.07 Ul
31.75 37 39 41 --- 44 45 46 46 46 45 43 --- --- 0.07
31.25 37 39 40 42 44 44 45 45 45 44 43 --- --- 0.06
30.75 36 38 40 41 43 44 44 45 44 43 --- --- --- 0.06
30.25 35 37 39 40 42 43 44 44 43 --- --- --- --- 0.06
29.75 35 36 38 39 41 42 43 43 --- --- --- --- --- 0.06
29.25 35 36 38 39 41 42 43 43 42 --- --- --- --- 0.05
28.75 35 36 37 39 40 42 43 43 42 41 --- --- 37 0.05
28.25 35 36 38 39 41 42 43 43 42 41 --- 38 37 0.05
27.75 35 36 38 40 41 42 43 43 42 41 39 38 37 0.04
27.25 35 37 39 40 42 43 43 --- 42 40 40 38 37 0.04
26.75 36 38 39 41 43 43 43 42 41 40 39 39 37 0.04
26.25 37 39 40 42 --- 44 44 43 42 40 40 39 38 0.05
25.75 38 40 41 43 44 45 44 43 42 41 40 39 37 0.06
25.25 39 41 43 44 45 45 45 44 43 42 40 39 37 0.06
24.75 40 42 44 44 45 46 46 45 43 42 40 38 36 0.07
Ut 0.16 0.17 0.17 0.15 0.16 0.16 0.16 0.16 0.15 0.15 0.16 0.18 0.19
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 19
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación horizontal: Valores en servicio en lux
Y/X(m) 39.58 40.09 40.59 41.10 41.61 42.11 42.62 43.13 43.64 44.14 44.65 45.16 45.67 45.67 Ul
31.75 --- --- --- --- --- 24 22 20 18 16 14 12 11 0.07
31.25 --- --- --- --- --- --- 23 20 18 16 15 13 12 0.06
30.75 --- --- --- --- --- --- 23 21 19 17 15 14 12 0.06
30.25 --- --- --- --- --- --- --- 22 19 18 16 14 13 0.06
29.75 --- --- --- --- --- --- --- 22 20 18 16 15 13 0.06
29.25 --- --- --- --- --- --- --- 23 21 19 17 15 14 0.05
28.75 37 36 --- --- --- --- --- 23 21 19 17 15 14 0.05
28.25 36 35 --- --- --- --- --- 23 21 19 17 16 14 0.05
27.75 36 34 32 --- --- --- --- 23 21 19 17 16 14 0.04
27.25 36 34 32 30 --- --- --- 22 20 19 17 15 14 0.04
26.75 36 34 31 29 --- --- --- 22 20 18 16 15 13 0.04
26.25 36 33 31 28 26 --- 23 21 19 17 16 14 13 0.05
25.75 35 33 30 28 25 23 21 20 18 16 15 14 12 0.06
25.25 35 32 29 27 25 22 20 19 17 16 14 13 12 0.06
24.75 34 31 28 26 23 21 19 18 16 15 13 12 11 0.07
Ut 0.18 0.19 0.22 0.24 0.25 0.28 0.29 0.29 0.31 0.31 0.34 0.37 0.40
Y/X(m) 46.17 46.68 47.19 47.70 48.20 48.71 49.22 49.73 50.23 50.74 51.25 51.76 52.26 52.26 Ul
31.75 10 9 8 7 6 5 5 4 4 3 3 --- --- 0.07
31.25 10 9 8 7 6 6 5 5 4 4 3 3 --- 0.06
30.75 11 10 9 8 7 6 5 5 4 4 3 3 3 0.06
30.25 11 10 9 8 7 6 6 5 4 4 3 3 3 0.06
29.75 12 10 9 8 7 7 6 5 5 4 4 3 3 0.06
29.25 12 11 10 9 8 7 6 5 5 4 4 3 3 0.05
28.75 12 11 10 9 8 7 6 5 5 4 4 3 3 0.05
28.25 12 11 10 9 8 7 6 5 5 4 4 3 3 0.05
27.75 12 11 10 9 8 7 6 5 5 4 4 3 3 0.04
27.25 12 11 10 9 8 7 6 5 5 4 4 3 3 0.04
26.75 12 11 10 9 8 7 6 5 5 4 4 3 3 0.04
26.25 12 10 9 8 7 7 6 5 5 4 4 3 3 0.05
25.75 11 10 9 8 7 6 6 5 5 4 4 3 3 0.06
25.25 11 9 9 8 7 6 5 5 4 4 3 3 3 0.06
24.75 10 9 8 7 6 6 5 5 4 4 3 --- --- 0.07
Ut 0.44 0.48 0.48 0.51 0.55 0.60 0.66 0.67 0.72 0.77 0.82 0.86 0.90
Y/X(m) 52.77 53.28 53.79 54.29 54.80 54.80 Ul
31.75 --- --- --- --- --- 0.07
31.25 --- --- --- --- --- 0.06
30.75 --- --- --- --- --- 0.06
30.25 --- --- --- --- --- 0.06
29.75 3 --- --- --- --- 0.06
29.25 3 2 --- --- --- 0.05
28.75 3 2 --- --- --- 0.05
28.25 3 2 2 --- --- 0.05
27.75 3 2 2 2 --- 0.04
27.25 3 2 2 2 --- 0.04
26.75 3 2 2 2 --- 0.04
26.25 3 2 2 --- --- 0.05
25.75 3 --- --- --- --- 0.06
25.25 --- --- --- --- --- 0.06
24.75 --- --- --- --- --- 0.07
Ut 0.95 0.97 0.98 0.99 ---
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 20
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación horizontal: Valores en servicio en lux
Y/X(m) -0.00 0.51 1.01 1.52 2.03 2.54 3.04 3.55 4.06 4.57 5.07 5.58 6.09 6.09 Ul
24.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.08
23.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.09
23.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.10
22.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.10
22.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.12
21.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.12
21.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.12
20.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.12
20.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.12
19.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.12
19.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.12
18.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
18.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
17.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.14
17.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
Ut --- 0.95 0.86 0.74 0.63 0.55 0.53 0.47 0.44 0.44 0.42 0.40 0.42
Y/X(m) 6.60 7.10 7.61 8.12 8.63 9.13 9.64 10.15 10.66 11.16 11.67 12.18 12.69 12.69 Ul
24.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.08
23.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.09
23.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.10
22.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.10
22.25 --- --- --- --- --- --- --- --- --- --- --- --- 29 0.12
21.75 --- --- --- --- --- --- --- --- --- --- --- 30 32 0.12
21.25 --- --- --- --- --- --- --- --- --- --- 30 33 35 0.12
20.75 --- --- --- --- --- --- --- --- --- 31 33 35 38 0.12
20.25 --- --- --- --- --- --- --- --- --- 33 36 38 41 0.12
19.75 --- --- --- --- --- --- --- --- 33 36 38 41 43 0.12
19.25 --- --- --- --- --- --- --- 33 36 38 41 43 46 0.12
18.75 --- --- --- --- --- --- 33 36 38 41 43 46 48 0.13
18.25 --- --- --- --- --- --- 36 38 41 43 45 48 50 0.13
17.75 --- --- --- --- --- 36 38 40 43 45 47 49 51 0.14
17.25 --- --- --- --- 36 38 40 43 45 47 49 51 52 0.13
Ut 0.40 0.41 0.37 0.33 0.32 0.29 0.25 0.24 0.27 0.24 0.27 0.26 0.28
Y/X(m) 13.19 13.70 14.21 14.71 15.22 15.73 16.24 16.74 17.25 17.76 18.27 18.77 19.28 19.28 Ul
24.25 --- --- 23 24 26 27 28 30 31 32 33 33 34 0.08
23.75 --- 24 25 27 28 30 31 32 33 34 34 35 35 0.09
23.25 25 27 28 30 31 32 33 34 35 36 36 36 36 0.10
22.75 28 30 31 33 34 35 36 37 38 38 39 39 38 0.10
22.25 31 33 34 36 37 38 39 40 41 41 41 41 40 0.12
21.75 34 36 38 39 40 41 42 43 43 44 44 43 42 0.12
21.25 37 39 41 42 43 44 45 46 46 46 46 46 45 0.12
20.75 40 42 44 46 47 47 48 48 49 49 48 48 46 0.12
20.25 43 45 47 48 49 50 50 51 51 51 50 49 48 0.12
19.75 46 47 49 51 52 52 53 53 53 52 51 50 48 0.12
19.25 48 50 51 53 54 55 55 55 55 54 52 51 49 0.12
18.75 50 52 53 55 56 57 57 57 56 55 53 52 50 0.13
18.25 51 54 55 57 58 58 58 58 58 57 55 54 52 0.13
17.75 53 55 56 58 59 59 60 59 59 59 57 56 54 0.14
17.25 54 55 57 58 59 60 60 61 61 60 60 58 --- 0.13
Ut 0.26 0.27 0.25 0.26 0.26 0.23 0.23 0.21 0.22 0.20 0.21 0.19 0.21
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 21
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación horizontal: Valores en servicio en lux
Y/X(m) 19.79 20.30 20.80 21.31 21.82 22.33 22.83 23.34 23.85 24.36 24.86 25.37 25.88 25.88 Ul
24.25 34 --- --- --- --- --- --- --- --- --- --- --- --- 0.08
23.75 35 35 --- --- --- --- --- --- --- --- --- 31 31 0.09
23.25 36 36 36 --- --- --- --- --- --- 33 32 32 32 0.10
22.75 38 37 37 36 36 --- --- --- 34 34 34 34 34 0.10
22.25 39 39 38 37 37 36 36 35 35 35 35 35 35 0.12
21.75 41 40 39 38 38 37 37 36 36 36 36 37 37 0.12
21.25 43 42 40 39 39 38 38 38 38 38 38 39 39 0.12
20.75 45 43 42 40 40 39 39 39 39 40 40 41 --- 0.12
20.25 46 44 43 42 41 41 41 41 42 42 --- 43 43 0.12
19.75 47 45 43 43 42 43 43 43 44 44 45 45 46 0.12
19.25 47 46 45 44 44 44 44 45 46 47 47 47 47 0.12
18.75 49 47 46 45 45 46 46 47 47 48 49 49 49 0.13
18.25 51 49 48 --- 47 47 47 48 49 49 50 51 51 0.13
17.75 53 --- 50 49 49 49 49 49 50 51 51 51 51 0.14
17.25 54 53 52 51 51 51 51 51 51 52 51 51 51 0.13
Ut 0.20 0.21 0.23 0.21 0.22 0.21 0.22 0.21 0.23 0.21 0.22 0.23 0.22
Y/X(m) 26.39 26.89 27.40 27.91 28.41 28.92 29.43 29.94 30.44 30.95 31.46 31.97 32.47 32.47 Ul
24.25 30 29 29 29 29 29 29 30 32 34 36 37 40 0.08
23.75 31 30 30 30 29 30 30 31 32 34 --- 38 40 0.09
23.25 32 32 31 31 31 31 31 32 --- 35 37 38 40 0.10
22.75 33 33 33 32 32 32 32 33 34 35 37 38 40 0.10
22.25 35 35 35 34 34 34 34 34 36 36 38 39 40 0.12
21.75 37 37 36 36 36 36 36 36 37 38 39 40 41 0.12
21.25 39 39 38 38 37 37 38 38 39 39 40 41 41 0.12
20.75 41 41 40 39 39 40 40 40 40 41 41 41 41 0.12
20.25 43 42 42 42 41 41 42 42 41 41 41 41 40 0.12
19.75 45 45 44 44 43 43 43 42 41 40 40 39 38 0.12
19.25 47 47 46 45 45 44 43 42 41 40 38 38 36 0.12
18.75 49 48 47 46 45 44 43 41 40 38 37 35 34 0.13
18.25 50 49 48 47 45 44 42 40 39 37 35 33 32 0.13
17.75 51 49 48 46 45 43 41 39 37 35 33 31 29 0.14
17.25 50 49 47 46 44 42 40 37 35 33 31 29 27 0.13
Ut 0.23 0.22 0.24 0.23 0.25 0.23 0.24 0.26 0.24 0.25 0.22 0.16 0.15
Y/X(m) 32.98 33.49 34.00 34.50 35.01 35.52 36.03 36.53 37.04 37.55 38.06 38.56 39.07 39.07 Ul
24.25 41 43 44 45 46 46 46 45 43 42 40 38 35 0.08
23.75 41 43 44 45 46 46 46 44 43 41 39 37 34 0.09
23.25 41 43 44 45 46 46 45 44 42 41 38 36 33 0.10
22.75 41 43 44 45 45 45 44 43 41 39 37 34 31 0.10
22.25 41 43 43 44 44 43 42 41 39 38 36 33 30 0.12
21.75 42 43 43 43 42 42 41 39 38 36 34 31 28 0.12
21.25 42 42 42 41 41 40 39 38 36 34 31 29 26 0.12
20.75 41 41 40 40 39 38 36 35 33 31 29 27 24 0.12
20.25 40 39 38 37 36 35 34 32 30 29 27 24 22 0.12
19.75 38 37 36 34 33 32 31 29 27 26 24 22 20 0.12
19.25 35 34 33 32 30 29 28 26 25 23 21 20 18 0.12
18.75 33 31 30 29 28 26 25 23 22 20 19 17 16 0.13
18.25 30 29 27 26 25 23 22 21 19 18 17 15 14 0.13
17.75 28 26 25 23 22 21 19 18 17 16 15 13 12 0.14
17.25 25 24 22 21 20 18 17 16 15 14 13 12 11 0.13
Ut 0.16 0.17 0.17 0.15 0.16 0.16 0.16 0.16 0.15 0.15 0.16 0.18 0.19
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 22
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación horizontal: Valores en servicio en lux
Y/X(m) 39.58 40.09 40.59 41.10 41.61 42.11 42.62 43.13 43.64 44.14 44.65 45.16 45.67 45.67 Ul
24.25 32 30 27 24 22 20 18 17 15 14 12 11 10 0.08
23.75 31 29 26 23 21 19 17 16 14 13 12 11 10 0.09
23.25 30 27 24 22 20 18 16 15 13 12 11 10 9 0.10
22.75 28 26 23 20 18 16 15 13 12 11 10 9 8 0.10
22.25 27 24 22 19 17 15 14 12 11 10 9 8 7 0.12
21.75 25 23 20 18 16 14 12 11 10 9 8 8 7 0.12
21.25 24 21 19 16 15 13 11 10 9 8 8 7 6 0.12
20.75 22 19 17 15 13 12 10 9 8 8 7 6 6 0.12
20.25 20 18 16 14 12 11 10 9 8 7 6 --- --- 0.12
19.75 18 16 14 13 11 10 9 8 7 6 --- --- --- 0.12
19.25 16 14 13 11 10 9 8 7 6 --- --- --- --- 0.12
18.75 14 13 12 10 9 8 7 --- --- --- --- --- --- 0.13
18.25 13 11 10 9 8 7 --- --- --- --- --- --- --- 0.13
17.75 11 10 9 8 --- --- --- --- --- --- --- --- --- 0.14
17.25 10 9 8 --- --- --- --- --- --- --- --- --- --- 0.13
Ut 0.18 0.19 0.22 0.24 0.25 0.28 0.29 0.29 0.31 0.31 0.34 0.37 0.40
Y/X(m) 46.17 46.68 47.19 47.70 48.20 48.71 49.22 49.73 50.23 50.74 51.25 51.76 52.26 52.26 Ul
24.25 9 8 8 7 6 6 5 4 4 4 --- --- --- 0.08
23.75 9 8 7 6 6 5 5 4 --- --- --- --- --- 0.09
23.25 8 7 7 6 5 5 4 --- --- --- --- --- --- 0.10
22.75 7 7 6 5 5 5 --- --- --- --- --- --- --- 0.10
22.25 7 6 6 5 --- --- --- --- --- --- --- --- --- 0.12
21.75 6 6 5 --- --- --- --- --- --- --- --- --- --- 0.12
21.25 6 --- --- --- --- --- --- --- --- --- --- --- --- 0.12
20.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.12
20.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.12
19.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.12
19.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.12
18.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
18.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
17.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.14
17.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
Ut 0.44 0.48 0.48 0.51 0.55 0.60 0.66 0.67 0.72 0.77 0.82 0.86 0.90
Y/X(m) 52.77 53.28 53.79 54.29 54.80 54.80 Ul
24.25 --- --- --- --- --- 0.08
23.75 --- --- --- --- --- 0.09
23.25 --- --- --- --- --- 0.10
22.75 --- --- --- --- --- 0.10
22.25 --- --- --- --- --- 0.12
21.75 --- --- --- --- --- 0.12
21.25 --- --- --- --- --- 0.12
20.75 --- --- --- --- --- 0.12
20.25 --- --- --- --- --- 0.12
19.75 --- --- --- --- --- 0.12
19.25 --- --- --- --- --- 0.12
18.75 --- --- --- --- --- 0.13
18.25 --- --- --- --- --- 0.13
17.75 --- --- --- --- --- 0.14
17.25 --- --- --- --- --- 0.13
Ut 0.95 0.97 0.98 0.99 ---
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 23
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación horizontal: Valores en servicio en lux
Y/X(m) -0.00 0.51 1.01 1.52 2.03 2.54 3.04 3.55 4.06 4.57 5.07 5.58 6.09 6.09 Ul
16.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.14
16.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.14
15.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.14
15.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
14.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
14.25 --- --- --- --- --- --- --- --- --- --- --- --- 43 0.13
13.75 --- --- --- --- --- --- --- --- --- --- --- --- 45 0.13
13.25 --- --- --- --- --- --- --- --- --- --- --- 45 47 0.14
12.75 --- --- --- --- --- --- --- --- --- --- 44 47 49 0.16
12.25 --- --- --- --- --- --- --- --- --- 43 45 48 50 0.16
11.75 --- --- --- --- --- --- --- --- 41 44 47 49 52 0.17
11.25 --- --- --- --- --- --- --- --- 42 45 48 50 52 0.18
10.75 --- --- --- --- --- --- --- 39 42 45 48 51 53 0.18
10.25 --- --- --- --- --- --- 36 39 42 45 48 50 52 0.18
9.75 --- --- --- --- --- 32 36 39 42 45 47 49 52 0.18
Ut --- 0.95 0.86 0.74 0.63 0.55 0.53 0.47 0.44 0.44 0.42 0.40 0.42
Y/X(m) 6.60 7.10 7.61 8.12 8.63 9.13 9.64 10.15 10.66 11.16 11.67 12.18 12.69 12.69 Ul
16.75 --- --- --- 37 39 41 43 45 47 48 50 51 52 0.14
16.25 --- --- 38 40 42 43 45 46 48 49 50 51 52 0.14
15.75 --- --- 41 43 44 45 47 48 48 49 50 51 52 0.14
15.25 --- 42 44 45 47 47 48 48 49 49 49 50 51 0.13
14.75 42 44 46 47 48 49 49 48 48 48 49 49 51 0.13
14.25 45 46 48 49 49 49 49 48 48 47 48 49 50 0.13
13.75 47 48 50 50 50 50 49 49 48 48 48 48 --- 0.13
13.25 49 50 51 51 51 51 50 50 49 48 --- --- 50 0.14
12.75 50 52 52 53 52 52 51 51 --- --- 49 50 51 0.16
12.25 52 53 53 54 54 54 53 53 --- 51 51 51 52 0.16
11.75 53 54 55 55 55 55 55 --- --- --- 53 53 54 0.17
11.25 54 55 56 56 56 57 --- --- --- --- 54 54 56 0.18
10.75 54 55 56 57 57 --- --- --- --- --- --- 56 57 0.18
10.25 54 55 56 57 58 --- --- --- --- --- --- 57 58 0.18
9.75 54 55 56 57 --- --- --- --- --- --- 57 57 58 0.18
Ut 0.40 0.41 0.37 0.33 0.32 0.29 0.25 0.24 0.27 0.24 0.27 0.26 0.28
Y/X(m) 13.19 13.70 14.21 14.71 15.22 15.73 16.24 16.74 17.25 17.76 18.27 18.77 19.28 19.28 Ul
16.75 54 55 57 58 60 60 61 62 62 62 --- 60 58 0.14
16.25 54 55 57 59 61 62 62 63 --- --- 62 61 59 0.14
15.75 53 55 57 59 61 62 63 --- 64 64 63 62 60 0.14
15.25 53 55 58 60 62 --- 64 64 64 64 64 63 62 0.13
14.75 53 55 58 --- 62 63 64 65 64 64 65 64 62 0.13
14.25 52 --- --- 60 62 63 64 65 65 65 65 64 63 0.13
13.75 --- 55 58 59 61 63 64 64 65 65 65 63 62 0.13
13.25 53 54 57 59 60 62 63 64 64 64 64 62 61 0.14
12.75 53 55 57 59 60 61 62 63 63 62 62 60 59 0.16
12.25 54 56 58 59 60 61 61 61 61 60 59 58 56 0.16
11.75 56 58 59 60 60 60 60 59 59 58 57 55 53 0.17
11.25 58 59 60 60 60 59 58 57 56 55 53 52 51 0.18
10.75 58 59 60 59 58 57 55 54 53 52 50 49 47 0.18
10.25 58 59 59 58 56 54 53 51 49 48 46 45 43 0.18
9.75 57 57 56 55 53 51 49 48 46 44 43 41 39 0.18
Ut 0.26 0.27 0.25 0.26 0.26 0.23 0.23 0.21 0.22 0.20 0.21 0.19 0.21
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 24
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación horizontal: Valores en servicio en lux
Y/X(m) 19.79 20.30 20.80 21.31 21.82 22.33 22.83 23.34 23.85 24.36 24.86 25.37 25.88 25.88 Ul
16.75 56 55 54 54 54 54 53 53 52 52 52 51 50 0.14
16.25 57 56 56 56 56 56 55 54 53 52 51 50 49 0.14
15.75 59 58 58 58 58 58 56 55 53 51 50 49 47 0.14
15.25 60 59 59 59 58 58 56 54 52 50 48 46 45 0.13
14.75 61 60 59 58 57 56 55 52 50 47 45 44 42 0.13
14.25 61 60 58 57 55 54 52 49 47 45 42 40 39 0.13
13.75 60 58 57 55 53 51 49 46 44 41 39 37 35 0.13
13.25 59 57 55 53 50 48 45 43 40 38 36 34 32 0.14
12.75 57 55 52 50 47 45 42 40 37 35 33 31 29 0.16
12.25 54 52 50 47 44 41 39 36 34 31 30 28 26 0.16
11.75 51 49 47 44 41 38 35 33 31 28 26 25 23 0.17
11.25 48 46 43 40 38 35 32 30 28 26 24 22 20 0.18
10.75 45 42 40 37 34 32 29 27 25 23 21 19 18 0.18
10.25 41 38 36 33 31 28 26 24 22 20 19 17 16 0.18
9.75 37 35 32 30 28 25 23 21 20 18 17 15 14 0.18
Ut 0.20 0.21 0.23 0.21 0.22 0.21 0.22 0.21 0.23 0.21 0.22 0.23 0.22
Y/X(m) 26.39 26.89 27.40 27.91 28.41 28.92 29.43 29.94 30.44 30.95 31.46 31.97 32.47 32.47 Ul
16.75 49 48 46 44 43 40 38 35 33 31 29 26 25 0.14
16.25 48 46 45 43 41 38 36 33 31 29 26 24 22 0.14
15.75 46 44 43 41 38 36 33 31 29 26 24 22 20 0.14
15.25 44 42 40 38 36 33 31 29 26 24 22 20 18 0.13
14.75 40 39 37 35 33 31 28 26 24 22 20 18 17 0.13
14.25 37 35 33 32 30 28 26 24 22 20 18 16 15 0.13
13.75 34 32 30 29 27 25 23 21 19 18 16 15 13 0.13
13.25 30 29 27 25 24 22 21 19 17 16 14 13 12 0.14
12.75 27 26 24 23 21 20 18 17 15 14 13 12 11 0.16
12.25 24 23 21 20 19 17 16 15 14 13 12 11 10 0.16
11.75 22 20 19 18 16 15 14 13 12 11 10 --- --- 0.17
11.25 19 18 17 15 14 13 12 12 11 --- --- --- --- 0.18
10.75 17 16 15 14 13 12 11 --- --- --- --- --- --- 0.18
10.25 15 14 13 12 11 10 --- --- --- --- --- --- --- 0.18
9.75 13 12 11 11 --- --- --- --- --- --- --- --- --- 0.18
Ut 0.23 0.22 0.24 0.23 0.25 0.23 0.24 0.26 0.24 0.25 0.22 0.16 0.15
Y/X(m) 32.98 33.49 34.00 34.50 35.01 35.52 36.03 36.53 37.04 37.55 38.06 38.56 39.07 39.07 Ul
16.75 23 22 20 19 18 16 15 14 13 12 11 10 10 0.14
16.25 21 19 18 17 16 14 13 12 12 11 10 9 9 0.14
15.75 19 17 16 15 14 13 12 11 10 9 9 --- --- 0.14
15.25 17 16 14 13 12 11 10 10 9 8 --- --- --- 0.13
14.75 15 14 13 12 11 10 9 8 --- --- --- --- --- 0.13
14.25 14 13 11 10 10 9 8 --- --- --- --- --- --- 0.13
13.75 12 11 10 9 9 --- --- --- --- --- --- --- --- 0.13
13.25 11 10 9 --- --- --- --- --- --- --- --- --- --- 0.14
12.75 10 --- --- --- --- --- --- --- --- --- --- --- --- 0.16
12.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.16
11.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.17
11.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.18
10.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.18
10.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.18
9.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.18
Ut 0.16 0.17 0.17 0.15 0.16 0.16 0.16 0.16 0.15 0.15 0.16 0.18 0.19
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 25
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación horizontal: Valores en servicio en lux
Y/X(m) 39.58 40.09 40.59 41.10 41.61 42.11 42.62 43.13 43.64 44.14 44.65 45.16 45.67 45.67 Ul
16.75 9 --- --- --- --- --- --- --- --- --- --- --- --- 0.14
16.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.14
15.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.14
15.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
14.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
14.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
13.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
13.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.14
12.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.16
12.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.16
11.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.17
11.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.18
10.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.18
10.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.18
9.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.18
Ut 0.18 0.19 0.22 0.24 0.25 0.28 0.29 0.29 0.31 0.31 0.34 0.37 0.40
Y/X(m) 46.17 46.68 47.19 47.70 48.20 48.71 49.22 49.73 50.23 50.74 51.25 51.76 52.26 52.26 Ul
16.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.14
16.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.14
15.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.14
15.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
14.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
14.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
13.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.13
13.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.14
12.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.16
12.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.16
11.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.17
11.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.18
10.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.18
10.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.18
9.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.18
Ut 0.44 0.48 0.48 0.51 0.55 0.60 0.66 0.67 0.72 0.77 0.82 0.86 0.90
Y/X(m) 52.77 53.28 53.79 54.29 54.80 54.80 Ul
16.75 --- --- --- --- --- 0.14
16.25 --- --- --- --- --- 0.14
15.75 --- --- --- --- --- 0.14
15.25 --- --- --- --- --- 0.13
14.75 --- --- --- --- --- 0.13
14.25 --- --- --- --- --- 0.13
13.75 --- --- --- --- --- 0.13
13.25 --- --- --- --- --- 0.14
12.75 --- --- --- --- --- 0.16
12.25 --- --- --- --- --- 0.16
11.75 --- --- --- --- --- 0.17
11.25 --- --- --- --- --- 0.18
10.75 --- --- --- --- --- 0.18
10.25 --- --- --- --- --- 0.18
9.75 --- --- --- --- --- 0.18
Ut 0.95 0.97 0.98 0.99 ---
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 26
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación horizontal: Valores en servicio en lux
Y/X(m) -0.00 0.51 1.01 1.52 2.03 2.54 3.04 3.55 4.06 4.57 5.07 5.58 6.09 6.09 Ul
9.25 --- --- --- --- --- 32 35 39 41 44 46 48 51 0.19
8.75 --- --- --- --- 29 32 35 38 40 42 44 47 49 0.19
8.25 --- --- --- 25 28 31 34 36 38 40 42 44 47 0.20
7.75 --- --- 21 24 27 30 32 35 36 38 40 43 45 0.20
7.25 --- --- 20 23 25 28 30 32 34 35 37 40 43 0.21
6.75 --- 17 19 21 23 26 28 29 31 32 35 37 --- 0.23
6.25 --- 17 18 20 22 23 25 26 28 30 32 34 37 0.25
5.75 --- --- --- 18 20 21 23 24 25 27 29 32 34 0.27
5.25 --- --- --- --- 18 19 20 22 23 25 27 29 32 0.27
4.75 --- --- --- --- --- 18 19 20 21 23 25 27 30 0.30
4.25 --- --- --- --- --- --- --- 18 20 21 23 25 28 0.35
3.75 --- --- --- --- --- --- --- --- 18 20 22 24 26 0.40
3.25 --- --- --- --- --- --- --- --- --- --- 20 22 24 0.47
2.75 --- --- --- --- --- --- --- --- --- --- --- 20 22 0.56
2.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.60
Ut --- 0.95 0.86 0.74 0.63 0.55 0.53 0.47 0.44 0.44 0.42 0.40 0.42
Y/X(m) 6.60 7.10 7.61 8.12 8.63 9.13 9.64 10.15 10.66 11.16 11.67 12.18 12.69 12.69 Ul
9.25 53 55 56 --- --- --- --- --- --- 58 58 57 57 0.19
8.75 52 54 --- --- --- --- --- --- --- --- 57 56 55 0.19
8.25 50 52 --- --- --- --- --- --- --- --- 56 55 54 0.20
7.75 48 --- 52 54 55 56 --- --- --- 56 55 53 52 0.20
7.25 --- 48 50 51 53 54 55 55 55 54 53 51 49 0.21
6.75 43 45 47 49 50 51 52 53 52 51 50 49 47 0.23
6.25 40 42 44 46 48 49 50 50 50 49 47 46 44 0.25
5.75 37 39 42 44 45 47 47 47 47 46 44 43 41 0.27
5.25 35 37 40 42 43 44 44 44 43 42 41 40 38 0.27
4.75 33 35 38 39 40 41 41 41 40 39 38 36 34 0.30
4.25 31 33 35 37 37 37 37 37 36 35 34 32 31 0.35
3.75 29 31 33 34 34 34 34 34 33 32 30 29 27 0.40
3.25 26 28 30 31 31 31 31 30 29 28 27 26 24 0.47
2.75 24 26 27 27 28 28 27 27 26 25 24 22 21 0.56
2.25 22 23 24 24 24 24 24 23 23 22 21 20 18 0.60
Ut 0.40 0.41 0.37 0.33 0.32 0.29 0.25 0.24 0.27 0.24 0.27 0.26 0.28
Y/X(m) 13.19 13.70 14.21 14.71 15.22 15.73 16.24 16.74 17.25 17.76 18.27 18.77 19.28 19.28 Ul
9.25 56 55 54 52 50 48 46 44 42 40 38 37 35 0.19
8.75 54 52 51 49 47 44 42 40 38 37 35 33 31 0.19
8.25 52 50 48 46 43 41 39 37 35 33 31 29 27 0.20
7.75 50 47 45 42 40 38 35 33 31 29 28 26 24 0.20
7.25 47 45 42 39 37 35 32 30 28 26 25 23 22 0.21
6.75 45 42 39 36 34 32 29 27 25 23 22 20 19 0.23
6.25 42 39 36 34 31 29 26 24 22 21 19 18 17 0.25
5.75 39 36 33 31 28 26 24 22 20 18 17 16 15 0.27
5.25 35 33 30 28 25 23 21 20 18 16 15 14 13 0.27
4.75 32 30 27 25 23 21 19 17 16 15 13 12 --- 0.30
4.25 29 27 25 23 21 19 17 15 14 13 --- --- --- 0.35
3.75 26 24 22 20 18 16 15 14 --- --- --- --- --- 0.40
3.25 23 21 19 18 16 15 --- --- --- --- --- --- --- 0.47
2.75 20 18 17 15 --- --- --- --- --- --- --- --- --- 0.56
2.25 17 16 15 --- --- --- --- --- --- --- --- --- --- 0.60
Ut 0.26 0.27 0.25 0.26 0.26 0.23 0.23 0.21 0.22 0.20 0.21 0.19 0.21
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 27
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación horizontal: Valores en servicio en lux
Y/X(m) 19.79 20.30 20.80 21.31 21.82 22.33 22.83 23.34 23.85 24.36 24.86 25.37 25.88 25.88 Ul
9.25 33 31 29 27 25 23 21 19 17 16 15 14 13 0.19
8.75 29 27 26 24 22 20 18 17 15 14 13 12 11 0.19
8.25 26 24 23 21 19 18 16 15 14 12 12 --- --- 0.20
7.75 23 21 20 18 17 16 14 13 12 11 --- --- --- 0.20
7.25 20 19 17 16 15 14 13 12 --- --- --- --- --- 0.21
6.75 18 16 15 14 13 12 --- --- --- --- --- --- --- 0.23
6.25 15 14 13 12 --- --- --- --- --- --- --- --- --- 0.25
5.75 14 13 --- --- --- --- --- --- --- --- --- --- --- 0.27
5.25 12 --- --- --- --- --- --- --- --- --- --- --- --- 0.27
4.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.30
4.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.35
3.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.40
3.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.47
2.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.56
2.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.60
Ut 0.20 0.21 0.23 0.21 0.22 0.21 0.22 0.21 0.23 0.21 0.22 0.23 0.22
Y/X(m) 26.39 26.89 27.40 27.91 28.41 28.92 29.43 29.94 30.44 30.95 31.46 31.97 32.47 32.47 Ul
9.25 12 11 --- --- --- --- --- --- --- --- --- --- --- 0.19
8.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.19
8.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.20
7.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.20
7.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.21
6.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.23
6.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.25
5.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.27
5.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.27
4.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.30
4.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.35
3.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.40
3.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.47
2.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.56
2.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.60
Ut 0.23 0.22 0.24 0.23 0.25 0.23 0.24 0.26 0.24 0.25 0.22 0.16 0.15
Y/X(m) 32.98 33.49 34.00 34.50 35.01 35.52 36.03 36.53 37.04 37.55 38.06 38.56 39.07 39.07 Ul
9.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.19
8.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.19
8.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.20
7.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.20
7.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.21
6.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.23
6.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.25
5.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.27
5.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.27
4.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.30
4.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.35
3.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.40
3.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.47
2.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.56
2.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.60
Ut 0.16 0.17 0.17 0.15 0.16 0.16 0.16 0.16 0.15 0.15 0.16 0.18 0.19
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 28
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación horizontal: Valores en servicio en lux
Y/X(m) 39.58 40.09 40.59 41.10 41.61 42.11 42.62 43.13 43.64 44.14 44.65 45.16 45.67 45.67 Ul
9.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.19
8.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.19
8.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.20
7.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.20
7.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.21
6.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.23
6.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.25
5.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.27
5.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.27
4.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.30
4.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.35
3.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.40
3.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.47
2.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.56
2.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.60
Ut 0.18 0.19 0.22 0.24 0.25 0.28 0.29 0.29 0.31 0.31 0.34 0.37 0.40
Y/X(m) 46.17 46.68 47.19 47.70 48.20 48.71 49.22 49.73 50.23 50.74 51.25 51.76 52.26 52.26 Ul
9.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.19
8.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.19
8.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.20
7.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.20
7.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.21
6.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.23
6.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.25
5.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.27
5.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.27
4.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.30
4.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.35
3.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.40
3.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.47
2.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.56
2.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.60
Ut 0.44 0.48 0.48 0.51 0.55 0.60 0.66 0.67 0.72 0.77 0.82 0.86 0.90
Y/X(m) 52.77 53.28 53.79 54.29 54.80 54.80 Ul
9.25 --- --- --- --- --- 0.19
8.75 --- --- --- --- --- 0.19
8.25 --- --- --- --- --- 0.20
7.75 --- --- --- --- --- 0.20
7.25 --- --- --- --- --- 0.21
6.75 --- --- --- --- --- 0.23
6.25 --- --- --- --- --- 0.25
5.75 --- --- --- --- --- 0.27
5.25 --- --- --- --- --- 0.27
4.75 --- --- --- --- --- 0.30
4.25 --- --- --- --- --- 0.35
3.75 --- --- --- --- --- 0.40
3.25 --- --- --- --- --- 0.47
2.75 --- --- --- --- --- 0.56
2.25 --- --- --- --- --- 0.60
Ut 0.95 0.97 0.98 0.99 ---
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 29
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación horizontal: Valores en servicio en lux
Y/X(m) -0.00 0.51 1.01 1.52 2.03 2.54 3.04 3.55 4.06 4.57 5.07 5.58 6.09 6.09 Ul
1.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.71
1.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.79
0.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.87
0.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.97
Ut --- 0.95 0.86 0.74 0.63 0.55 0.53 0.47 0.44 0.44 0.42 0.40 0.42
Y/X(m) 6.60 7.10 7.61 8.12 8.63 9.13 9.64 10.15 10.66 11.16 11.67 12.18 12.69 12.69 Ul
1.75 --- --- 21 21 21 21 21 20 20 19 18 17 16 0.71
1.25 --- --- --- 19 19 19 18 18 17 16 15 15 --- 0.79
0.75 --- --- --- --- --- 16 16 16 15 14 --- --- --- 0.87
0.25 --- --- --- --- --- --- 14 13 --- --- --- --- --- 0.97
Ut 0.40 0.41 0.37 0.33 0.32 0.29 0.25 0.24 0.27 0.24 0.27 0.26 0.28
Y/X(m) 13.19 13.70 14.21 14.71 15.22 15.73 16.24 16.74 17.25 17.76 18.27 18.77 19.28 19.28 Ul
1.75 15 --- --- --- --- --- --- --- --- --- --- --- --- 0.71
1.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.79
0.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.87
0.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.97
Ut 0.26 0.27 0.25 0.26 0.26 0.23 0.23 0.21 0.22 0.20 0.21 0.19 0.21
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 30
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación horizontal: Valores en servicio en lux
Y/X(m) 19.79 20.30 20.80 21.31 21.82 22.33 22.83 23.34 23.85 24.36 24.86 25.37 25.88 25.88 Ul
1.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.71
1.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.79
0.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.87
0.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.97
Ut 0.20 0.21 0.23 0.21 0.22 0.21 0.22 0.21 0.23 0.21 0.22 0.23 0.22
Y/X(m) 26.39 26.89 27.40 27.91 28.41 28.92 29.43 29.94 30.44 30.95 31.46 31.97 32.47 32.47 Ul
1.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.71
1.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.79
0.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.87
0.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.97
Ut 0.23 0.22 0.24 0.23 0.25 0.23 0.24 0.26 0.24 0.25 0.22 0.16 0.15
Y/X(m) 32.98 33.49 34.00 34.50 35.01 35.52 36.03 36.53 37.04 37.55 38.06 38.56 39.07 39.07 Ul
1.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.71
1.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.79
0.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.87
0.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.97
Ut 0.16 0.17 0.17 0.15 0.16 0.16 0.16 0.16 0.15 0.15 0.16 0.18 0.19
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 31
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación horizontal: Valores en servicio en lux
Y/X(m) 39.58 40.09 40.59 41.10 41.61 42.11 42.62 43.13 43.64 44.14 44.65 45.16 45.67 45.67 Ul
1.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.71
1.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.79
0.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.87
0.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.97
Ut 0.18 0.19 0.22 0.24 0.25 0.28 0.29 0.29 0.31 0.31 0.34 0.37 0.40
Y/X(m) 46.17 46.68 47.19 47.70 48.20 48.71 49.22 49.73 50.23 50.74 51.25 51.76 52.26 52.26 Ul
1.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.71
1.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.79
0.75 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.87
0.25 --- --- --- --- --- --- --- --- --- --- --- --- --- 0.97
Ut 0.44 0.48 0.48 0.51 0.55 0.60 0.66 0.67 0.72 0.77 0.82 0.86 0.90
Y/X(m) 52.77 53.28 53.79 54.29 54.80 54.80 Ul
1.75 --- --- --- --- --- 0.71
1.25 --- --- --- --- --- 0.79
0.75 --- --- --- --- --- 0.87
0.25 --- --- --- --- --- 0.97
Ut 0.95 0.97 0.98 0.99 ---
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 32
Desarrollo del Proyecto
G / Cálculos
TODO - Isolíneas - Iluminancia
Origen zona de estudioPosición: X: -0.00 m Y: 0.00 m Z: 0.00 m
IluminanciaMedia: Emed = 31.60 luxMínima: Emin = 1.88 luxMáxima: Emax = 65.03 lux
UniformidadesMedia: Umed = Emin/Emed= 0.06Extrema: Uex = Emin/Emax = 0.03
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 33
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación semicilíndrica: Valores en servicio en lux
Y/X(m) -0.00 0.51 1.01 1.52 2.03 2.54 3.04 3.55 4.06 4.57 5.07 5.58 6.09 6.09 Ul
46.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
46.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
45.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
45.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
44.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
44.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
43.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
43.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
42.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
42.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
41.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
41.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
40.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
40.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
39.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
Ut --- --- --- --- --- --- --- --- --- --- --- --- ---
Y/X(m) 6.60 7.10 7.61 8.12 8.63 9.13 9.64 10.15 10.66 11.16 11.67 12.18 12.69 12.69 Ul
46.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
46.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
45.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
45.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
44.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
44.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
43.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
43.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
42.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
42.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
41.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
41.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
40.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
40.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
39.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
Ut --- --- --- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Y/X(m) 13.19 13.70 14.21 14.71 15.22 15.73 16.24 16.74 17.25 17.76 18.27 18.77 19.28 19.28 Ul
46.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
46.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
45.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
45.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
44.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
44.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
43.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
43.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
42.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
42.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
41.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
41.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
40.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
40.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
39.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
Ut 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.01 0.00 0.00 0.00 0.00
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 34
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación semicilíndrica: Valores en servicio en lux
Y/X(m) 19.79 20.30 20.80 21.31 21.82 22.33 22.83 23.34 23.85 24.36 24.86 25.37 25.88 25.88 Ul
46.75 0 0 0 0 0 0 0 0 0 1 1 1 1 0.00
46.25 0 0 0 0 1 1 1 1 1 1 1 1 1 0.00
45.75 0 0 1 1 1 1 1 1 1 1 1 1 1 0.00
45.25 0 0 1 1 1 1 1 1 1 1 1 1 1 0.00
44.75 0 0 1 1 1 1 1 1 1 1 1 1 1 0.00
44.25 0 0 1 1 1 1 1 1 1 1 1 1 1 0.00
43.75 0 0 1 1 1 1 1 1 1 1 1 1 1 0.00
43.25 0 0 1 1 1 1 1 1 1 1 1 1 1 0.00
42.75 0 0 1 1 1 1 1 1 1 1 1 1 1 0.00
42.25 0 0 1 1 1 1 1 1 1 1 2 2 2 0.00
41.75 0 0 1 2 2 2 2 2 2 2 2 2 2 0.00
41.25 0 0 2 2 2 2 2 2 2 2 2 2 2 0.00
40.75 0 0 2 2 2 2 2 2 2 2 2 3 3 0.00
40.25 0 0 2 2 2 2 2 2 2 3 3 3 3 0.00
39.75 0 0 2 2 3 3 3 3 3 3 3 4 4 0.00
Ut 0.00 0.00 0.02 0.02 0.02 0.02 0.02 0.02 0.03 0.03 0.03 0.02 0.02
Y/X(m) 26.39 26.89 27.40 27.91 28.41 28.92 29.43 29.94 30.44 30.95 31.46 31.97 32.47 32.47 Ul
46.75 1 1 3 3 3 3 3 3 3 3 3 3 3 0.00
46.25 1 1 4 4 4 4 4 4 4 4 4 4 4 0.00
45.75 1 1 4 4 5 5 4 4 4 4 4 4 4 0.00
45.25 1 1 5 5 5 5 5 5 5 5 5 5 5 0.00
44.75 1 1 6 6 6 6 6 6 6 6 6 5 5 0.00
44.25 1 1 7 7 7 7 7 7 7 7 7 6 6 0.00
43.75 1 1 8 8 8 8 8 8 8 8 7 7 7 0.00
43.25 1 1 9 9 9 9 9 9 9 9 9 8 7 0.00
42.75 2 2 10 10 10 11 11 11 10 10 10 9 8 0.00
42.25 2 2 10 11 12 12 12 12 12 12 11 10 10 0.00
41.75 2 2 11 12 12 13 13 13 13 13 12 11 11 0.00
41.25 3 3 12 12 13 14 14 15 15 14 14 13 12 0.00
40.75 3 3 12 13 14 14 15 16 16 15 15 14 13 0.00
40.25 4 4 12 13 13 14 16 16 16 16 16 15 14 0.00
39.75 4 4 11 12 13 14 15 16 17 17 16 16 15 0.00
Ut 0.02 0.02 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.04 0.04 0.04
Y/X(m) 32.98 33.49 34.00 34.50 35.01 35.52 36.03 36.53 37.04 37.55 38.06 38.56 39.07 39.07 Ul
46.75 3 3 3 3 3 3 3 3 3 3 2 2 2 0.00
46.25 4 3 3 3 3 3 3 3 3 3 3 2 2 0.00
45.75 4 4 4 3 3 3 4 3 3 3 3 3 2 0.00
45.25 4 4 4 4 4 3 4 4 4 3 3 3 3 0.00
44.75 5 5 4 4 4 4 4 4 4 4 3 3 3 0.00
44.25 6 5 5 5 4 4 5 5 4 4 4 3 3 0.00
43.75 6 6 5 5 5 4 5 5 5 4 4 4 3 0.00
43.25 7 6 6 6 5 5 6 5 5 5 4 4 4 0.00
42.75 8 7 7 6 6 5 6 6 5 5 5 4 4 0.00
42.25 9 8 7 7 6 6 7 6 6 5 5 5 4 0.00
41.75 10 9 8 7 7 6 7 7 6 6 5 5 5 0.00
41.25 11 10 9 8 7 6 8 7 7 6 6 5 5 0.00
40.75 12 11 10 9 8 7 9 8 7 7 6 6 6 0.00
40.25 13 11 10 9 8 8 10 9 8 8 7 7 6 0.00
39.75 13 12 11 10 9 8 10 10 9 8 8 7 7 0.00
Ut 0.04 0.04 0.04 0.04 0.04 0.03 0.03 0.03 0.03 0.03 0.02 0.02 0.02
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 35
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación semicilíndrica: Valores en servicio en lux
Y/X(m) 39.58 40.09 40.59 41.10 41.61 42.11 42.62 43.13 43.64 44.14 44.65 45.16 45.67 45.67 Ul
46.75 2 2 2 2 2 1 1 1 1 1 1 1 1 0.00
46.25 2 2 2 2 2 2 1 1 1 1 1 1 1 0.00
45.75 2 2 2 2 2 2 2 2 1 1 1 1 1 0.00
45.25 2 2 2 2 2 2 2 2 2 2 1 1 1 0.00
44.75 3 3 2 2 2 2 2 2 2 2 2 1 1 0.00
44.25 3 3 3 2 2 2 2 2 2 2 2 2 2 0.00
43.75 3 3 3 3 3 2 2 2 2 2 2 2 2 0.00
43.25 3 3 3 3 3 3 2 2 2 2 2 2 2 0.00
42.75 4 3 3 3 3 3 3 3 2 2 2 2 2 0.00
42.25 4 4 4 3 3 3 3 3 3 2 2 2 2 0.00
41.75 4 4 4 4 4 3 3 3 3 3 3 2 2 0.00
41.25 5 5 4 4 4 4 4 3 3 3 3 3 2 0.00
40.75 5 5 5 5 4 4 4 4 3 3 3 3 3 0.00
40.25 6 6 5 5 5 4 4 4 4 3 3 3 3 0.00
39.75 7 6 6 6 5 5 5 4 4 4 3 3 3 0.00
Ut 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02
Y/X(m) 46.17 46.68 47.19 47.70 48.20 48.71 49.22 49.73 50.23 50.74 51.25 51.76 52.26 52.26 Ul
46.75 1 1 1 1 1 1 1 1 1 1 1 1 0 0.00
46.25 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
45.75 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
45.25 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
44.75 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
44.25 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
43.75 2 1 1 1 1 1 1 1 1 1 1 1 1 0.00
43.25 2 2 1 1 1 1 1 1 1 1 1 1 1 0.00
42.75 2 2 2 1 1 1 1 1 1 1 1 1 1 0.00
42.25 2 2 2 2 1 1 1 1 1 1 1 1 1 0.00
41.75 2 2 2 2 2 1 1 1 1 1 1 1 1 0.00
41.25 2 2 2 2 2 2 1 1 1 1 1 1 1 0.00
40.75 2 2 2 2 2 2 2 1 1 1 1 1 1 0.00
40.25 3 2 2 2 2 2 2 2 1 1 1 1 1 0.00
39.75 3 3 2 2 2 2 2 2 1 1 1 1 1 0.00
Ut 0.02 0.02 0.02 0.03 0.03 0.03 0.03 0.03 0.04 0.04 0.04 0.04 0.05
Y/X(m) 52.77 53.28 53.79 54.29 54.80 54.80 Ul
46.75 0 0 0 0 0 0.00
46.25 0 0 0 0 0 0.00
45.75 1 0 0 0 0 0.00
45.25 1 1 0 0 0 0.00
44.75 1 1 1 0 0 0.00
44.25 1 1 1 1 0 0.00
43.75 1 1 1 1 0 0.00
43.25 1 1 1 1 1 0.00
42.75 1 1 1 1 1 0.00
42.25 1 1 1 1 1 0.00
41.75 1 1 1 1 1 0.00
41.25 1 1 1 1 1 0.00
40.75 1 1 1 1 1 0.00
40.25 1 1 1 1 1 0.00
39.75 1 1 1 1 1 0.00
Ut 0.05 0.05 0.06 0.06 0.06
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 36
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación semicilíndrica: Valores en servicio en lux
Y/X(m) -0.00 0.51 1.01 1.52 2.03 2.54 3.04 3.55 4.06 4.57 5.07 5.58 6.09 6.09 Ul
39.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
38.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
38.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
37.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
37.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
36.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
36.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
35.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
35.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
34.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
34.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
33.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
33.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
32.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
32.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
Ut --- --- --- --- --- --- --- --- --- --- --- --- ---
Y/X(m) 6.60 7.10 7.61 8.12 8.63 9.13 9.64 10.15 10.66 11.16 11.67 12.18 12.69 12.69 Ul
39.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
38.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
38.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
37.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
37.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
36.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
36.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
35.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
35.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
34.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
34.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
33.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
33.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
32.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
32.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
Ut --- --- --- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Y/X(m) 13.19 13.70 14.21 14.71 15.22 15.73 16.24 16.74 17.25 17.76 18.27 18.77 19.28 19.28 Ul
39.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
38.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
38.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
37.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
37.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
36.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
36.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
35.75 0 0 0 0 0 0 0 0 0 0 1 1 1 0.00
35.25 0 0 0 0 0 0 0 0 1 1 1 1 1 0.00
34.75 0 0 0 0 0 0 1 1 1 1 1 1 1 0.00
34.25 0 0 0 0 0 0 1 1 1 1 1 1 1 0.00
33.75 0 0 0 0 0 0 1 1 1 1 1 1 1 0.00
33.25 0 0 0 0 0 0 1 1 1 1 1 1 1 0.00
32.75 0 0 0 0 0 0 1 1 1 1 1 1 1 0.00
32.25 0 0 0 0 0 0 1 1 1 1 1 1 1 0.00
Ut 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.01 0.00 0.00 0.00 0.00
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 37
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación semicilíndrica: Valores en servicio en lux
Y/X(m) 19.79 20.30 20.80 21.31 21.82 22.33 22.83 23.34 23.85 24.36 24.86 25.37 25.88 25.88 Ul
39.25 0 0 3 3 3 3 3 3 3 3 4 4 4 0.00
38.75 0 0 3 3 3 3 3 4 4 4 4 5 5 0.00
38.25 0 0 3 4 4 4 4 4 4 5 5 6 6 0.00
37.75 0 0 4 4 4 4 4 5 5 5 6 6 7 0.00
37.25 0 0 4 4 4 5 5 5 6 6 7 7 8 0.00
36.75 0 0 4 5 5 5 6 6 6 7 8 8 9 0.00
36.25 0 1 5 5 5 6 6 7 7 8 9 9 10 0.00
35.75 1 1 5 5 6 6 7 7 8 9 9 10 10 0.00
35.25 1 1 5 6 6 7 7 8 9 10 10 11 11 0.00
34.75 1 1 5 6 7 7 8 9 10 11 12 12 12 0.00
34.25 1 1 5 6 7 8 9 10 12 12 13 13 13 0.00
33.75 1 1 5 6 7 8 9 11 13 14 14 14 14 0.00
33.25 1 1 5 5 7 8 10 12 14 15 15 15 14 0.00
32.75 1 1 4 5 7 8 10 12 14 15 15 15 14 0.00
32.25 1 1 3 5 6 9 11 13 14 15 15 15 15 0.00
Ut 0.00 0.00 0.02 0.02 0.02 0.02 0.02 0.02 0.03 0.03 0.03 0.02 0.02
Y/X(m) 26.39 26.89 27.40 27.91 28.41 28.92 29.43 29.94 30.44 30.95 31.46 31.97 32.47 32.47 Ul
39.25 5 5 10 11 12 14 15 16 17 17 17 17 16 0.00
38.75 6 6 10 11 12 13 15 16 17 18 18 17 16 0.00
38.25 7 7 9 10 11 13 15 16 17 18 18 18 17 0.00
37.75 7 7 8 9 11 13 14 16 17 18 18 18 17 0.00
37.25 8 8 9 10 11 13 14 16 17 18 19 18 18 0.00
36.75 9 9 11 11 12 13 14 16 17 18 19 18 18 0.00
36.25 10 10 12 13 13 14 15 16 17 18 18 18 17 0.00
35.75 11 11 14 14 14 14 15 15 16 17 17 17 17 0.00
35.25 11 11 15 15 15 15 15 15 15 16 16 16 16 0.00
34.75 12 12 15 15 15 15 15 15 15 15 15 15 15 0.00
34.25 13 12 16 15 15 15 14 14 14 13 13 14 14 0.00
33.75 13 12 15 15 15 14 14 13 13 13 13 12 13 0.00
33.25 13 12 15 15 14 14 13 12 12 12 12 12 12 0.00
32.75 13 12 15 14 14 13 12 12 11 11 11 11 11 0.00
32.25 14 13 15 14 13 13 12 11 11 10 10 10 9 0.00
Ut 0.02 0.02 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.04 0.04 0.04
Y/X(m) 32.98 33.49 34.00 34.50 35.01 35.52 36.03 36.53 37.04 37.55 38.06 38.56 39.07 39.07 Ul
39.25 14 13 12 11 10 9 12 11 10 9 9 8 8 0.00
38.75 15 14 13 11 11 9 13 12 11 10 10 9 9 0.00
38.25 16 15 13 12 11 10 14 13 12 12 11 10 10 0.00
37.75 16 15 14 13 12 11 15 15 14 13 12 11 11 0.00
37.25 16 15 14 13 12 11 17 16 15 14 14 13 12 0.00
36.75 17 15 14 13 13 12 18 17 17 16 15 14 13 0.00
36.25 16 16 15 14 13 12 19 19 18 17 16 16 15 0.00
35.75 16 15 15 14 14 13 20 20 19 19 18 17 16 0.00
35.25 15 15 14 13 14 13 21 21 20 20 19 18 18 0.00
34.75 14 14 14 13 14 13 21 21 21 21 20 20 19 0.00
34.25 13 13 13 12 13 13 21 21 21 21 21 21 20 0.00
33.75 13 12 12 12 13 12 20 20 21 21 21 21 21 0.00
33.25 11 11 11 11 12 12 19 19 20 21 21 21 21 0.00
32.75 10 10 10 10 12 12 17 18 19 20 21 21 21 0.00
32.25 9 9 9 9 11 11 16 17 18 19 20 21 21 0.00
Ut 0.04 0.04 0.04 0.04 0.04 0.03 0.03 0.03 0.03 0.03 0.02 0.02 0.02
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 38
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación semicilíndrica: Valores en servicio en lux
Y/X(m) 39.58 40.09 40.59 41.10 41.61 42.11 42.62 43.13 43.64 44.14 44.65 45.16 45.67 45.67 Ul
39.25 7 7 6 6 6 5 5 5 4 4 4 3 3 0.00
38.75 8 8 7 7 6 6 5 5 5 4 4 4 4 0.00
38.25 9 8 8 7 7 6 6 5 5 5 4 4 4 0.00
37.75 10 9 9 8 7 7 6 6 5 5 5 4 4 0.00
37.25 11 10 10 9 8 7 7 6 6 6 5 5 4 0.00
36.75 12 11 11 10 9 8 8 7 6 6 6 5 5 0.00
36.25 14 13 12 11 10 9 8 8 7 6 6 6 5 0.00
35.75 15 14 13 12 11 10 9 8 8 7 6 6 5 0.00
35.25 16 15 14 13 12 11 10 9 8 8 7 6 6 0.00
34.75 18 16 15 14 13 11 11 10 9 8 7 7 6 0.00
34.25 19 17 16 15 14 12 11 10 10 9 8 7 7 0.00
33.75 20 19 17 16 15 14 12 11 10 10 9 8 7 0.00
33.25 20 19 18 17 16 15 13 12 11 10 9 9 8 0.00
32.75 21 20 19 18 17 16 15 13 12 11 10 9 8 0.00
32.25 21 21 20 19 18 17 16 15 13 12 11 10 9 0.00
Ut 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02
Y/X(m) 46.17 46.68 47.19 47.70 48.20 48.71 49.22 49.73 50.23 50.74 51.25 51.76 52.26 52.26 Ul
39.25 3 3 3 2 2 2 2 2 2 1 1 1 1 0.00
38.75 3 3 3 3 2 2 2 2 2 2 1 1 1 0.00
38.25 4 3 3 3 3 2 2 2 2 2 2 1 1 0.00
37.75 4 3 3 3 3 2 2 2 2 2 2 2 1 0.00
37.25 4 4 3 3 3 3 2 2 2 2 2 2 2 0.00
36.75 4 4 4 3 3 3 3 2 2 2 2 2 2 0.00
36.25 5 4 4 4 3 3 3 3 2 2 2 2 2 0.00
35.75 5 5 4 4 4 3 3 3 3 2 2 2 2 0.00
35.25 5 5 5 4 4 3 3 3 3 3 2 2 2 0.00
34.75 6 5 5 4 4 4 3 3 3 3 2 2 2 0.00
34.25 6 6 5 5 4 4 4 3 3 3 3 2 2 0.00
33.75 7 6 6 5 5 4 4 4 3 3 3 3 2 0.00
33.25 7 7 6 5 5 5 4 4 4 3 3 3 2 0.00
32.75 8 7 6 6 5 5 5 4 4 3 3 3 3 0.00
32.25 8 8 7 6 6 5 5 4 4 4 3 3 3 0.00
Ut 0.02 0.02 0.02 0.03 0.03 0.03 0.03 0.03 0.04 0.04 0.04 0.04 0.05
Y/X(m) 52.77 53.28 53.79 54.29 54.80 54.80 Ul
39.25 1 1 1 1 1 0.00
38.75 1 1 1 1 1 0.00
38.25 1 1 1 1 1 0.00
37.75 1 1 1 1 1 0.00
37.25 1 1 1 1 1 0.00
36.75 2 1 1 1 1 0.00
36.25 2 1 1 1 1 0.00
35.75 2 2 1 1 1 0.00
35.25 2 2 2 1 1 0.00
34.75 2 2 2 2 1 0.00
34.25 2 2 2 2 1 0.00
33.75 2 2 2 2 2 0.00
33.25 2 2 2 2 2 0.00
32.75 2 2 2 2 2 0.00
32.25 3 2 2 2 2 0.00
Ut 0.05 0.05 0.06 0.06 0.06
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 39
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación semicilíndrica: Valores en servicio en lux
Y/X(m) -0.00 0.51 1.01 1.52 2.03 2.54 3.04 3.55 4.06 4.57 5.07 5.58 6.09 6.09 Ul
31.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
31.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
30.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
30.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
29.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
29.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
28.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
28.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
27.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
27.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
26.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
26.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
25.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
25.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
24.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
Ut --- --- --- --- --- --- --- --- --- --- --- --- ---
Y/X(m) 6.60 7.10 7.61 8.12 8.63 9.13 9.64 10.15 10.66 11.16 11.67 12.18 12.69 12.69 Ul
31.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
31.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
30.75 0 0 0 0 0 0 0 0 0 0 1 1 1 0.00
30.25 0 0 0 0 0 0 0 1 1 1 1 1 1 0.00
29.75 0 0 0 0 0 1 1 1 1 1 1 1 1 0.00
29.25 0 0 0 0 0 1 1 1 1 1 1 1 1 0.00
28.75 0 0 0 0 1 1 1 1 1 1 1 1 1 0.00
28.25 0 0 0 1 1 1 1 1 1 1 1 1 1 0.00
27.75 0 0 0 1 1 1 1 1 1 1 1 1 1 0.00
27.25 0 0 0 1 1 1 1 1 1 1 1 1 1 0.00
26.75 0 0 0 1 1 1 1 1 1 1 1 1 1 0.00
26.25 0 0 0 1 1 1 1 1 1 1 1 1 1 0.00
25.75 0 0 0 1 1 1 1 1 1 2 2 2 2 0.00
25.25 0 0 0 1 1 1 1 2 2 2 2 2 2 0.00
24.75 0 0 0 1 1 2 2 2 2 2 2 2 2 0.00
Ut --- --- --- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Y/X(m) 13.19 13.70 14.21 14.71 15.22 15.73 16.24 16.74 17.25 17.76 18.27 18.77 19.28 19.28 Ul
31.75 0 0 0 0 0 0 1 1 1 1 1 1 1 0.00
31.25 0 0 0 0 0 0 1 1 1 1 1 1 1 0.00
30.75 1 1 1 1 1 1 1 1 1 1 2 2 2 0.00
30.25 1 1 1 1 1 1 1 1 1 2 2 2 2 0.00
29.75 1 1 1 1 1 1 2 2 2 2 2 2 2 0.00
29.25 1 1 1 1 1 1 2 2 2 2 2 2 2 0.00
28.75 1 1 1 1 1 1 2 2 2 2 3 3 3 0.00
28.25 1 1 1 1 1 1 2 2 2 3 3 3 3 0.00
27.75 1 1 1 1 1 1 2 2 3 3 3 3 4 0.00
27.25 1 1 1 1 1 1 3 3 3 4 4 4 4 0.00
26.75 1 1 1 1 1 1 3 3 3 4 4 4 5 0.00
26.25 1 1 1 1 1 1 3 4 4 5 5 5 5 0.00
25.75 2 2 2 2 1 1 4 4 4 5 6 6 6 0.00
25.25 2 2 2 2 2 2 5 5 5 6 6 7 7 0.00
24.75 2 2 2 2 2 2 5 5 6 7 7 8 8 0.00
Ut 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.01 0.00 0.00 0.00 0.00
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 40
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación semicilíndrica: Valores en servicio en lux
Y/X(m) 19.79 20.30 20.80 21.31 21.82 22.33 22.83 23.34 23.85 24.36 24.86 25.37 25.88 25.88 Ul
31.75 1 1 3 5 7 9 11 13 14 15 15 15 15 0.00
31.25 2 2 4 6 8 10 12 14 15 15 15 15 15 0.00
30.75 2 2 6 7 9 11 13 14 15 15 15 15 14 0.00
30.25 2 2 7 9 10 12 13 15 16 16 15 15 14 0.00
29.75 2 2 9 10 11 13 14 15 16 16 15 15 14 0.00
29.25 2 3 10 11 13 14 15 16 16 16 15 15 14 0.00
28.75 3 3 11 13 14 15 15 16 16 15 15 15 14 0.00
28.25 3 3 12 13 14 15 15 15 15 15 14 15 14 0.00
27.75 4 4 13 14 14 15 15 15 15 14 14 14 13 0.00
27.25 4 4 13 14 14 15 15 14 14 13 13 14 13 0.00
26.75 5 5 14 14 14 14 14 14 13 13 12 14 13 0.00
26.25 6 6 14 14 14 14 14 14 13 12 12 13 13 0.00
25.75 6 7 14 14 14 14 13 13 13 12 11 13 13 0.00
25.25 7 7 14 14 14 14 13 13 12 12 11 13 13 0.00
24.75 8 8 14 14 14 14 13 13 12 11 11 13 13 0.00
Ut 0.00 0.00 0.02 0.02 0.02 0.02 0.02 0.02 0.03 0.03 0.03 0.02 0.02
Y/X(m) 26.39 26.89 27.40 27.91 28.41 28.92 29.43 29.94 30.44 30.95 31.46 31.97 32.47 32.47 Ul
31.75 14 13 15 14 13 12 11 11 10 10 9 9 9 0.00
31.25 14 12 14 13 12 11 11 10 9 9 9 8 8 0.00
30.75 13 12 14 13 12 11 10 10 9 8 8 8 7 0.00
30.25 13 12 13 12 11 11 10 9 9 8 8 7 7 0.00
29.75 13 12 13 12 11 10 10 9 8 8 7 7 7 0.00
29.25 13 12 13 12 11 10 9 9 8 8 7 7 6 0.00
28.75 13 12 12 11 11 10 9 9 8 8 7 7 6 0.00
28.25 13 12 12 11 11 10 9 9 8 8 7 7 6 0.00
27.75 12 12 12 11 11 10 9 9 8 8 7 7 6 0.00
27.25 12 11 12 11 11 10 9 9 8 8 7 7 7 0.00
26.75 12 11 12 11 11 10 10 9 9 8 8 7 7 0.00
26.25 12 12 12 11 11 10 10 9 9 8 8 8 7 0.00
25.75 12 12 12 11 11 10 10 10 9 9 8 8 8 0.00
25.25 12 12 12 12 11 11 10 10 10 9 9 9 9 0.00
24.75 13 12 12 12 12 11 11 10 10 10 10 10 10 0.00
Ut 0.02 0.02 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.04 0.04 0.04
Y/X(m) 32.98 33.49 34.00 34.50 35.01 35.52 36.03 36.53 37.04 37.55 38.06 38.56 39.07 39.07 Ul
31.75 9 9 9 9 11 11 14 15 16 18 19 21 21 0.00
31.25 8 8 8 8 11 11 12 14 16 17 19 20 22 0.00
30.75 7 7 7 7 10 10 12 13 15 17 19 20 22 0.00
30.25 7 7 7 7 10 10 12 14 15 17 19 20 22 0.00
29.75 6 6 6 6 10 10 13 14 16 17 19 21 22 0.00
29.25 6 6 6 6 10 10 14 15 16 17 19 21 22 0.00
28.75 6 6 6 6 10 10 15 16 17 18 19 20 22 0.00
28.25 6 6 6 6 10 10 15 16 17 18 19 20 22 0.00
27.75 6 6 6 6 10 11 16 17 18 19 20 21 22 0.00
27.25 6 6 6 6 10 11 16 17 18 19 20 21 22 0.00
26.75 7 7 6 6 10 11 15 17 18 19 21 22 23 0.00
26.25 7 7 7 7 10 10 15 16 18 20 21 23 23 0.00
25.75 8 8 7 7 9 10 15 16 18 20 22 23 23 0.00
25.25 9 8 8 8 9 10 15 17 18 20 22 22 23 0.00
24.75 9 9 8 8 9 11 15 17 19 20 22 22 22 0.00
Ut 0.04 0.04 0.04 0.04 0.04 0.03 0.03 0.03 0.03 0.03 0.02 0.02 0.02
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 41
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación semicilíndrica: Valores en servicio en lux
Y/X(m) 39.58 40.09 40.59 41.10 41.61 42.11 42.62 43.13 43.64 44.14 44.65 45.16 45.67 45.67 Ul
31.75 22 22 21 20 19 18 17 16 14 13 12 11 10 0.00
31.25 22 22 22 21 20 19 18 17 15 14 13 12 11 0.00
30.75 23 23 23 22 21 20 19 18 16 15 14 12 11 0.00
30.25 23 24 23 23 22 21 20 18 17 16 14 13 12 0.00
29.75 24 24 24 23 23 22 21 19 18 17 15 14 13 0.00
29.25 24 24 24 24 23 22 21 20 19 17 16 15 13 0.00
28.75 23 24 24 24 24 23 22 21 19 18 16 15 14 0.00
28.25 23 24 24 24 24 23 22 21 19 18 17 15 14 0.00
27.75 22 23 24 24 24 23 22 21 19 18 17 15 14 0.00
27.25 23 23 23 23 23 22 21 20 19 18 16 15 14 0.00
26.75 23 23 23 23 22 22 21 20 18 17 16 14 13 0.00
26.25 23 23 22 22 22 21 20 19 18 16 15 14 13 0.00
25.75 23 22 22 21 20 20 19 18 17 16 14 13 12 0.00
25.25 22 21 21 20 19 18 18 17 16 15 13 12 11 0.00
24.75 21 21 20 19 18 17 16 15 14 13 12 11 11 0.00
Ut 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02
Y/X(m) 46.17 46.68 47.19 47.70 48.20 48.71 49.22 49.73 50.23 50.74 51.25 51.76 52.26 52.26 Ul
31.75 9 8 7 7 6 6 5 5 4 4 3 3 3 0.00
31.25 10 9 8 7 7 6 5 5 4 4 4 3 3 0.00
30.75 10 9 8 8 7 6 6 5 5 4 4 3 3 0.00
30.25 11 10 9 8 7 7 6 5 5 4 4 4 3 0.00
29.75 12 10 9 8 8 7 6 6 5 5 4 4 3 0.00
29.25 12 11 10 9 8 7 6 6 5 5 4 4 3 0.00
28.75 12 11 10 9 8 7 6 6 5 5 4 4 3 0.00
28.25 12 11 10 9 8 7 7 6 5 5 4 4 3 0.00
27.75 12 11 10 9 8 7 7 6 5 5 4 4 4 0.00
27.25 12 11 10 9 8 7 7 6 5 5 4 4 4 0.00
26.75 12 11 10 9 8 7 6 6 5 5 4 4 3 0.00
26.25 12 10 9 9 8 7 6 6 5 5 4 4 3 0.00
25.75 11 10 9 8 7 7 6 6 5 5 4 4 3 0.00
25.25 10 9 9 8 7 6 6 5 5 4 4 4 3 0.00
24.75 10 9 8 7 7 6 6 5 5 4 4 3 3 0.00
Ut 0.02 0.02 0.02 0.03 0.03 0.03 0.03 0.03 0.04 0.04 0.04 0.04 0.05
Y/X(m) 52.77 53.28 53.79 54.29 54.80 54.80 Ul
31.75 3 2 2 2 2 0.00
31.25 3 2 2 2 2 0.00
30.75 3 3 2 2 2 0.00
30.25 3 3 2 2 2 0.00
29.75 3 3 2 2 2 0.00
29.25 3 3 3 2 2 0.00
28.75 3 3 3 2 2 0.00
28.25 3 3 3 2 2 0.00
27.75 3 3 3 2 2 0.00
27.25 3 3 3 2 2 0.00
26.75 3 3 3 2 2 0.00
26.25 3 3 3 2 2 0.00
25.75 3 3 3 2 2 0.00
25.25 3 3 2 2 2 0.00
24.75 3 3 2 2 2 0.00
Ut 0.05 0.05 0.06 0.06 0.06
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 42
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación semicilíndrica: Valores en servicio en lux
Y/X(m) -0.00 0.51 1.01 1.52 2.03 2.54 3.04 3.55 4.06 4.57 5.07 5.58 6.09 6.09 Ul
24.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
23.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
23.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
22.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
22.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
21.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
21.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
20.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
20.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
19.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
19.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
18.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
18.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
17.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
17.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
Ut --- --- --- --- --- --- --- --- --- --- --- --- ---
Y/X(m) 6.60 7.10 7.61 8.12 8.63 9.13 9.64 10.15 10.66 11.16 11.67 12.18 12.69 12.69 Ul
24.25 0 0 0 1 1 2 2 2 2 2 2 2 2 0.00
23.75 0 0 0 1 2 2 2 2 2 2 3 3 3 0.00
23.25 0 0 0 2 2 2 2 3 3 3 3 3 3 0.00
22.75 0 0 0 2 2 3 3 3 3 3 3 3 3 0.00
22.25 0 0 0 2 2 3 3 3 3 4 4 4 3 0.00
21.75 0 0 0 2 3 3 4 4 4 4 4 4 4 0.00
21.25 0 0 0 3 3 4 4 4 4 4 4 4 4 0.00
20.75 0 0 0 3 3 4 4 5 5 5 5 5 5 0.00
20.25 0 0 0 3 4 5 5 5 5 5 5 5 5 0.00
19.75 0 0 0 4 4 5 6 6 6 6 6 6 6 0.00
19.25 0 0 0 4 5 6 6 7 7 7 7 6 6 0.00
18.75 0 0 0 5 5 7 7 7 7 7 7 7 7 0.00
18.25 0 0 0 5 6 7 8 8 8 8 8 7 7 0.00
17.75 0 0 0 6 6 8 9 9 9 9 8 8 8 0.00
17.25 0 0 0 6 7 9 9 9 9 9 9 8 8 0.00
Ut --- --- --- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Y/X(m) 13.19 13.70 14.21 14.71 15.22 15.73 16.24 16.74 17.25 17.76 18.27 18.77 19.28 19.28 Ul
24.25 2 2 2 2 2 2 6 6 6 8 8 9 9 0.00
23.75 2 2 2 2 2 2 7 7 7 9 10 10 10 0.00
23.25 3 3 3 2 2 2 8 8 8 10 11 11 11 0.00
22.75 3 3 3 3 3 2 9 9 9 12 12 12 12 0.00
22.25 3 3 3 3 3 3 10 10 10 13 13 13 14 0.00
21.75 4 4 3 3 3 3 11 11 11 14 15 15 15 0.00
21.25 4 4 4 4 3 3 11 12 12 15 16 16 16 0.00
20.75 4 4 4 4 4 3 12 12 13 16 17 17 17 0.00
20.25 5 5 4 4 4 4 12 13 13 17 18 18 17 0.00
19.75 5 5 5 5 4 4 12 12 13 17 18 18 17 0.00
19.25 6 5 5 5 5 4 11 12 12 17 17 18 17 0.00
18.75 6 6 6 5 5 5 11 11 11 16 16 17 17 0.00
18.25 7 6 6 6 5 5 10 10 10 15 16 17 17 0.00
17.75 7 7 6 6 6 6 9 9 9 14 16 17 17 0.00
17.25 7 7 7 6 6 6 7 8 9 14 15 17 17 0.00
Ut 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.01 0.00 0.00 0.00 0.00
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 43
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación semicilíndrica: Valores en servicio en lux
Y/X(m) 19.79 20.30 20.80 21.31 21.82 22.33 22.83 23.34 23.85 24.36 24.86 25.37 25.88 25.88 Ul
24.25 9 9 15 14 14 14 13 13 12 11 10 13 13 0.00
23.75 10 11 15 15 14 14 13 13 12 11 10 14 14 0.00
23.25 12 12 16 15 15 14 13 13 12 11 10 14 14 0.00
22.75 13 13 16 16 15 14 13 13 12 11 10 14 14 0.00
22.25 14 14 17 16 15 14 13 13 12 11 11 14 14 0.00
21.75 15 14 17 16 15 14 14 13 12 11 11 14 14 0.00
21.25 15 15 17 16 15 15 14 13 12 12 11 14 14 0.00
20.75 16 16 17 16 15 15 14 13 12 12 11 13 14 0.00
20.25 17 16 17 16 15 15 14 13 12 12 11 13 13 0.00
19.75 17 16 17 16 16 15 14 13 13 12 12 12 13 0.00
19.25 17 16 17 16 16 15 14 14 13 13 13 13 14 0.00
18.75 17 16 17 17 16 16 15 15 14 14 13 15 16 0.00
18.25 17 16 17 17 17 17 16 16 15 15 14 18 18 0.00
17.75 17 17 18 18 18 18 17 17 16 15 15 20 20 0.00
17.25 18 18 19 19 19 19 18 18 17 16 15 22 22 0.00
Ut 0.00 0.00 0.02 0.02 0.02 0.02 0.02 0.02 0.03 0.03 0.03 0.02 0.02
Y/X(m) 26.39 26.89 27.40 27.91 28.41 28.92 29.43 29.94 30.44 30.95 31.46 31.97 32.47 32.47 Ul
24.25 13 13 13 12 12 12 11 11 11 11 11 11 11 0.00
23.75 13 13 13 13 13 12 12 12 12 12 12 12 11 0.00
23.25 14 13 14 13 13 13 13 13 13 13 13 12 12 0.00
22.75 14 14 14 14 14 14 14 14 14 14 13 13 13 0.00
22.25 14 15 15 15 15 15 15 15 15 15 14 14 13 0.00
21.75 15 15 15 15 16 16 16 16 16 15 15 15 14 0.00
21.25 15 15 16 16 17 17 17 17 17 16 16 15 14 0.00
20.75 14 15 16 17 18 19 19 18 18 17 16 16 15 0.00
20.25 14 15 16 18 19 20 20 19 18 18 17 16 15 0.00
19.75 14 16 17 18 20 20 20 20 19 18 17 16 15 0.00
19.25 15 17 18 19 20 21 21 20 19 18 16 15 14 0.00
18.75 17 18 19 20 21 21 21 20 19 17 16 15 14 0.00
18.25 19 19 20 21 21 21 21 20 18 17 16 14 13 0.00
17.75 20 21 21 22 21 21 20 19 18 16 15 14 12 0.00
17.25 22 22 22 22 22 21 20 18 17 16 14 13 12 0.00
Ut 0.02 0.02 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.04 0.04 0.04
Y/X(m) 32.98 33.49 34.00 34.50 35.01 35.52 36.03 36.53 37.04 37.55 38.06 38.56 39.07 39.07 Ul
24.25 10 10 9 9 11 12 16 18 19 21 21 22 21 0.00
23.75 11 10 10 9 13 14 17 19 20 21 21 21 21 0.00
23.25 11 11 10 10 15 15 18 19 20 21 21 21 20 0.00
22.75 12 11 11 10 17 17 19 20 21 21 21 20 19 0.00
22.25 13 12 11 10 18 18 20 21 21 21 20 20 18 0.00
21.75 13 12 12 11 19 19 20 21 21 20 20 19 17 0.00
21.25 14 13 12 11 19 19 20 20 20 19 18 17 16 0.00
20.75 14 13 12 11 19 19 19 19 19 18 17 16 15 0.00
20.25 14 13 12 11 18 18 18 18 17 17 16 15 14 0.00
19.75 13 12 11 10 17 17 17 16 16 15 14 13 12 0.00
19.25 13 12 11 10 16 15 16 15 14 14 13 12 11 0.00
18.75 12 11 10 9 15 14 14 14 13 12 12 11 10 0.00
18.25 12 11 10 9 14 13 13 12 12 11 10 10 9 0.00
17.75 11 10 9 8 12 12 12 11 10 10 9 9 8 0.00
17.25 10 9 8 8 11 11 10 10 9 9 8 8 7 0.00
Ut 0.04 0.04 0.04 0.04 0.04 0.03 0.03 0.03 0.03 0.03 0.02 0.02 0.02
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 44
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación semicilíndrica: Valores en servicio en lux
Y/X(m) 39.58 40.09 40.59 41.10 41.61 42.11 42.62 43.13 43.64 44.14 44.65 45.16 45.67 45.67 Ul
24.25 21 20 19 18 17 16 15 14 13 12 11 11 10 0.00
23.75 20 19 18 17 16 15 14 13 12 11 10 10 9 0.00
23.25 19 18 17 15 15 14 13 12 11 10 10 9 8 0.00
22.75 18 17 15 14 13 12 12 11 10 9 9 8 8 0.00
22.25 17 16 14 13 12 11 11 10 9 8 8 7 7 0.00
21.75 16 15 13 12 11 10 10 9 8 8 7 7 6 0.00
21.25 15 14 12 11 10 9 9 8 8 7 7 6 6 0.00
20.75 14 13 12 11 10 9 8 7 7 7 6 6 5 0.00
20.25 13 12 11 10 9 8 7 7 6 6 6 5 5 0.00
19.75 12 11 10 9 8 8 7 6 6 6 5 5 5 0.00
19.25 10 10 9 8 8 7 6 6 6 5 5 4 4 0.00
18.75 9 9 8 8 7 6 6 6 5 5 4 4 4 0.00
18.25 9 8 7 7 6 6 6 5 5 4 4 4 4 0.00
17.75 8 7 7 6 6 6 5 5 4 4 4 4 3 0.00
17.25 7 7 6 6 5 5 5 4 4 4 4 3 3 0.00
Ut 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02
Y/X(m) 46.17 46.68 47.19 47.70 48.20 48.71 49.22 49.73 50.23 50.74 51.25 51.76 52.26 52.26 Ul
24.25 9 8 8 7 6 6 5 5 4 4 4 3 3 0.00
23.75 8 8 7 6 6 5 5 5 4 4 4 3 3 0.00
23.25 8 7 7 6 6 5 5 4 4 4 3 3 3 0.00
22.75 7 6 6 6 5 5 4 4 4 3 3 3 3 0.00
22.25 6 6 6 5 5 4 4 4 3 3 3 3 3 0.00
21.75 6 5 5 5 4 4 4 4 3 3 3 3 2 0.00
21.25 5 5 5 4 4 4 4 3 3 3 3 2 2 0.00
20.75 5 5 4 4 4 4 3 3 3 3 2 2 2 0.00
20.25 5 4 4 4 3 3 3 3 3 2 2 2 2 0.00
19.75 4 4 4 3 3 3 3 3 2 2 2 2 2 0.00
19.25 4 4 3 3 3 3 3 2 2 2 2 2 2 0.00
18.75 4 3 3 3 3 3 2 2 2 2 2 2 2 0.00
18.25 3 3 3 3 3 2 2 2 2 2 2 2 1 0.00
17.75 3 3 3 3 2 2 2 2 2 2 2 1 1 0.00
17.25 3 3 2 2 2 2 2 2 2 2 1 1 1 0.00
Ut 0.02 0.02 0.02 0.03 0.03 0.03 0.03 0.03 0.04 0.04 0.04 0.04 0.05
Y/X(m) 52.77 53.28 53.79 54.29 54.80 54.80 Ul
24.25 3 3 2 2 2 0.00
23.75 3 2 2 2 2 0.00
23.25 3 2 2 2 2 0.00
22.75 2 2 2 2 2 0.00
22.25 2 2 2 2 2 0.00
21.75 2 2 2 2 2 0.00
21.25 2 2 2 2 2 0.00
20.75 2 2 2 2 1 0.00
20.25 2 2 2 1 1 0.00
19.75 2 2 1 1 1 0.00
19.25 2 1 1 1 1 0.00
18.75 1 1 1 1 1 0.00
18.25 1 1 1 1 1 0.00
17.75 1 1 1 1 1 0.00
17.25 1 1 1 1 1 0.00
Ut 0.05 0.05 0.06 0.06 0.06
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 45
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación semicilíndrica: Valores en servicio en lux
Y/X(m) -0.00 0.51 1.01 1.52 2.03 2.54 3.04 3.55 4.06 4.57 5.07 5.58 6.09 6.09 Ul
16.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
16.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
15.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
15.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
14.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
14.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
13.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
13.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
12.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
12.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
11.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
11.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
10.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
10.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
9.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
Ut --- --- --- --- --- --- --- --- --- --- --- --- ---
Y/X(m) 6.60 7.10 7.61 8.12 8.63 9.13 9.64 10.15 10.66 11.16 11.67 12.18 12.69 12.69 Ul
16.75 0 0 0 7 7 10 10 10 10 10 9 9 8 0.00
16.25 0 0 0 7 8 10 11 11 10 10 10 9 9 0.00
15.75 0 0 0 8 8 11 11 11 11 11 10 9 9 0.00
15.25 0 0 0 8 9 12 12 11 11 11 10 10 9 0.00
14.75 0 0 0 9 9 12 12 12 11 11 11 10 10 0.00
14.25 0 0 0 9 9 13 12 12 11 11 11 11 10 0.00
13.75 0 0 0 9 9 13 12 12 12 11 11 11 11 0.00
13.25 0 0 0 8 8 12 12 12 12 12 12 12 12 0.00
12.75 0 0 0 7 7 11 12 12 12 12 12 13 13 0.00
12.25 0 0 0 6 6 11 11 12 12 13 13 13 14 0.00
11.75 0 0 0 5 5 10 11 12 13 13 14 14 15 0.00
11.25 0 0 0 3 4 9 10 12 13 13 14 16 17 0.00
10.75 0 0 0 2 3 8 9 11 12 14 15 17 18 0.00
10.25 0 0 0 1 3 7 8 10 12 13 15 17 18 0.00
9.75 0 0 0 1 3 6 7 9 11 13 15 17 18 0.00
Ut --- --- --- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Y/X(m) 13.19 13.70 14.21 14.71 15.22 15.73 16.24 16.74 17.25 17.76 18.27 18.77 19.28 19.28 Ul
16.75 8 7 7 7 7 6 7 8 9 13 15 17 18 0.00
16.25 8 8 7 7 7 7 8 8 9 13 15 16 18 0.00
15.75 8 8 8 8 8 8 9 10 10 13 15 16 18 0.00
15.25 9 9 8 9 9 8 11 11 11 13 15 17 19 0.00
14.75 9 9 9 10 9 9 12 12 12 14 16 17 19 0.00
14.25 10 10 10 11 10 10 14 13 13 16 17 19 20 0.00
13.75 11 11 12 11 11 11 15 14 14 18 19 20 21 0.00
13.25 12 13 13 13 12 12 15 15 14 20 20 21 22 0.00
12.75 13 14 14 14 13 13 16 15 15 21 22 22 22 0.00
12.25 14 15 15 14 14 14 16 16 15 22 22 22 23 0.00
11.75 16 16 16 15 15 14 17 16 15 23 23 23 22 0.00
11.25 17 17 16 16 15 14 16 15 14 23 22 22 22 0.00
10.75 18 18 17 16 15 14 16 15 14 22 21 21 20 0.00
10.25 19 18 18 17 15 14 15 14 13 21 20 19 19 0.00
9.75 19 19 18 17 15 14 15 14 12 19 18 18 17 0.00
Ut 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.01 0.00 0.00 0.00 0.00
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 46
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación semicilíndrica: Valores en servicio en lux
Y/X(m) 19.79 20.30 20.80 21.31 21.82 22.33 22.83 23.34 23.85 24.36 24.86 25.37 25.88 25.88 Ul
16.75 18 19 20 21 20 20 19 18 18 17 16 23 23 0.00
16.25 19 20 21 22 22 21 20 19 18 17 16 24 23 0.00
15.75 19 21 23 23 23 22 21 20 18 17 16 24 23 0.00
15.25 20 21 23 24 23 22 21 20 18 17 16 23 23 0.00
14.75 21 22 23 24 23 22 21 19 18 17 15 22 22 0.00
14.25 21 22 23 23 23 22 20 19 17 16 14 21 20 0.00
13.75 22 23 23 23 22 21 19 18 16 15 14 19 18 0.00
13.25 22 23 23 22 21 20 19 17 16 14 13 17 17 0.00
12.75 23 23 22 21 20 19 17 16 15 13 12 16 15 0.00
12.25 23 22 22 20 19 18 16 15 14 12 11 14 13 0.00
11.75 22 21 20 19 18 16 15 14 12 11 10 13 12 0.00
11.25 21 20 19 18 16 15 14 12 11 10 9 11 11 0.00
10.75 20 19 18 16 15 14 13 11 10 9 8 10 9 0.00
10.25 18 17 16 15 14 13 11 10 9 8 7 9 8 0.00
9.75 16 15 15 13 12 11 10 9 8 7 7 8 8 0.00
Ut 0.00 0.00 0.02 0.02 0.02 0.02 0.02 0.02 0.03 0.03 0.03 0.02 0.02
Y/X(m) 26.39 26.89 27.40 27.91 28.41 28.92 29.43 29.94 30.44 30.95 31.46 31.97 32.47 32.47 Ul
16.75 23 23 23 22 21 20 19 18 16 15 13 12 11 0.00
16.25 23 23 22 22 21 19 18 17 15 14 12 11 10 0.00
15.75 23 22 22 21 20 18 17 16 14 13 12 10 9 0.00
15.25 22 21 21 20 18 17 16 14 13 12 11 10 9 0.00
14.75 21 20 19 18 17 16 14 13 12 11 10 9 8 0.00
14.25 19 18 17 16 15 14 13 12 11 10 9 8 7 0.00
13.75 17 17 16 15 14 13 12 11 10 9 8 7 7 0.00
13.25 16 15 14 13 12 11 11 10 9 8 8 7 6 0.00
12.75 14 13 13 12 11 10 9 9 8 7 7 6 6 0.00
12.25 13 12 11 10 10 9 9 8 7 7 6 6 5 0.00
11.75 11 10 10 9 9 8 8 7 7 6 6 5 5 0.00
11.25 10 9 9 8 8 7 7 6 6 6 5 5 5 0.00
10.75 9 8 8 7 7 7 6 6 5 5 5 4 4 0.00
10.25 8 7 7 7 6 6 6 5 5 5 4 4 4 0.00
9.75 7 7 6 6 6 5 5 5 4 4 4 4 3 0.00
Ut 0.02 0.02 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.04 0.04 0.04
Y/X(m) 32.98 33.49 34.00 34.50 35.01 35.52 36.03 36.53 37.04 37.55 38.06 38.56 39.07 39.07 Ul
16.75 10 9 8 7 10 9 9 9 8 8 8 7 7 0.00
16.25 9 8 7 6 9 8 8 8 7 7 7 6 6 0.00
15.75 8 7 7 6 8 8 7 7 7 6 6 6 6 0.00
15.25 8 7 6 6 7 7 7 6 6 6 5 5 5 0.00
14.75 7 6 6 5 7 6 6 6 5 5 5 5 5 0.00
14.25 7 6 5 5 6 6 5 5 5 5 4 4 4 0.00
13.75 6 6 5 5 6 5 5 5 4 4 4 4 4 0.00
13.25 6 5 5 4 5 5 5 4 4 4 4 3 3 0.00
12.75 5 5 4 4 5 4 4 4 4 3 3 3 3 0.00
12.25 5 5 4 4 4 4 4 4 3 3 3 3 3 0.00
11.75 5 4 4 3 4 4 4 3 3 3 3 3 2 0.00
11.25 4 4 4 3 4 3 3 3 3 3 3 2 2 0.00
10.75 4 4 3 3 3 3 3 3 3 2 2 2 2 0.00
10.25 4 3 3 3 3 3 3 3 2 2 2 2 2 0.00
9.75 3 3 3 3 3 3 3 2 2 2 2 2 2 0.00
Ut 0.04 0.04 0.04 0.04 0.04 0.03 0.03 0.03 0.03 0.03 0.02 0.02 0.02
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 47
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación semicilíndrica: Valores en servicio en lux
Y/X(m) 39.58 40.09 40.59 41.10 41.61 42.11 42.62 43.13 43.64 44.14 44.65 45.16 45.67 45.67 Ul
16.75 6 6 6 5 5 5 4 4 4 4 3 3 3 0.00
16.25 6 6 5 5 5 4 4 4 4 3 3 3 3 0.00
15.75 5 5 5 4 4 4 4 3 3 3 3 3 2 0.00
15.25 5 5 4 4 4 4 3 3 3 3 3 2 2 0.00
14.75 4 4 4 4 4 3 3 3 3 3 2 2 2 0.00
14.25 4 4 4 3 3 3 3 3 3 2 2 2 2 0.00
13.75 4 3 3 3 3 3 3 2 2 2 2 2 2 0.00
13.25 3 3 3 3 3 3 2 2 2 2 2 2 2 0.00
12.75 3 3 3 3 2 2 2 2 2 2 2 2 2 0.00
12.25 3 3 2 2 2 2 2 2 2 2 2 2 1 0.00
11.75 2 2 2 2 2 2 2 2 2 2 1 1 1 0.00
11.25 2 2 2 2 2 2 2 2 2 1 1 1 1 0.00
10.75 2 2 2 2 2 2 2 1 1 1 1 1 1 0.00
10.25 2 2 2 2 2 1 1 1 1 1 1 1 1 0.00
9.75 2 2 2 1 1 1 1 1 1 1 1 1 1 0.00
Ut 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02
Y/X(m) 46.17 46.68 47.19 47.70 48.20 48.71 49.22 49.73 50.23 50.74 51.25 51.76 52.26 52.26 Ul
16.75 3 2 2 2 2 2 2 2 2 1 1 1 1 0.00
16.25 2 2 2 2 2 2 2 2 1 1 1 1 1 0.00
15.75 2 2 2 2 2 2 2 1 1 1 1 1 1 0.00
15.25 2 2 2 2 2 1 1 1 1 1 1 1 1 0.00
14.75 2 2 2 2 1 1 1 1 1 1 1 1 1 0.00
14.25 2 2 2 1 1 1 1 1 1 1 1 1 1 0.00
13.75 2 2 1 1 1 1 1 1 1 1 1 1 1 0.00
13.25 2 1 1 1 1 1 1 1 1 1 1 1 1 0.00
12.75 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
12.25 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
11.75 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
11.25 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
10.75 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
10.25 1 1 1 1 1 1 1 1 1 1 1 1 0 0.00
9.75 1 1 1 1 1 1 1 1 1 1 1 0 0 0.00
Ut 0.02 0.02 0.02 0.03 0.03 0.03 0.03 0.03 0.04 0.04 0.04 0.04 0.05
Y/X(m) 52.77 53.28 53.79 54.29 54.80 54.80 Ul
16.75 1 1 1 1 1 0.00
16.25 1 1 1 1 1 0.00
15.75 1 1 1 1 1 0.00
15.25 1 1 1 1 1 0.00
14.75 1 1 1 1 1 0.00
14.25 1 1 1 1 1 0.00
13.75 1 1 1 1 1 0.00
13.25 1 1 1 1 1 0.00
12.75 1 1 1 1 1 0.00
12.25 1 1 1 1 0 0.00
11.75 1 1 0 0 0 0.00
11.25 1 0 0 0 0 0.00
10.75 0 0 0 0 0 0.00
10.25 0 0 0 0 0 0.00
9.75 0 0 0 0 0 0.00
Ut 0.05 0.05 0.06 0.06 0.06
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 48
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación semicilíndrica: Valores en servicio en lux
Y/X(m) -0.00 0.51 1.01 1.52 2.03 2.54 3.04 3.55 4.06 4.57 5.07 5.58 6.09 6.09 Ul
9.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
8.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
8.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
7.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
7.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
6.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
6.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
5.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
5.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
4.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
4.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
3.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
3.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
2.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
2.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
Ut --- --- --- --- --- --- --- --- --- --- --- --- ---
Y/X(m) 6.60 7.10 7.61 8.12 8.63 9.13 9.64 10.15 10.66 11.16 11.67 12.18 12.69 12.69 Ul
9.25 0 0 0 2 3 5 7 9 11 13 15 17 18 0.00
8.75 0 0 0 3 3 4 6 9 11 13 15 17 18 0.00
8.25 0 0 0 4 4 6 7 9 12 14 16 17 18 0.00
7.75 0 0 0 4 4 8 9 11 12 14 16 17 18 0.00
7.25 0 0 0 4 4 9 10 12 13 15 16 17 17 0.00
6.75 0 0 0 4 4 10 11 13 14 15 16 17 17 0.00
6.25 0 0 0 4 4 11 12 13 14 16 16 17 17 0.00
5.75 0 0 0 4 4 12 13 14 15 15 16 16 16 0.00
5.25 0 0 0 4 4 12 13 14 14 15 15 15 15 0.00
4.75 0 0 0 3 4 12 13 13 14 14 14 14 13 0.00
4.25 0 0 0 3 3 12 12 13 13 13 13 12 12 0.00
3.75 0 0 0 3 3 11 11 12 12 12 11 11 11 0.00
3.25 0 0 0 3 3 10 10 10 11 10 10 10 9 0.00
2.75 0 0 0 2 2 9 9 9 9 9 9 9 8 0.00
2.25 0 0 0 2 2 8 8 8 8 8 8 7 7 0.00
Ut --- --- --- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Y/X(m) 13.19 13.70 14.21 14.71 15.22 15.73 16.24 16.74 17.25 17.76 18.27 18.77 19.28 19.28 Ul
9.25 19 18 17 16 15 14 14 13 12 18 17 16 15 0.00
8.75 18 18 17 16 15 13 14 12 11 16 15 14 14 0.00
8.25 18 18 17 15 14 13 13 11 10 14 14 13 12 0.00
7.75 18 17 16 15 13 12 12 11 9 13 12 11 11 0.00
7.25 17 16 15 14 13 11 11 10 9 12 11 10 9 0.00
6.75 17 16 15 13 12 11 10 9 8 11 10 9 8 0.00
6.25 16 15 14 13 11 10 10 8 7 9 9 8 8 0.00
5.75 15 14 13 12 10 9 9 8 7 9 8 7 7 0.00
5.25 14 13 12 11 9 8 8 7 6 8 7 7 6 0.00
4.75 13 12 11 10 9 8 7 7 6 7 7 6 6 0.00
4.25 11 11 10 9 8 7 7 6 5 6 6 6 5 0.00
3.75 10 9 9 8 7 6 6 5 5 6 5 5 5 0.00
3.25 9 8 8 7 6 6 5 5 5 5 5 5 4 0.00
2.75 8 7 7 6 6 5 5 5 4 5 5 4 4 0.00
2.25 7 6 6 5 5 5 4 4 4 4 4 4 4 0.00
Ut 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.01 0.00 0.00 0.00 0.00
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 49
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación semicilíndrica: Valores en servicio en lux
Y/X(m) 19.79 20.30 20.80 21.31 21.82 22.33 22.83 23.34 23.85 24.36 24.86 25.37 25.88 25.88 Ul
9.25 14 14 13 12 11 10 9 8 8 7 6 7 7 0.00
8.75 13 12 11 11 10 9 8 7 7 6 6 7 6 0.00
8.25 11 11 10 9 9 8 7 7 6 6 5 6 6 0.00
7.75 10 9 9 8 8 7 7 6 6 5 5 6 5 0.00
7.25 9 8 8 7 7 6 6 6 5 5 4 5 5 0.00
6.75 8 7 7 7 6 6 5 5 5 4 4 5 4 0.00
6.25 7 7 6 6 6 5 5 4 4 4 4 4 4 0.00
5.75 6 6 6 5 5 5 4 4 4 4 3 4 4 0.00
5.25 6 5 5 5 5 4 4 4 3 3 3 3 3 0.00
4.75 5 5 5 4 4 4 4 3 3 3 3 3 3 0.00
4.25 5 5 4 4 4 4 3 3 3 3 3 3 3 0.00
3.75 5 4 4 4 4 3 3 3 3 2 2 3 2 0.00
3.25 4 4 4 3 3 3 3 3 2 2 2 2 2 0.00
2.75 4 4 3 3 3 3 3 2 2 2 2 2 2 0.00
2.25 3 3 3 3 3 3 2 2 2 2 2 2 2 0.00
Ut 0.00 0.00 0.02 0.02 0.02 0.02 0.02 0.02 0.03 0.03 0.03 0.02 0.02
Y/X(m) 26.39 26.89 27.40 27.91 28.41 28.92 29.43 29.94 30.44 30.95 31.46 31.97 32.47 32.47 Ul
9.25 6 6 6 5 5 5 5 4 4 4 4 3 3 0.00
8.75 6 5 5 5 5 4 4 4 4 3 3 3 3 0.00
8.25 5 5 5 4 4 4 4 4 3 3 3 3 3 0.00
7.75 5 4 4 4 4 4 3 3 3 3 3 3 2 0.00
7.25 4 4 4 4 3 3 3 3 3 3 2 2 2 0.00
6.75 4 4 3 3 3 3 3 3 2 2 2 2 2 0.00
6.25 4 3 3 3 3 3 3 2 2 2 2 2 2 0.00
5.75 3 3 3 3 3 2 2 2 2 2 2 2 2 0.00
5.25 3 3 3 3 2 2 2 2 2 2 2 2 2 0.00
4.75 3 3 2 2 2 2 2 2 2 2 2 2 1 0.00
4.25 3 2 2 2 2 2 2 2 2 2 1 1 1 0.00
3.75 2 2 2 2 2 2 2 2 1 1 1 1 1 0.00
3.25 2 2 2 2 2 2 2 1 1 1 1 1 1 0.00
2.75 2 2 2 2 2 1 1 1 1 1 1 1 1 0.00
2.25 2 2 2 2 1 1 1 1 1 1 1 1 1 0.00
Ut 0.02 0.02 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.04 0.04 0.04
Y/X(m) 32.98 33.49 34.00 34.50 35.01 35.52 36.03 36.53 37.04 37.55 38.06 38.56 39.07 39.07 Ul
9.25 3 3 3 2 3 3 2 2 2 2 2 2 2 0.00
8.75 3 3 2 2 3 2 2 2 2 2 2 2 1 0.00
8.25 2 2 2 2 2 2 2 2 2 2 2 1 1 0.00
7.75 2 2 2 2 2 2 2 2 2 2 1 1 1 0.00
7.25 2 2 2 2 2 2 2 2 2 1 1 1 1 0.00
6.75 2 2 2 2 2 2 2 2 1 1 1 1 1 0.00
6.25 2 2 2 1 2 2 1 1 1 1 1 1 1 0.00
5.75 2 2 1 1 2 1 1 1 1 1 1 1 1 0.00
5.25 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
4.75 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
4.25 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
3.75 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
3.25 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
2.75 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
2.25 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
Ut 0.04 0.04 0.04 0.04 0.04 0.03 0.03 0.03 0.03 0.03 0.02 0.02 0.02
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 50
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación semicilíndrica: Valores en servicio en lux
Y/X(m) 39.58 40.09 40.59 41.10 41.61 42.11 42.62 43.13 43.64 44.14 44.65 45.16 45.67 45.67 Ul
9.25 2 1 1 1 1 1 1 1 1 1 1 1 1 0.00
8.75 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
8.25 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
7.75 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
7.25 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
6.75 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
6.25 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
5.75 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
5.25 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
4.75 1 1 1 1 1 1 1 1 1 1 1 0 0 0.00
4.25 1 1 1 1 1 1 1 1 1 0 0 0 0 0.00
3.75 1 1 1 1 1 1 1 1 0 0 0 0 0 0.00
3.25 1 1 1 1 1 1 0 0 0 0 0 0 0 0.00
2.75 1 1 1 1 1 0 0 0 0 0 0 0 0 0.00
2.25 1 1 1 1 0 0 0 0 0 0 0 0 0 0.00
Ut 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02
Y/X(m) 46.17 46.68 47.19 47.70 48.20 48.71 49.22 49.73 50.23 50.74 51.25 51.76 52.26 52.26 Ul
9.25 1 1 1 1 1 1 1 1 1 1 0 0 0 0.00
8.75 1 1 1 1 1 1 1 1 1 0 0 0 0 0.00
8.25 1 1 1 1 1 1 1 1 0 0 0 0 0 0.00
7.75 1 1 1 1 1 1 1 0 0 0 0 0 0 0.00
7.25 1 1 1 1 1 1 0 0 0 0 0 0 0 0.00
6.75 1 1 1 1 0 0 0 0 0 0 0 0 0 0.00
6.25 1 1 1 0 0 0 0 0 0 0 0 0 0 0.00
5.75 1 0 0 0 0 0 0 0 0 0 0 0 0 0.00
5.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
4.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
4.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
3.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
3.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
2.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
2.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
Ut 0.02 0.02 0.02 0.03 0.03 0.03 0.03 0.03 0.04 0.04 0.04 0.04 0.05
Y/X(m) 52.77 53.28 53.79 54.29 54.80 54.80 Ul
9.25 0 0 0 0 0 0.00
8.75 0 0 0 0 0 0.00
8.25 0 0 0 0 0 0.00
7.75 0 0 0 0 0 0.00
7.25 0 0 0 0 0 0.00
6.75 0 0 0 0 0 0.00
6.25 0 0 0 0 0 0.00
5.75 0 0 0 0 0 0.00
5.25 0 0 0 0 0 0.00
4.75 0 0 0 0 0 0.00
4.25 0 0 0 0 0 0.00
3.75 0 0 0 0 0 0.00
3.25 0 0 0 0 0 0.00
2.75 0 0 0 0 0 0.00
2.25 0 0 0 0 0 0.00
Ut 0.05 0.05 0.06 0.06 0.06
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 51
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación semicilíndrica: Valores en servicio en lux
Y/X(m) -0.00 0.51 1.01 1.52 2.03 2.54 3.04 3.55 4.06 4.57 5.07 5.58 6.09 6.09 Ul
1.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
1.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
0.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
0.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
Ut --- --- --- --- --- --- --- --- --- --- --- --- ---
Y/X(m) 6.60 7.10 7.61 8.12 8.63 9.13 9.64 10.15 10.66 11.16 11.67 12.18 12.69 12.69 Ul
1.75 0 0 0 2 2 7 7 7 7 7 7 6 6 0.00
1.25 0 0 0 2 2 7 7 6 6 6 6 6 5 0.00
0.75 0 0 0 1 1 6 6 6 5 5 5 5 5 0.00
0.25 0 0 0 1 1 5 5 5 5 5 4 4 4 0.00
Ut --- --- --- 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Y/X(m) 13.19 13.70 14.21 14.71 15.22 15.73 16.24 16.74 17.25 17.76 18.27 18.77 19.28 19.28 Ul
1.75 6 5 5 5 4 4 4 4 3 4 4 3 3 0.00
1.25 5 5 5 4 4 4 4 3 3 4 3 3 3 0.00
0.75 4 4 4 4 4 3 3 3 3 3 3 3 3 0.00
0.25 4 4 4 3 3 3 3 3 3 3 3 3 2 0.00
Ut 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.01 0.00 0.00 0.00 0.00
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 52
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación semicilíndrica: Valores en servicio en lux
Y/X(m) 19.79 20.30 20.80 21.31 21.82 22.33 22.83 23.34 23.85 24.36 24.86 25.37 25.88 25.88 Ul
1.75 3 3 3 3 2 2 2 2 2 2 2 2 2 0.00
1.25 3 3 3 2 2 2 2 2 2 2 2 2 2 0.00
0.75 3 2 2 2 2 2 2 2 2 2 1 2 2 0.00
0.25 2 2 2 2 2 2 2 2 2 1 1 2 1 0.00
Ut 0.00 0.00 0.02 0.02 0.02 0.02 0.02 0.02 0.03 0.03 0.03 0.02 0.02
Y/X(m) 26.39 26.89 27.40 27.91 28.41 28.92 29.43 29.94 30.44 30.95 31.46 31.97 32.47 32.47 Ul
1.75 2 2 2 1 1 1 1 1 1 1 1 1 1 0.00
1.25 2 1 1 1 1 1 1 1 1 1 1 1 1 0.00
0.75 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
0.25 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
Ut 0.02 0.02 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.04 0.04 0.04
Y/X(m) 32.98 33.49 34.00 34.50 35.01 35.52 36.03 36.53 37.04 37.55 38.06 38.56 39.07 39.07 Ul
1.75 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
1.25 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
0.75 1 1 1 1 1 1 1 1 1 1 1 1 1 0.00
0.25 1 1 1 1 1 1 1 1 1 1 1 1 0 0.00
Ut 0.04 0.04 0.04 0.04 0.04 0.03 0.03 0.03 0.03 0.03 0.02 0.02 0.02
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 53
Desarrollo del Proyecto
G / Cálculos
TODOMatriz de iluminación semicilíndrica: Valores en servicio en lux
Y/X(m) 39.58 40.09 40.59 41.10 41.61 42.11 42.62 43.13 43.64 44.14 44.65 45.16 45.67 45.67 Ul
1.75 1 1 0 0 0 0 0 0 0 0 0 0 0 0.00
1.25 1 0 0 0 0 0 0 0 0 0 0 0 0 0.00
0.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
0.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
Ut 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02
Y/X(m) 46.17 46.68 47.19 47.70 48.20 48.71 49.22 49.73 50.23 50.74 51.25 51.76 52.26 52.26 Ul
1.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
1.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
0.75 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
0.25 0 0 0 0 0 0 0 0 0 0 0 0 0 0.00
Ut 0.02 0.02 0.02 0.03 0.03 0.03 0.03 0.03 0.04 0.04 0.04 0.04 0.05
Y/X(m) 52.77 53.28 53.79 54.29 54.80 54.80 Ul
1.75 0 0 0 0 0 0.00
1.25 0 0 0 0 0 0.00
0.75 0 0 0 0 0 0.00
0.25 0 0 0 0 0 0.00
Ut 0.05 0.05 0.06 0.06 0.06
Fecha: 07-06-2012 Nº de Proyecto:
Indalwin 6.2.15.25 página 54
Desarrollo del Proyecto
G / Cálculos
TODO - Isolíneas - Semicilíndrica
Origen zona de estudioPosición: X: -0.00 m Y: 0.00 m Z: 0.00 m
SemicilíndricaMedia: Emed = 5.61 luxMínima: Emin = 0.00 luxMáxima: Emax = 24.40 lux
UniformidadesMedia: Umed = Emin/Emed= 0.00Extrema: Uex = Emin/Emax = 0.00
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
39 V12/007-ALUM
4 PLIEGO DE CONDICIONES
4.1 CONDICIONES DE LOS MATERIALES
La capacidad de los equipos será según se especifica en los documentos del Proyecto. En
caso de discrepancia entre los planos y este Pliego, prevalecerán las indicaciones del Pliego
de condiciones para todos los efectos.
Los equipos y materiales se instalarán de acuerdo con las recomendaciones del fabricante
correspondiente, siempre que no contradigan los de estos documentos.
Todos los materiales y equipos empleados en esta instalación deberán ser de la mayor
calidad y todos los artículos de fabricación estándar normalizada, nuevos y de diseño actual
en el mercado.
El Contratista presentará a requerimiento de la Dirección Técnica si así se le exigiese,
albaranes de entrega de todos o parte de los materiales que constituyen la instalación.
Cualquier accesorio o complemento que no se haya indicado en estos documentos al
especificar el material o equipo pero que no se necesario a juicio de la Dirección Técnica
para el funcionamiento y montaje correcto de la instalación, se considera que será
suministrado y montado por el Contratista sin coste adicional alguno para la propiedad,
interpretándose que su importe se encuentra comprendido proporcionalmente en los precios
unitarios de los demás elementos.
En caso de que así lo solicite la Dirección Técnica, el Contratista deberá presentar catálogos
y/o muestras de los materiales que se indiquen, relacionados con el proyecto. Asimismo,
deberá presentar muestras técnicas de montaje y dibujos de puntos críticos de la
instalación, para determinarlos previamente a la ejecución si así se lo exigiera.
Todos los materiales que se instalen llevaran impreso en lugar la marca y modelo del
fabricado que serán lo especificados en los documentos de este Proyecto o similares
previamente aprobados.
4.1.1 Conductores eléctricos
Los conductores eléctricos serán de cobre electrolítico, con doble capa aislante siendo su
tensión nominal de 1.000 voltios, para la línea repartidora y de 750 voltios para el resto de la
instalación, debiendo estar homologados según las normas UNE.
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
40 V12/007-ALUM
GUIA DE ELECCION DE CABLES A UTILIZAR EN LAS DISTINTAS INSTALACIONES DE BAJA TENSION
1. Redes aéreas para distribución en Baja Tensión ITC-BT-06:
Los conductores serán de cobre, aluminio o de otros materiales o aleaciones que posean
características eléctricas y mecánicas adecuadas y serán preferentemente aislados.
Conductores aislados: Según UNE 21.030, serán de tensión asignada no inferior a 0,6/1 kV,
de sección mínima 16 mm² en aluminio y 10 mm² en cobre.
Los cables habitualmente utilizados responden a la denominación RZ (Cu o Al), cable en
haz, a espiral visible (los llamados “trenzados”) con aislamiento de polietileno reticulado
(XLPE).
Conductores desnudos: Según UNE 21.012 o UNE 21.018 según que sean de cobre o
aluminio.
Se considerarán como conductores desnudos aquellos aislados para una tensión nominal
inferior a 0,6/1 kV.
Su utilización tendrá carácter especial debidamente justificado, excluyendo el caso de zonas
de arbolado o con peligro de incendio.
Los cables habitualmente utilizados responden a la denominación Cu duro, ALı/STıA,
ALı/A2oSA.
2. Redes subterráneas para distribución en Baja Tensión ITC-BT-07:
Los conductores serán de cobre o de aluminio y estarán aislados con mezclas apropiadas
de compuestos poliméricos. Estarán además debidamente protegidos contra la corrosión
que puede provocar el terreno donde se instalen y tendrán la resistencia mecánica suficiente
para soportar los esfuerzos a que puedan estar sometidos.
Podrán ser de uno o más conductores y de tensión asignada no inferior a 0,6/1 kV, y
deberán cumplir las especificaciones de la norma UNE-HD 603.
La sección no será inferior a 6 mm² para cobre, y a 16 mm² para aluminio.
Los cables que habitualmente se utilizan responden a la denominación RV, XZı.
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
41 V12/007-ALUM
3. Instalaciones de alumbrado exterior ITC-BT-09:
Los cables serán multipolares o unipolares con conductores de cobre y tensiones nominales
de 0,6/1 kV.
Redes subterráneas: Según UNE 21.123, de las mismas características a los empleados en
redes subterráneas de distribución reguladas en la ITC-BT-07, y de 6 mm² de sección
mínima.
Los cables que habitualmente se utilizan responden a la denominación VV-K, RV-K
Redes aéreas: De las mismas características a los empleados en redes aéreas aisladas de
distribución descritas en la ITC-BT-06, y de 4 mm² de sección mínima.
Los cables que habitualmente se utilizan responden a la denominación RZ (Cu)
Instalación en soportes: Los conductores serán de cobre, de sección mínima 2,5 mm², y de
tensión asignada de 0,6/1 kV, como mínimo.
Los cables que habitualmente se utilizan responden a la denominación VV-K, RV-K
Instalación en luminarias suspendidas: Los conductores serán flexibles, que penetren en la
luminaria con la holgura suficiente para evitar que las oscilaciones de ésta provoquen
esfuerzos perjudiciales en los cables y en los terminales de conexión, utilizándose
dispositivos que no disminuyan el grado de protección de luminaria IP X3 según UNE
20.324.
Los cables que habitualmente se utilizan responden a la denominación VV-K, RV-K
4. Acometidas ITC-BT-11:
Aérea posada sobre fachada: Los cables serán del tipo aislado 0,6/1 kV y su instalación se
hará preferentemente, bajo conductos cerrados o canales protectoras con tapa desmontable
con la ayuda de un útil.
Aérea tensada sobre postes: Los cables serán del tipo aislado 0,6/1 kV y podrán instalarse
suspendidos de un cable fiador, independiente y debidamente tensado o también mediante
la utilización de un conductor neutro fiador con una adecuada resistencia mecánica, y
debidamente calculado para ésta función.
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
42 V12/007-ALUM
Los cables habitualmente utilizados responden a la denominación RZ (Cu o Al), cable en
haz, a espiral visible (los llamados “trenzados”) con aislamiento de polietileno reticulado
(XLPE).
Subterránea: Este tipo de instalación, se realizará de acuerdo con lo indicado en la ITC-BT-
07. Los cables podrán ser de uno o más conductores y de tensión asignada no inferior a
0,6/1 kV, y deberán cumplir las especificaciones de la norma UNE-HD 603.
La sección no será inferior a 6 mm² para cobre, y a 16 mm² para aluminio.
Para tensión asignada 450/750 V, los denominados H07V-K y ES07V-K (AS)
5. Línea general de alimentación ITC-BT-14:
UNE 21.123-4: RZ1-K (AS): cable de tensión asignada 0,6/1 kV, conductor de cobre de
clase 5 (K-flexible), aislamiento de polietileno reticulado (R) y cubierta de compuesto
termoplástico a base de poliolefina (Z1)
UNE 21.123-5: DZ1-K (AS): cable de tensión asignada 0,6/1 kV, conductor de cobre de
clase 5 (K-flexible), aislamiento de etileno propileno (D) y cubierta de compuesto
termoplástico a base de poliolefina (Z1)
UNE 21.123-4: RZ1-Al (AS): cable con conductor de aluminio, habitualmente se utilizan para
instalaciones singulares.
UNE 21.123-4: Cables de Aluminio RZ1-Al (AS), habitualmente se utilizan para instalaciones
singulares.
6. Derivaciones individuales ITC-BT-15:
Atención: La derivación individual se inicia en el embarrado general y comprende los fusibles
de seguridad, el conjunto de medida y los dispositivos generales de mando y protección.
Montaje superficial o empotrado: UNE 211002: ES07Z1-K (AS): unipolar aislado de tensión
asignada 450/750 V, conductor de cobre de clase 5 (K-flexible), aislamiento de compuesto
termoplástico a base de poliolefina (Z1)
UNE 21.123-4: RZ1-K (AS): cable de tensión asignada 0,6/1 kV, conductor de cobre de
clase 5 (K-flexible), aislamiento de polietileno reticulado (R) y cubierta de compuesto
termoplástico a base de poliolefina (Z1)
UNE 21.123-5: DZ1-K (AS): cable de tensión asignada 0,6/1 kV, conductor de
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
43 V12/007-ALUM
cobre de clase 5 (K-flexible), aislamiento de etileno propileno (D) y cubierta de
compuesto termoplástico a base de poliolefina (Z1)
Montaje enterrado: UNE 21.123-4: RZ1-K (AS): cable de tensión asignada 0,6/1 kV,
conductor de
cobre de clase 5 (K-flexible), aislamiento de polietileno reticulado (R) y cubierta de
compuesto termoplástico a base de poliolefina (Z1)
UNE 21.123-5: DZ1-K (AS): cable de tensión asignada 0,6/1 kV, conductor de cobre de
clase 5 (K-flexible), aislamiento de etileno propileno (D) y cubierta de compuesto
termoplástico a base de poliolefina (Z1)
Montaje en canal de obra, tubo y canal no propagadores de la llama: UNE 211002: ES07Z1-
K (AS): unipolar aislado de tensión asignada 450/750 V, conductor de cobre de clase 5 (K-
flexible), aislamiento de compuesto termoplástico a base de poliolefina (Z1)
UNE 21.123-4: RZ1-K (AS): cable de tensión asignada 0,6/1 kV, conductor de cobre de
clase 5 (K-flexible), aislamiento de polietileno reticulado (R) y cubierta de compuesto
termoplástico a base de poliolefina (Z1)
UNE 21.123-5: DZ1-K (AS): cable de tensión asignada 0,6/1 kV, conductor de cobre de
clase 5 (K-flexible), aislamiento de etileno propileno (D) y cubierta de compuesto
termoplástico a base de poliolefina (Z1)
Montaje en canal de obra, en bandejas y bandejas de escalera: UNE 21.123-4: RZ1-K (AS):
cable de tensión asignada 0,6/1 kV, conductor de cobre de clase 5 (K-flexible), aislamiento
de polietileno reticulado (R) y cubierta de compuesto termoplástico a base de poliolefina (Z1)
UNE 21.123-5: DZ1-K (AS): cable de tensión asignada 0,6/1 kV, conductor de cobre de
clase 5 (K-flexible), aislamiento de etileno propileno (D) y cubierta de compuesto
termoplástico a base de poliolefina (Z1)
UNE 21.123-4: RZ1-Al (AS): cable con conductor de aluminio, habitualmente se utilizan para
instalaciones singulares.
UNE 21.123-4: Cables de Aluminio RZ1-Al (AS), habitualmente se utilizan para instalaciones
singulares.
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
44 V12/007-ALUM
7. Cuadros de contadores ITC-BT-16:
UNE 21 027-9: H07Z-R: unipolar aislado de tensión asignada 450/750 V, conductor de cobre
clase 2 (R-rígido), aislamiento de compuesto termoestable (Z)
UNE 211002: ES07Z1-R (AS): unipolar aislado de tensión asignada 450/750 V, conductor de
cobre de clase 2 (R-rígido), aislamiento de compuesto termoplástico a base de poliolefina
(Z1)
8. Instalaciones interiores en general: ITC-BT-19 y ITC-BT-20:
Serán de cobre o aluminio, siempre aislados, excepto cuando vayan montados sobre
aisladores, tal y como se indica en la ITC-BT 20.
Conductores aislados bajo tubos protectores: Los cables utilizados serán de tensión
asignada no inferior a 450/750 V, y los tubos cumplirán lo establecido en la ITC-BT-21:
UNE-EN 50086-2-1: Tubo rígido: 4321 y no propagador de la llama:
UNE-EN 50086-2-2: Tubo curvable: 2221 y no propagador de la llama:
UNE-EN 50086-2-3: Tubo flexible: 4321 y no propagador de la llama:
Los conductores a utilizar serían:
Para tensión asignada 450/750 V, los denominados H07V-K y ES07V-K (AS)
Para tensión asignada 0,6/1 kV, los denominados RZ1-K (AS) y VV-K
Conductores aislados fijados directamente sobre las paredes:
UNE 21 123-4: RZ1-K (AS): cable de tensión asignada 0,6/1 kV, conductor de
cobre de clase 5 (K-flexible), aislamiento de polietileno reticulado (R) y cubierta de
compuesto termoplástico a base de poliolefina (Z1)
UNE 21.123-5: DZ1-K (AS): cable de tensión asignada 0,6/1 kV, conductor de cobre de
clase 5 (K-flexible), aislamiento de etileno propileno (D) y cubierta de compuesto
termoplástico a base de poliolefina (Z1)
En el RBT no menciona norma UNE de cables sólo la 20.460-5-52, en cuanto a la
realización de la instalación; en cambio la guía técnica sí menciona la UNE 21 123, aunque
no seguida del 4 ó el 5, con lo cual se podría entender que serían los relacionados RZ1-K
(AS) y DZ1-K (AS). También los denominados VV-K y RV-K
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
45 V12/007-ALUM
Conductores aislados enterrados:
Deberán ir bajo tubo salvo que tengan cubierta y una tensión asignada 0,6/1 kV. Las
condiciones se establecerán según lo señalado en las ITC-BT-07 (Redes de distribución
subterráneas) y ITC-BT-21 (Tubos y canales protectoras).
Según guía técnica, cuando los conductores se instalen bajo tubo enterrado, no se instalará
más de un circuito por cada tubo. (UNE-EN 50086-2-4)
Conductores aislados directamente empotrados en estructuras: con cubierta (incluidos
cables armados o con aislamiento mineral) , temperatura entre – 5º y 90ºC, por ejemplo los
de polietileno reticulado o etileno propileno.
Los cables que habitualmente se utilizan responden a la denominación RV-K
Conductores aéreos igual a lo establecido en ITC-BT-06 (pueden ser desnudos sobre
aisladores).
Los cables que habitualmente se utilizan responden a la denominación RZ (Cu, Al)
Conductores aislados en el interior de huecos de la construcción de tensión asignada no
inferior a 450/750 V. Los cables o tubos podrán instalarse directamente en los huecos de la
construcción con la condición de que sean no propagadores de la llama.
Bajo tubo o canal: Los cables que habitualmente se utilizan responden a la denominación
H07V-K y ES07Z1-K (AS)
Directamente en los huecos: Los cables que habitualmente se utilizan responden a la
denominación VV-K, RV-K y RZ1-K (AS)
Según guía técnica: Cuando se instalen directamente cables en huecos de la construcción,
deben tener aislamiento y cubierta y de tensión asignada 0,6/1 kV.
Conductores aislados bajo canales protectoras Siempre que sean de grado IP4X o superior,
se pueden utilizar conductores de tensión asignada 450/750 V. En caso de que sean de
grado inferior a IP 4X, sólo podrá utilizarse conductor aislado bajo cubierta estanca, de
tensión asignada 300/500 V.
Bajo canal con apertura mediante herramienta: Los cables que habitualmente se utilizan
responden a la denominación H07V-K y ES07Z1-K (AS)
Bajo canal con apertura sin herramienta: Los cables que habitualmente se utilizan
responden a la denominación H05VV-F y H05Z1Z1-F
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
46 V12/007-ALUM
Conductores aislados bajo molduras Sólo utilizables en locales o emplazamientos secos,
temporalmente húmedos o polvorientos. Los cables serán de tensión asignada
no inferior a 450/750 V.
Los cables que habitualmente se utilizan responden a la denominación H07V-K y ES07Z1-K
(AS)
Conductores aislados en bandeja o soporte de bandejas Sólo se pueden utilizar cables
aislados con cubierta (incluidos cables armados o con aislamiento mineral), unipolares o
multipolares según norma UNE 20460-5-52.
Según guía técnica, y debido a que las bandejas no efectúan una función de protección, se
recomienda la instalación de cables de tensión asignada 0,6/1 kV.
Los cables que habitualmente se utilizan responden a la denominación VV-K, RV-K y RZ1-K
(AS)
Canalizaciones eléctricas prefabricadas. Deberán tener un grado de protección adecuado a
las características del local por el que discurren.
Para iluminación (por carril) deberán ser conformes con las especificaciones de la norma
UNE EN 60570.
Las de uso general, según norma UNE EN 60439-2
9. Instalaciones interiores en viviendas : ITC-BT-26:
Serán de cobre, aislados y con una tensión asignada de 450/750 V como mínimo.
En cuanto al sistema de instalación, éstas se realizarán mediante:
Instalaciones empotradas (bajo tubo flexible o curvable)
Instalaciones superficiales (bajo tubo curvable, rígido, bajo canal protectora cerrada o
canalización prefabricada)
En ambos casos deberán cumplir lo indicado en las ITC-20 e ITC-21.
Según guía técnica los conductores aislados comúnmente utilizados corresponden a los
tipos especificados en la norma UNE 21.031-3:
H07V-U, unipolar aislado de tensión asignada 450/750 V, con conductor de cobre clase 1 (-
U) y aislamiento de PVC (V).
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
47 V12/007-ALUM
H07V-R, unipolar aislado de tensión asignada 450/750 V, con conductor de cobre clase 2 (-
R) y aislamiento de PVC (V).
H07V-K, unipolar aislado de tensión asignada 450/750 V, con conductor de cobre clase 5 (-
K) y aislamiento de PVC (V).
Clase 1: conductor rígido de un solo alambre (-U)
Clase 2: conductor rígido de varios alambres cableados (-R)
Clase 5: conductor flexible de varios alambres finos, no apto para usos móviles (-K)
Interiores de viviendas en general: Los cables que habitualmente se utilizan responden a la
denominación H07V-U, H07V-R y H07V-K
Interiores de viviendas para locales con bañera o ducha: Los cables que habitualmente se
utilizan responden a la denominación H07V-U, H07V-R y H07VK y H05VV-F
10. Instalaciones en locales de pública concurrencia: ITC-BT-28
Las canalizaciones deben realizarse según ITC-BT 19 e ITC-BT 20 y estarán constituidas
por:
Conductores aislados, de tensión asignada no inferior a 450/750 V, colocados bajo tubos o
canales protectores, preferentemente empotrados en especial en las zonas accesibles al
público.
Conductores aislados, de tensión asignada no inferior a 450/750 V, con cubierta de
protección, colocados en huecos de la construcción totalmente construidos en materiales
incombustibles de resistencia al fuego RF-120, como mínimo.
Conductores rígidos aislados, de tensión asignada no inferior a 0,6/1 kV, armados,
colocados directamente sobre las paredes.
Según guía técnica, adicionalmente, se acepta el uso de bandejas o soporte de bandejas,
según apartado 2.2.9 de la ITC-20, siempre que la canalización se instale a una altura no
inferior a 2,5 m desde el nivel del suelo. Solamente pueden utilizarse cables de tensión
asignada mínima de 0,6/1 kV.
Tipos de cable a utilizar:
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
48 V12/007-ALUM
UNE 211002: ES07Z1-K (AS): unipolar aislado de tensión asignada 450/750 V, conductor de
cobre de clase 5 (K-flexible), aislamiento de compuesto termoplástico a base de poliolefina
(Z1)
UNE 211002: ES05Z1-K (AS): unipolar aislado de tensión asignada 300/500 V, conductor de
cobre de clase 5 (K-flexible), aislamiento de compuesto termoplástico a base de poliolefina
(Z1) (para conexionado interior de los cuadros eléctricos).
UNE 21.123-4: RZ1-K (AS): cable de tensión asignada 0,6/1 kV, conductor de cobre de
clase 5 (K-flexible), aislamiento de polietileno reticulado (R) y cubierta de compuesto
termoplástico a base de poliolefina (Z1)
UNE 21.123-5: DZ1-K (AS): cable de tensión asignada 0,6/1 kV, conductor de cobre de
clase 5 (K-flexible), aislamiento de etileno propileno (D) y cubierta de compuesto
termoplástico a base de poliolefina (Z1)
Los cables destinados a circuitos de servicios de seguridad no autónomos o a circuitos de
servicios con fuentes autónomas centralizadas, deben mantener el servicio durante y
después del incendio, siendo conformes a las especificaciones de la norma UNE-EN 50.200
y tendrán emisión de humos y opacidad reducida. Los cables RZ1-K y DZ1-K cumplen con
éstas prescripciones. Pero además deben cumplir con el apartado 3.4.6 “Ensayos de
reacción al fuego” de la norma UNE 21.123. Los cables que cumplen con éstas propiedades
se distinguen en el mercado por las siglas (AS+).
Locales de pública concurrencia en general bajo tubo: Los cables que habitualmente se
utilizan son los denominados:
Para tensión asignada 450/750 V, los denominados ES07Z1-K (AS)
Para tensión asignada 0,6/1 kV, los denominados RZ1-K (AS)
Conexión interior de cuadros: Los cables que habitualmente se utilizan son los denominados
ES05Z1-K (AS) y ES07Z1-K (AS)
Circuitos de servicios de seguridad: Los cables que habitualmente se utilizan son los
denominados SZ1-K (AS+), (resistentes al fuego)
11. Locales con riesgo de incendio o explosion (ITC-BT-29):
Para instalaciones de seguridad intrínseca, los sistemas de cableado cumplirán los
requisitos de la norma UNE-EN 60079-14 y la UNE-EN 50039.
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
49 V12/007-ALUM
Los cables para el resto de instalaciones tendrán una tensión mínima asignada de 450/750
V.
Instalación fija bajo tubo: Los cables que habitualmente se utilizan son los denominados
ES07Z1-K (AS) y H07V-K (+ no propagador del incendio)
Instalación de cables con protección mecánica: Los cables que habitualmente se utilizan son
los denominados RVMV-K, RVMV (+ no propagador del incendio) y RZ1MZ1-K
Alimentación de equipos portátiles: Los cables que habitualmente se utilizan son los
denominados H07RN-F
12. Locales de características especiales (ITC-BT-30):
Húmedos, mojados, con riesgo de corrosión, polvorientos sin riesgo de incendio o explosión,
a temperatura elevada, a muy baja temperatura, en locales que existen baterías de
acumuladores, afectos a un servicio eléctrico, otros locales de características especiales:
EN EL RBT, SÓLO VIENE REFERENCIA A CABLES EN LOS HÚMEDOS Y MOJADOS.
Locales húmedos:
Instalación de cables aislados en el interior de tubos: Los conductores tendrán una tensión
asignada de 450/750 V y discurrirán por el interior de tubos:
- Empotrados: según se especifica en la ITC-BT-21
- En superficie: según se especifica en la ITC-BT-21, pero tendrán que disponer de un grado
de resistencia a la corrosión 3.
Los cables que habitualmente se utilizan son los denominados H07V-K, H07V-U y H07V-R
Instalación de cables aislados con cubierta en el interior de canales aislantes: Se instalarán
en superficie y las conexiones, empalmes y derivaciones se realizarán en el interior de
cajas.
Los cables que habitualmente se utilizan son los denominados H05VV-F y H05Z1Z1-F
Instalación de cables aislados y armados con alambres galvanizados sin tubo protector: Los
conductores tendrán una tensión asignada de 0,6/1 kV y discurrirán por:
- En el interior de huecos de la construcción
- Fijados en superficie mediante dispositivos hidrófugos y aislantes.
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
50 V12/007-ALUM
Los cables que habitualmente se utilizan son los denominados RVMV-K y RVMV
Locales mojados:
Instalación de cables aislados en el interior de tubos: Los conductores tendrán una tensión
asignada de 450/750 V y discurrirán por el interior de tubos:
- Empotrados: según se especifica en la ITC-BT-21
- En superficie: según se especifica en la ITC-BT-21, pero tendrán que disponer de un grado
de resistencia a la corrosión 4.
Los cables que habitualmente se utilizan son los denominados H07V-K, H07V-U y H07V-R
Instalación de cables aislados con cubierta en el interior de canales aislantes: Los
conductores tendrán una tensión asignada de 450/750 V y discurrirán por el interior de
canales que se instalarán en superficie; las conexiones, empalmes y derivaciones se
realizarán en el interior de cajas.
Los cables que habitualmente se utilizan son los denominados RV-K y H07RN-F
13. Instalaciones con fines especiales. Piscinas y fuentes (ITC-BT-31):
Para elección de los cables, y su instalación en los volúmenes 0, 1 y 2, tendremos en cuenta
las características indicadas en la ITC-BT-30, para los locales mojados.
14. Instalaciones con fines especiales. Máquinas de elevación y transporte (ITCBT-32):
En las instalaciones en el exterior para servicios móviles se utilizarán cables flexibles con
cubierta de policloropeno o similar según UNE 21.027 ó UNE 21.150.
Los cables que habitualmente se utilizan son los denominados H07RN-F
15. Instalaciones provisionales y temporales de obras: ITC-BT-33:
Para acometidas e instalaciones exteriores serán de tensión asignada mínima 450/750 V,
con cubierta de policloropeno o similar, según UNE 21.027. Los cables que habitualmente
se utilizan son los denominados H07RN-F
Para instalaciones interiores, serán de tensión asignada mínima 300/500 V, según UNE
21.027 o UNE 21.031. Los cables que habitualmente se utilizan son los denominados
H05VV-F y H07RN-F
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
51 V12/007-ALUM
16. Instalaciones con fines especiales. Ferias y stands. (ITC-BT-34):
Para instalaciones interiores los cables serán de tensión asignada mínima 300/500 V según
UNE 21.027 ó UNE 21.031 y aptos para servicios móviles. Los cables que habitualmente se
utilizan son los denominados H05VV-F, H05Z1Z1-F y H07RN-F
En instalaciones exteriores los cables serán de tensión asignada mínima 450/750 V con
cubierta de policloropeno o similar, según UNE 21.027 ó UNE 21.150 y aptos para servicios
móviles. Los cables que habitualmente se utilizan son los denominados H07RN-F
Para alumbrados festivos se utilizan cables flexibles de características constructivas según
UNE 21.027 ó UNE 21.031. Los cables que habitualmente se utilizan son los denominados
H03RN-F, H05RN-F, H07RNH2-F y H03VH7-H
17. Instalaciones con fines especiales. Establecimientos agrícolas y hortícolas (ITCBT-35):
Las prescripciones particulares para estos establecimientos quedan recogidos en la norma
UNE 20.460-7-705
18. Instalaciones a muy baja tensión (ITC-BT-36):
Las prescripciones particulares para estos establecimientos quedan recogidos en las
normas UNE correspondientes.
19. Instalaciones a tensiones especiales (ITC-BT-37):
Los cables empleados serán siempre de tensión nominal no inferior a 1.000 V. Cuando
éstos cables se instalen sobre soportes aislantes, deberán poseer una envolvente que los
proteja contra el deterioro mecánico.
20. Instalaciones con fines especiales. Requisitos particulares para quirófanos y salas de intervención (ITC-BT-38):
Las características de aislamiento de los conductores responderán a lo dispuesto en ITC-
BT-19 y, en su caso, la ITC-BT- 29
21. Instalaciones con fines especiales. Cercas eléctricas para ganado (ITC-BT-39):
Las prescripciones particulares para estos establecimientos quedan recogidos en las
normas UNE correspondientes.
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
52 V12/007-ALUM
22. Instalaciones generadoras de baja tensión (ITC-BT-40):
Los cables de conexión deberán estar dimensionados para una intensidad no inferior al
125% de la máxima intensidad del generador y la caída de tensión entre el generador y el
punto de interconexión a la red de distribución pública o a la instalación interior, no será
superior al 1,5%, para la intensidad nominal.
23. Instalaciones eléctricas en caravanas y parques de caravanas (ITC-BT-41):
Las prescripciones particulares para estos establecimientos quedan recogidos en la norma
UNE 20.460-7-708.
Dispositivos de conexión: Los cables que habitualmente se utilizan son los denominados
H07RN-F
Caravanas: Los cables que habitualmente se utilizan son los denominados H07V-K, H07V-R
y H07RN-F
24. Instalaciones eléctricas en puertos y marinas para barcos de recreo (ITC-BT-42):
Las prescripciones particulares para estos establecimientos quedan recogidos en la norma
UNE 21.166 o UNE 21.027-16, según la tensión asignada al cable.
Para contacto con el agua: Los cables que habitualmente se utilizan son los denominados
H07RN8-F
Conexión a los barcos de recreo: Se utilizará un cable flexible tipo H07RN-F, unido de
manera estable al barco de recreo mediante un conector, de acuerdo con las características
indicadas en el apartado 4.3.2 de la ITC.
Instalaciones de receptores. Prescripciones generales (ITC-BT-43): Las prescripciones
particulares para estas instalaciones quedan recogidos en el apartado 2.5 de la ITC. La
tensión asignada de los cables utilizados será como mínimo la tensión de alimentación y
nunca inferior a 300/300 V. Sus secciones no serán inferiores a 0,5 mm2. Las características
del cable a emplear serán coherentes con su utilización prevista.
25. Instalaciones de receptores. Receptores para alumbrado (ITC-BT-44):
La tensión asignada de los cables utilizados será como mínimo la tensión de alimentación y
nunca inferior a 300/300 V. Las características del cable a emplear serán adecuadas a la
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
53 V12/007-ALUM
utilización prevista, siendo capaces de soportar la temperatura a la que puedan estar
sometidas. Distinguiremos los siguientes:
Receptores suspendidos: Se recomienda consultar con un fabricante Cableado interno: Los
cables que habitualmente se utilizan son los 300/300 V, si bien se recomienda consultar con
un fabricante.
Rótulos luminosos: Para rótulos y las instalaciones que los alimenten con tensiones
asignadas de salida en vacío comprendidas entre 1 y 10 kV se aplicará lo dispuesto en la
norma UNE-EN 50.107.
26. Instalaciones de receptores. Aparatos de caldeo (ITC-BT-45):
Las prescripciones particulares para estas instalaciones quedan recogidos en la ITC.
27. Instalaciones de receptores. Motores (ITC-BT-47):
Las prescripciones particulares para estas instalaciones quedan recogidos en la norma UNE
20.460 y las especificaciones aplicables a los locales (o emplazamientos) donde hayan de
ser instaladas. Las secciones mínimas se calcularán atendiendo a lo dispuesto en el
apartado 3 de la ITC.
28. Instalaciones eléctricas en muebles: ITC-BT-49:
Los cables se podrán colocar en tubos, canales protectoras o bien ir conducidos dentro de
un canal realizado durante la construcción del elemento de mobiliario. Las instalaciones de
tubos y canales serán conformes a lo indicado en la ITC-BT 21.
Serán flexibles aislados con goma (equivalente, como mínimo, al tipo H05RR-F), o PVC
(equivalentes como mínimo, al tipo H05VV-F).
Según guía técnica para instalación en canal interior del mueble realizado durante su
construcción se pueden utilizar los cables siguientes:
UNE 21.027-4: Cable tipo H05RR-F: Cable de tensión asignada 300/500 V, con conductor
de cobre clase 5 (-F), con aislamiento (R) y cubierta de etileno propileno(R). (Si es R, sería
polietileno reticulado, por lo que parece que puede ser un error de la guía técnica.)
Temperatura máxima de servicio del conductor 60ºC
UNE 21.031-5: Cable tipo H05VV-F: Cable de tensión asignada 300/500 V, con conductor
de cobre clase 5 (-F), con aislamiento (V) y cubierta de PVC (V).
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
54 V12/007-ALUM
Temperatura máxima de servicio del conductor 70ºC
Para las canalizaciones en tubos o en canales protectoras pueden utilizarse conductores
unipolares aislados (tipo H07V con conductor rígido o flexible).
29. Instalaciones eléctricas en locales que contienen radiadores para saunas (ITC-BT-50):
Las prescripciones particulares para estas instalaciones serán las establecidas en la norma
UNE 20.460-7-703.
4.1.2 Conductores de protección.-
Los conductores de protección serán igualmente de cobre con el mismo aislamiento y
sección que los conductores activos hasta una sección de estos de 16 mm2.
Para conductores activos entre 25 y 35 mm2, los de protección serán de 16 mm2 y la mitad
de la sección que en activos para secciones mayores de 35 mm2.
Irán instalados en el interior del mismo tubo protector que los conductores activos.
4.1.3 Identificación de los conductores.-
Los conductores para corriente alterna se identificarán interiormente por el siguiente código
de colores:
Fase R Marrón
Fase S Gris
Fase T Negro
Neutro Azul ultramar
Tierra Amarillo con rayas transversales verdes
Los conductores para corriente continua se identificarán según:
Positivo Rojo
Negativo Azul ultramar
El color de la funda exterior será:
Media tensión Rojo
Baja tensión Negro
Cables de seguridad intrínseca Azul
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
55 V12/007-ALUM
4.1.4 Tubos protectores.-
Los tubos de protección utilizados para la colocación en su interior de los conductores serán
básicamente de PVC, en versión rígida o flexible, presentando en toda su superficie una
perfecta impermeabilización sin presentar grietas ni roturas debiendo presentar el sistema
de juntas empleado una seguridad contra la entrada de agua en las canalizaciones de
extrema garantía
Los tubos sometidos a la presión de una prensa, deberán sufrir sin romperse y sin acusar
permeabilidad a través de sus paredes una presión de dos atmósferas.
4.1.5 Cajas de empalmes y derivación.-
Para las derivaciones individuales de cada luminaria se emplearan cofres diseñados al
efecto, con un grado de protección IPP 433 según UNE 20.324. Se instalaran en el interior
de cada báculo y contaran con protección por cortacircuitos fusibles de cápsula cilíndrica,
según UNE 21.103. La resistencia de aislamiento entre las partes activas y masa deberá ser
superior a 5 Mohmios, a una tensión de 500 V.
4.1.6 Aparatos de mando y maniobra.-
Deberá cumplir las características especificadas en los esquemas eléctricos adjuntos a este
proyecto. Deberán estar calificados como Material Homologado acompañándose, en caso
necesario, del certificado de ensayo de laboratorio oficial.
4.1.7 Aparatos de mando y maniobra y protección.-
Se engloban aquí los interruptores automáticos magnetotérmicos, interruptores diferenciales
y los cortacircuitos fusibles.
Interruptor diferencial: Para conseguir una protección adecuada contra contactos indirectos,
se instalara este de una sensibilidad de 300 mA. Deberá llevar impreso de forma indeleble,
la marca, tipo, tensión nominal en voltios, intensidad nominal en A. Y sensibilidad en mA.
Interruptor magnetotérmico: La protección de la instalación contra sobrecargas y
cortocircuitos se hará con un interruptor magnetotérmico. Deberá llevar impreso de forma
indeleble, la marca, el tipo, tensión nominal, intensidad y poder de corte.
Fusibles: En el interior de las cajas de derivación se instalaran cortacircuitos fusibles de
calibre adecuado. Se dispondrán sobre material aislante e incombustible y estarán
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
56 V12/007-ALUM
construidos de forma que no se pueda proyectar metal fundido. Se podrán cambiar bajo
tensión sin peligro alguno y llevaran impreso la intensidad y tensión nominal.
4.2 NORMAS DE EJECUCIÓN DE LAS INSTALACIONES.-
4.2.1 Recepción de los materiales
No se emplearán materiales sin que previamente hayan sido examinados en las condiciones
que prescriben las respectivas calidades indicadas para cada material. Este control previo
no constituye su recepción definitiva, pudiendo ser rechazados por la dirección facultativa de
la obra, aún después de colocados, si no cumpliesen las condiciones exigidas en la
normativa aplicable. A tal efecto, la dirección facultativa de la obra empleará los métodos de
ensayo y selección que considere oportunos.
4.2.2 Instalación de enlace
4.2.2.1 Nicho polígono. C.G.P. Fijación
La pared de fijación de la CGP tendrá una resistencia no inferior a la del tabicón del 9.
La CGPM se fijarán sobre el paramento, como mínimo, por cuatro puntos mediante
dispositivos roscados, recibidos en la obra de fábrica.
Puertas
La puerta y el bastidor serán metálicos, protegidos contra la corrosión, ó de materiales
ignífugos que garanticen un grado de protección IP XX9. Se instalará una cerradura ó
candado normalizado por Iberdrola. La hoja podrá revestirse de cualquier tipo de material y
ajustarse a las características del entorno, a elección del cliente.
Las dimensiones de la(s) puerta(s) se ajustarán a las indicadas en la tabla anterior.
Las puertas dispondrán de dos dispositivos de ventilación apropiados (rejillas). Estarán
montadas de tal forma que impida la introducción de objetos.
4.2.2.2 Centro de mando El accionamiento y protección de las unidades luminosas, se realizara desde el centro de
mando de dimensiones adecuadas, cuyo emplazamiento figura en los planos, ubicándose
en el interior del armario de doble aislamiento.
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
57 V12/007-ALUM
La fundación para armarios tendrá como mínimo 20 cm de altura sobre la rasante de la
acera, y si en el armario van contadores, la necesaria para que la lectura de estos quede
como mínimo a 160 cm de la rasante del suelo.
La fundación se montará de modo que una vez instalado sobre ella el armario, este quede
perfectamente aplomado.
En los armarios se prolongarán las fundaciones que sean huecas hasta 60 cm bajo el suelo
para proteger los cables, las mencionadas fundaciones podrán ser de ladrillo o
prefabricadas.
Las fundaciones estarán dotadas de casquillos metálicos apropiados, a los que se
atornillarán los pernos de anclaje del armario, asegurando su sujeción firme en caso de la
instalación de un armario prefabricado.
El armario quedará, una vez instalado, con acceso libre de obstáculos, preferentemente a
línea de fachada.
Los terminales colocados en los conductores para su conexión a los cuadros serán de
características adecuadas a la sección y naturaleza de los cables.
Estarán firmemente sujetos a las cuerdas de los conductores utilizando las técnicas
indicadas por sus fabricantes, tanto para la limpieza del cobre como la ejecución de las
entalladuras o punzamientos necesarios para su sujeción.
Las prensas hidráulicas o tenazas de presión, necesarias para la compresión de los
terminales sobre los conductores serán las recomendadas por los fabricantes de los
terminales y estarán dotadas de las matrices adecuadas al tipo de terminal.
Los terminales estarán sujetos a las palas de las bases portafusibles intercalando entre las
palas de los terminales una arandela plana y una elástica entre la arandela plana y la tuerca
que proporcione una presión de contacto constante aunque varíe la temperatura del
conjunto.
Los tornillos empleados para la sujeción de los terminales tendrán las características
descritas anteriormente; estando convenientemente apretados por un par de apriete igual al
recomendado por el fabricante de los terminales.
Los terminales estarán señalizados con los colores indicados anteriormente. Las cintas de
identificación se colocarán de forma que no oculten las entalladuras de los terminales para
permitir la comprobación de la correcta ejecución de la compresión.
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
58 V12/007-ALUM
Su situación en el cuadro de protección será (mirando el armario de frente) a la izquierda, el
conductor neutro de color azul y a continuación, de izquierda a derecha las fases, blanco,
rojo y marrón.
Los elementos a instalar serán de primera calidad y se montarán sobre bastidores de
perfiles ranurados.
4.2.2.3 Piezas de conexión Los manguitos para la unión de las cuerdas serán exclusivamente los indicados por el
fabricante y su montaje se realizará con las técnicas y herramientas que se indiquen en las
instrucciones y normas del fabricante.
4.2.2.4 Reconstrucción del aislamiento en los empalmes. Las cintas vulcanizables empleadas para la ejecución de los empalmes se seleccionaran de
acuerdo con las instrucciones del fabricante del conductor utilizado, siendo apropiadas para
el tipo de aislamiento de los cables a empalmar.
Las cintas de PVC para recubrimiento y protección de los empalmes o cajas terminales
tendrán la calificación de Material Homologado
4.2.2.5 Rasillas, ladrillos o placas de PVC Los ladrillos o rasillas en la capa protectora serán de material cerámico de medidas
uniformes, no permitiéndose la utilización de piezas rotas. Se podrán utilizar placas de PVC
estando estas calificadas como Material Autorizado.
4.2.2.6 Cinta de atención a la existencia de cable La cinta de señalización a la existencia de conductores tendrá la calificación de Material
Autorizado, debiendo tener las características indicadas en la RU 0205 (Enero 1986).
4.2.2.7 Cimentaciones Las cimentaciones serán de hormigón HM-20/B/20, con pernos embebidos para anclaje y
con comunicación a columna.
La sujeción de la columna a la cimentación se hará mediante placa de base a la que se
unirán los pernos mediante arandela, tuerca y contratuerca.
Las características de las cimentaciones se muestran en la siguiente tabla.
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
59 V12/007-ALUM
Base (mm) Profundidad (mm)
Tronconico de P.R.F.V. 4 metros 600x600 650Tronconico de P.R.F.V. 5 metros 600x600 650Tronconico de P.R.F.V. 6 metros 600x600 700Tronconico de P.R.F.V. 7 metros 800x800 800Tronconico de P.R.F.V. 8 metros 800x800 800Tronconico de P.R.F.V. 9 metros 800x800 950
CimentaciónTipo
4.2.2.8 Zanjas Las zanjas serán de la forma y características indicadas en los planos correspondientes. El
fondo de la zanja se nivelará cuidadosamente retirando las piezas puntiagudas y cortantes
El relleno de las zanjas deberá efectuarse con el material adecuado, que podrá ser las
tierras procedentes de la excavación si sus condiciones de calidad en el momento de
realizarse el relleno son adecuadas, quedando totalmente prohibido el relleno de zanjas con
barro. Si es necesario se rellenarán con tierras secas de aportación.
Se emplearán sistemas y materiales análogos a los de las redes subterráneas de
distribución reguladas en la ITC-BT-07. Los cables se dispondrán en canalización enterrada
bajo tubo, con unas dimensiones variables en función al número de cables a instalar según
planos de detalle.
El tubo irá envuelto por una capa de hormigón HM-20/B/20 de 31 cm de espesor y apoyado
sobre una cama de 5 cm. El resto de la zanja se completará con 19 cm de relleno
seleccionado y se colocará una cinta de señalización, que advierta de la existencia de
cables, una distancia mínima del nivel del suelo de 0,10 m y a 0,25 m por encima del tubo.
En los cruzamientos de calzadas, la canalización, además de entubada, irá hormigonada
con HM-20/B/20 y se instalará como mínimo un tubo de reserva.
No se instalará más de un circuito por tubo. Los tubos serán de doble capa de 110 mm. de
diámetro con resistencia al impacto normal y al a la compresión de 450 N y serán conformes
a lo establecido en la norma UNE-EN 50.086 2-4.
A fin de hacer completamente registrable la instalación, cada uno de los soportes llevará
adosado una arqueta de fábrica de hormigón HM-20/B/20 con paredes de 15 cm de espesor
y suelo de grava, con tapa de fundición de 40x40 cm. Éstas se ubicarán también en cada
uno de los cruces, derivaciones y cambios de dirección.
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
60 V12/007-ALUM
Los empalmes y derivaciones deberán realizarse en cajas de bornes adecuadas, situadas
dentro de los soportes de las luminarias, y a una altura mínima de 0,3 m sobre el nivel del
suelo o en una arqueta registrable, que garanticen, en ambos casos, la continuidad, el
aislamiento y la estanqueidad del conductor.
Además de todo lo descrito, la instalación en todo caso, se ajustará por el vigente
reglamento electrotécnico de baja tensión.
4.2.2.9 Arquetas Las arquetas serán de la forma y dimensiones indicadas en los planos, pudiendo realizarse
en hormigón o en obra de fábrica.
Se realizarán en los cruces de calzada y en los lugares donde sea necesario para realizar
cambios de dirección.
4.2.2.10 Soportes Las luminarias sujetas sobre columnas-soporte que se ajustarán a la normativa vigente (en
el caso de que sean de acero deberán cumplir el RD 2642/85, RD 401/89 y OM de 16/5/89).
Serán de materiales resistentes a las acciones de la intemperie o estarán debidamente
protegidas contra éstas, no debiendo permitir la entrada de agua de lluvia ni la acumulación
del agua de condensación. Los soportes, sus anclajes y cimentaciones, se dimensionarán
de forma que resistan las solicitaciones mecánicas, particularmente teniendo en cuenta la
acción del viento, con un coeficiente de seguridad no inferior a 2,5.
Las columnas irán provistas de registros de acceso para la manipulación de sus elementos
de protección y maniobra, por lo menos a 0,30 m. del suelo, dotados de una puerta o
trampilla con grado de protección IP 44 según UNE 20.324 (EN 60529) e IK10 según UNE-
EN 50.102, que sólo se pueda abrir mediante el empleo de útiles especiales. En su interior
se ubicará una tabla de conexiones de material aislante, provisto de alojamiento para los
fusibles y de fichas para la conexión de los cables.
Se utilizarán soportes de las siguientes características.
- Columnas de poliéster reforzado con fibra de vidreo (P.R.F.V.) con placa base de 60 mm
en punta, de 7 metros de altura.
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
61 V12/007-ALUM
4.2.2.11 Luminarias El modelo de luminaria a utilizar será luminarias Indalux, modelo IQV, VSAP 100 W. Con las
siguientes características:
- Carcasa formada por una cubierta superior en aleación de aluminio L-3071 y un aro
soporte en aleación de aluminio L-2521 resistente a la corrosión, inyectado a alta presión
y pintada en polvo poliéster negro texturado o blanco RAL 9016 brillo. Incorpora junta de
estanqueidad en fieltro de base poliéster, antihumedad y fungicida.Precisa de un
acoplamiento auxiliar para su fijación a columna (simple o doble), o a brazo o pared.
- Bastidor abatible en acero galvanizado, que soporta el reflector y el equipo eléctrico.
- Reflector en aluminio de alta pureza anodizado.
- Bandeja portaequipos en acero galvanizado. Incorpora equipo eléctrico electromagnético
de tipo compacto Indalblock® sin cableado exterior.
- Cierre fijado al aro soporte y con cable de seguridad, mediante tornillos (IQV), de vidrio
plano templado y serigrafiado. Incorpora tornillos de fijación por accionamiento manual,
en acero inoxidable con cabeza de poliamida.
- Prensaestopas en el aro soporte, para entrada de cable de alimentación hasta Ø 12 mm.
Conexión a las bornas del equipo eléctrico.
4.3 PRUEBAS REGLAMENTARIAS.-
Independientemente de la necesaria tramitación administrativa referente a la puesta en
servicio de las instalaciones, las empresas suministradoras de energía eléctrica procederán,
antes de la conexión de sus instalaciones a sus redes de distribución, a verificar las mismas
en relación al aislamiento que presentan con relación a tierra y entre conductores, Así como
respecto a las corrientes de fuga que se produzcan con los receptores de uso simultáneo
conectados a la misma en elemento de realizar las prueba.
Los valores obtenidos no serán inferiores a 250.000 Ohmios por lo que se refiere a la
resistencia de aislamiento.
Las corrientes de fuga, en las condiciones anteriormente indicadas no serán superiores,
para el conjunto de la instalación ó para cada uno de los circuitos en que ésta pueda
dividirse a efectos de su protección, a la sensibilidad que presenta los interruptores
diferenciales instalados como protección contra los contactos indirectos.
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
62 V12/007-ALUM
Cuando los valores obtenidos en la indicada verificación sean inferiores ó superiores a los
señalados respectivamente para el aislamiento y corriente de fuga, las empresas
suministradoras de energía eléctrica no podrán conectar a sus redes las instalaciones
receptoras, debiendo en cada caso poner el hecho en conocimiento de las Consellerias de
Industria ó delegaciones del Ministerio de Industria en el más breve plazo posible.
Dichas pruebas comprenderán la realización de las siguientes operaciones en presencia de
la Dirección Técnica.
• Comprobación de los calibres de todas y cada una de las protecciones existentes
(fusibles, automáticos, etc.).
• Comprobación de la regulación de todos los relés existentes.
• Comprobación individual del buen funcionamiento de todas las luminarias de la
instalación.
• Prueba de la instalación en carga para las potencias demandadas calculadas en cada
cuadro secundario.
• Comprobación en general de que la instalación cumple con todos los apartados de este
Pliego de Condiciones y la Reglamentación vigente.
• Comprobación en general del buen funcionamiento de todos los sistemas, equipos y
aparatos comprendidos en la instalación, en condiciones similares a las de trabajo de
cada uno.
4.4 CONDICIONES DE USO, MANTENIMIENTO Y SEGURIDAD.-
Una vez finalizada la instalación, para cualquier modificación, deberá intervenir un instalador
autorizado o un técnico competente.
Periódicamente se comprobaran los dispositivos de protección contra cortocircuitos,
contactos directos e indirectos, así como sus intensidades nominales en relación con la
sección, con la carga y en definitiva con las posibles variaciones no comunicadas que se
hayan podido efectuar en las instalaciones.
Se comprobaran los dispositivos de protección contra cortocircuitos, así como sus
intensidades nominales en relación con la sección de los conductores que protegen.
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
63 V12/007-ALUM
El personal de oficio del Ayuntamiento o quien el mismo delegue, una vez recibidas las
instalaciones, se hará cargo del mantenimiento y conservación de las instalaciones referidas
en el presente proyecto.
4.5 CERTIFICADOS Y DOCUMENTACIÓN
Previamente a la iniciación de los trabajos de instalación eléctrica a que se refiere el
presente proyecto ó durante el periodo de montaje, la Dirección de Obra podrá solicitar
certificados de homologación de los materiales que intervienen en la instalación eléctrica así
como documentación.
Al término de la ejecución de la instalación, el instalador autorizado realizará las
verificaciones que resulten oportunas, en función de las características de aquélla, según se
especifica en la y en su caso todas las que determine la dirección de obra.
Asimismo, las instalaciones que se especifican en la ITC-BT-05, deberán ser objeto de la
correspondiente Inspección Inicial por Organismo de Control.
Finalizadas las obras y realizadas las verificaciones e inspección Inicial a que se refieren los
puntos anteriores, instalador autorizado deberá emitir un Certificado dé Instalación, según
modelo establecido por la Administración, que deberá comprender, al menos, lo siguiente:
• los datos referentes a las principales características de la instalación;
• la potencia prevista de la instalación;
• la referencia del certificado del Organismo de Control que hubiera realizado con
calificación de resultado favorable, la inspección inicial;
• identificación del instalador autorizado responsable de la Instalación;
• declaración expresa de que la instalación ha sido ejecutada de acuerdo con las
prescripciones del Reglamento Electrotécnico para Baja Tensión y, en su caso, con las
especificaciones particulares aprobadas a la Compañía eléctrica, así como con el
Proyecto.
Antes de la puesta en servicio de las instalaciones, el instalador autorizado deberá presentar
ante el Órgano competente de la Comunidad Autónoma, al objeto de, su inscripción en el
correspondiente registro, el Certificado de Instalación con su correspondiente anexo de
información al usuario, por quintuplicado, al que se acompañará el Proyecto, así como el
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
64 V12/007-ALUM
certificado de Dirección de Obra firmado por el correspondiente técnico titulado competente,
y el certificado de inspección inicial con calificación de resultado favorable, del Organismo
de Control.
El Órgano competente de la Comunidad Autónoma deberá diligenciar las copias del
Certificado de Instalación y, en su caso, del certificado de inspección inicial, devolviendo
cuatro al instalador autorizado, dos para sí y las otras dos para la propiedad, a fin de que
ésta pueda, a su vez, quedarse con una copia y entregar la otra a la Compañía eléctrica,
requisito sin él cual ésta no podrá suministrar energía a la instalación salvo lo indicado en el
Artículo 18.3 del Reglamento Electrotécnico para Baja Tensión.
4.6 LIBRO DE ÓRDENES
Para el seguimiento de las instalaciones y anotar las aclaraciones a los detalles del
proyecto, deberá existir en obra un "LIBRO DE ORDENES" con hojas numeradas
correlativamente en el que se anotarán así mismo las modificaciones al proyecto, si las
hubiera, para conocimiento de la propiedad y del Instalador Autorizado que realice las
instalaciones eléctricas.
Castellón, Julio 2012
Jorge Navarro Robledo Ing. Téc. Industrial Col. 545
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
65 V12/007-ALUM
5 PRESUPUESTO
5.1 MEDICIONES
Código Ud Resumen Comentario N Long Anc Alt Parcial CanPres 1 Alumbrado CE00001 M3. Excavación en zanja en cualquier clase de terreno. 22,10 Excavación en zanja en cualquier clase de terreno incluida la roca compacta, incluso
demolición del pavimento existente, entibación, agotamiento, rasanteo, nivelación y compactación del fondo resultante de la excavación. Incluso ayuda manual en zonas de difícil acceso.
Acera 0,000 1 linea 1 59,000 0,400 0,700 16,520 2 lineas 1 4,000 0,450 0,700 1,260 Calzada 0,000 1 lineas 1 12,000 0,450 0,800 4,320 CE00001 22,10 DES0001 M3. Hormigón HM-20/B/20/I 8,91 Hormigón en masa, tipo HM-20/B/20/I (de resistencia característica 20 N/mm2) de
consistencia blanda, tamaño máximo del árido 20 mm, incluso encofrado y desencofrado, puesto en obra, vibrado y curado.
Acera 0,000 1 linea 1 59,000 0,400 0,300 7,080 2 lineas 1 4,000 0,450 0,300 0,540 Calzada 0,000 1 lineas 1 12,000 0,450 0,400 2,160 A deducir
conducciones -
0,0187,000 -0,870
DES0001 8,91 CE00003 M3. Relleno de zanja con seleccionados de exca/obra. 12,32 Relleno de zanja con productos seleccionados no plásticos y de tamaño max. 50 mm.
procedentes de la excavación o de préstamos, compactados al 95% del P. M.
Acera 0,000 1 linea 1 59,000 0,400 0,400 9,440 2 lineas 1 4,000 0,450 0,400 0,720 Calzada 0,000 1 lineas 1 12,000 0,450 0,400 2,160 CE00003 12,32 DMT0005 M3. Carga y Transporte 9,78 Carga y transporte a vertedero autorizado del material sobrante de la excavación. Excavación 1 22,100 22,100 A deducir
relleno -1 12,320 -12,320
DMT0005 9,78 AL0002 ml Cable Cu tipo RV 0,6/1Kv. de 1x6 mm² 316,00 Cable tipo RV 0,6/1Kv. de 1x6 mm² de sección, de conductor de Cu, para linea de
alumbrado subterránea, incluso conexiones, instalado y probado.
4 63,000 252,000 4 16,000 64,000 AL0002 316,00 PNU_AL001 ml Cable Cu tipo RV 450/750v de 1x16 mm² para tierra. 79,00 Cable tipo RV 450/750 v. de 1x16 mm² de sección, con recubrimiento de color verde-
amarillo, de conductor de Cu, para linea de toma de tierra, incluso conexiones, instalado y probado.
1 63,000 63,000 1 16,000 16,000 PNU_AL001 79,00
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
66 V12/007-ALUM
Código Ud Resumen Comentario N Long Anc Alt Parcial CanPres AL0001 ml Cable Cu tipo RV 0,6/1Kv. de 1x2.5 mm² 158,00 Cable tipo RV 0,6/1Kv. de 1x2,5 mm² de sección, de conductor de Cu, para linea de
alumbrado subterránea, incluso conexiones, instalado y probado.
2 63,000 126,000 2 16,000 32,000 PNU_AL001 158,00 LE0103 ml Conducto de PVCØ110 corrugado 91,00 Conducto de PVCØ110 corrugado exteriormente, liso interiormente, para paso de cableado,
incluso paso de ataguía.
Acera 0,000 1 linea 1 59,000 59,000 2 lineas 2 4,000 8,000 Calzada 0,000 1 lineas 2 12,000 24,000 LE0103 91,00 AL0155 ud Cimentación punto de luz h=7m 7,00 Cimentación de punto de luz de 7 m de altura, de hormigón en masa HM-20/B/20 de
dimensiones 80x80x80 cm, incluso pernos de anclaje de 24 mm, placas, codo de acometida, excavación en cualquier clase de terreno, carga y transporte de escombros a vertedero. Totalmente realizada.
7 7,000 AL0155 7,00 AQ0033 ud Arqueta de 0.4 x 0.4 para red alumbrado 10,00 Arqueta de 0,40x0,40 m. para red de alumbrado, con paredes de 15 cms de espesor de
HM-20/B/20, encofrado a dos caras y suelo de grava. Incluso marco y tapa metálica con identificación del servicio, de 0,40x0,40 m., incluso conexión a conducciones.
Arqueta cruce 2 2,000 Puntos de luz 7 7,000 1 1,000 AQ0033 10,00 TT0002 ud Sistema de puesta a tierra c/pica 2m y conexiones 8,00 Sistema de puesta a tierra formado por pica de acero cobreada de 2 m y 14 mm de
diámetro y conexiones a conductor de unión de picas de tierra.
Puntos de luz 7 7,000 1 1,000 TT0002 8,00 DE0012 Ml. Cinta señalizadora de PVC para instalación eléctrica 75,00 Cinta señalizadora de PVC para instalación eléctrica subterránea, totalmente colocado. Acera 0,000 1 linea 1 59,000 59,000 2 lineas 1 4,000 4,000 Calzada 0,000 1 lineas 1 12,000 12,000 DE0012 75,00 PNU_AL008 ud Punto de luz IQV, VSAP 100W y 7m 5,00 Punto de luz formado por luminaria modelo IQV (Indalux), con Reductor de Flujo,
portalámparas E40 para lámpara tubular de V.S.A.P. de 100 W, dispositivo de sujeción vertical u horizontal, sujeta a columna de fibra, marca Adhorna, de 7 m de altura con placa base y Ø60mm en punta, incluso caja de conexiones, lámpara y cableado hasta luminaria. Completamente instalado, probado y en funcionamiento.
5 5,000 PNU_AL008 5,00 PNU_AL012 ud Punto de luz IQV, VSAP 100W y 7m (doble) 2,00 Punto de luz formado por dos luminarias modelo IQV (Indalux), con Reductor de Flujo,
portalámparas E40 para lámpara tubular de V.S.A.P. de 100 W, dispositivo de sujeción vertical u horizontal, sujeta a columna de fibra, marca Adhorna, de 7 m de altura con placa base y Ø60mm en punta, incluso caja de conexiones, lámpara y cableado hasta luminaria. Completamente instalado, probado y en funcionamiento.
2 2,000 PNU_AL012 2,00
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
67 V12/007-ALUM
Código Ud Resumen Comentario N Long Anc Alt Parcial CanPres PNU_AL007 ud Punto de luz Viento, VSAP 100W y 7m 1,00 Punto de luz formado por luminaria modelo Viento (Indalux), con Reductor de Flujo,
portalámparas E40 para lámpara tubular de V.S.A.P. de 100 W, dispositivo de sujeción vertical u horizontal, sujeta a columna de fibra, marca Adhorna, de 7 m de altura con placa base y Ø60mm en punta, incluso caja de conexiones, lámpara y cableado hasta luminaria. Completamente instalado, probado y en funcionamiento.
Punto de luz existente
1 1,000
PNU_AL007 1,00 PNU_AL024 ud Cuadro eléctrico para red de alumbrado 1,00 Cuadro eléctrico para red de alumbrado proyectada, con mecanismos y aparallaje de
protección y maniobra, seccionadores, relés, U.C.S., reductor de flujo, trabajos eléctricos, conexiones y pruebas.
Cuadro 1 1,000 PNU_AL024 1,00PA_01 Pa. Legalización 1,00 A justificar en pagos en la legalización ante los SS.TT. de Industria y Energia de Castellón,
incluso tasas administrativas y inspección inicial por organismo de control.
1 1,000 PA_01 1,00 2 Seguridad y Salud 1 C2SS Ud. Seguridad y salud 1,00 Unidades de Seguridad y
Salud contempladas en las obras.
1 1,000 C2SS 1,00 2 1 3 Control de calidad 1 C2CC Ud. Control de Calidad 1,00 Unidades de Control de
Calidad contempladas en las obras.
1 1,000 C2CC 1,00 3 1 4 Estudio gestión de residuos 1 V1401 u Gestión de residuos 1,00 Según Estudio de Gestión de
Residuos
1 1,000 V1401 1,00 4 1
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
69 V12/007-ALUM
5.2 PRESUPUESTO
Código Ud Resumen CanPres PrPres ImpPres 1 Alumbrado 1 14.465,96 14.465,96 CE00001 M3. Excavación en zanja en cualquier clase de
terreno. 22,10 8,08 178,57
Excavación en zanja en cualquier clase de terreno incluida la roca compacta, incluso demolición del pavimento existente, entibación, agotamiento, rasanteo, nivelación y compactación del fondo resultante de la excavación. Incluso ayuda manual en zonas de difícil acceso.
DES0001 M3. Hormigón HM-20/B/20/I 8,91 44,97 400,68 Hormigón en masa, tipo HM-20/B/20/I (de
resistencia característica 20 N/mm2) de consistencia blanda, tamaño máximo del árido 20 mm, incluso encofrado y desencofrado, puesto en obra, vibrado y curado.
CE00003 M3. Relleno de zanja con seleccionados de exca/obra.
12,32 3,85 47,43
Relleno de zanja con productos seleccionados no plásticos y de tamaño max. 50 mm. procedentes de la excavación o de préstamos, compactados al 95% del P. M.
DMT0005 M3. Carga y Transporte 9,78 0,53 5,18 Carga y transporte a vertedero autorizado del
material sobrante de la excavación.
AL0002 ml Cable Cu tipo RV 0,6/1Kv. de 1x6 mm² 316,00 0,63 199,08 Cable tipo RV 0,6/1Kv. de 1x6 mm² de sección,
de conductor de Cu, para linea de alumbrado subterránea, incluso conexiones, instalado y probado.
PNU_AL001 ml Cable Cu tipo RV 450/750v de 1x16 mm² para tierra.
79,00 1,71 135,09
Cable tipo RV 450/750 v. de 1x16 mm² de sección, con recubrimiento de color verde-amarillo, de conductor de Cu, para linea de toma de tierra, incluso conexiones, instalado y probado.
AL0002 ml Cable Cu tipo RV 0,6/1Kv. de 1x2.5 mm² 158,00 0,52 82,16 Cable tipo RV 0,6/1Kv. de 1x2,5 mm² de sección,
de conductor de Cu, para linea de alumbrado subterránea, incluso conexiones, instalado y probado.
LE0103 ml Conducto de PVCØ110 corrugado 91,00 2,75 250,25 Conducto de PVCØ110 corrugado exteriormente,
liso interiormente, para paso de cableado, incluso paso de ataguía.
AL0155 ud Cimentación punto de luz h=7m 7,00 41,33 289,31 Cimentación de punto de luz de 7 m de altura, de
hormigón en masa HM-20/B/20 de dimensiones 80x80x80 cm, incluso pernos de anclaje de 24 mm, placas, codo de acometida, excavación en cualquier clase de terreno, carga y transporte de escombros a vertedero. Totalmente realizada.
AQ0033 ud Arqueta de 0.4 x 0.4 para red alumbrado 10,00 52,01 520,10 Arqueta de 0,40x0,40 m. para red de alumbrado,
con paredes de 15 cms de espesor de HM-20/B/20, encofrado a dos caras y suelo de grava. Incluso marco y tapa metálica con identificación del servicio, de 0,40x0,40 m., incluso conexión a conducciones.
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
70 V12/007-ALUM
Código Ud Resumen CanPres PrPres ImpPres TT0002 ud Sistema de puesta a tierra c/pica 2m y
conexiones 8,00 65,41 523,28
Sistema de puesta a tierra formado por pica de acero cobreada de 2 m y 14 mm de diámetro y conexiones a conductor de unión de picas de tierra.
DE0012 Ml. Cinta señalizadora de PVC para instalación eléctrica
75,00 0,22 16,50
Cinta señalizadora de PVC para instalación eléctrica subterránea, totalmente colocado.
PNU_AL008 ud Punto de luz IQV, VSAP 100W y 7m 5,00 818,26 4.091,30 Punto de luz formado por luminaria modelo IQV
(Indalux), con Reductor de Flujo, portalámparas E40 para lámpara tubular de V.S.A.P. de 100 W, dispositivo de sujeción vertical u horizontal, sujeta a columna de fibra, marca Adhorna, de 7 m de altura con placa base y Ø60mm en punta, incluso caja de conexiones, lámpara y cableado hasta luminaria. Completamente instalado, probado y en funcionamiento.
PNU_AL012 ud Punto de luz IQV, VSAP 100W y 7m (doble) 2,00 1.159,73 2.319,46 Punto de luz formado por dos luminarias modelo
IQV (Indalux), con Reductor de Flujo, portalámparas E40 para lámpara tubular de V.S.A.P. de 100 W, dispositivo de sujeción vertical u horizontal, sujeta a columna de fibra, marca Adhorna, de 7 m de altura con placa base y Ø60mm en punta, incluso caja de conexiones, lámpara y cableado hasta luminaria. Completamente instalado, probado y en funcionamiento.
PNU_AL007 ud Punto de luz Viento, VSAP 100W y 7m 1,00 853,26 853,26 Punto de luz formado por luminaria modelo
Viento (Indalux), con Reductor de Flujo, portalámparas E40 para lámpara tubular de V.S.A.P. de 100 W, dispositivo de sujeción vertical u horizontal, sujeta a columna de fibra, marca Adhorna, de 7 m de altura con placa base y Ø60mm en punta, incluso caja de conexiones, lámpara y cableado hasta luminaria. Completamente instalado, probado y en funcionamiento.
PNU_AL024 ud Cuadro eléctrico para red de alumbrado 1,00 4.204,31 4.204,31 Cuadro eléctrico para red de alumbrado
proyectada, con mecanismos y aparallaje de protección y maniobra, seccionadores, relés, U.C.S., reductor de flujo, trabajos eléctricos, conexiones y pruebas.
PA_01 Pa Legalización 1,00 350,00 350,00 A justificar en pagos en la legalización ante los
SS.TT. de Industria y Energia de Castellón, incluso tasas administrativas y inspección inicial por organismo de control.
TOTAL 1 14.465,96 14.465,96 2 Seguridad y Salud 1 222,10 222,10 C2SS Ud. Seguridad y salud 1,00 222,10 222,10 Unidades de Seguridad y Salud contempladas en
las obras.
2 1 222,10 222,10
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
71 V12/007-ALUM
Código Ud Resumen CanPres PrPres ImpPres 3 Control de calidad 1 59,23 59,23 C2CC Ud. Control de Calidad 1,00 59,23 59,23 Unidades de Control de Calidad contempladas
en las obras.
3 1 59,23 59,23 4 Estudio gestión de residuos 1 59,23 59,23 V1401 u Gestión de residuos 1,00 59,23 59,23 Según Estudio de Gestión de Residuos 4 1 59,23 59,23 V12-007 1 14.806,52 14.806,52
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
73 V12/007-ALUM
5.3 RESUMEN DEL PRESUPUESTO
Código Resumen ImpPresC01 LSMT 14.465,96C02 Seguridad y Salud 222,10C03 Control de calidad 59,23C04 Estudio gestión de residuos 59,23 TOTAL EJECUCIÓN MATERIAL 14.806,52
13 % Gastos generales 1.924,85 6 % Beneficio industrial 888,39
TOTAL PRESUPUESTO BASE DE LICITACIÓN (I.V.A. EXCLUIDO) 17.619,76 18 % I.V.A. 3.171,56
TOTAL PRESUPUESTO BASE DE LICITACIÓN (I.V.A. INCLUIDO) 20.791,32
Castellón, Julio 2012
Jorge Navarro Robledo Ing. Téc. Industrial Col. 545
PROYECTO INSTALACION ELECTRICA DE BAJA TENSION
PARA TANATORIO EN BENICASIM BENICASIM (CASTELLÓN)
75 V12/007-ALUM
6 PLANOS
• PLANO 1 SITUACION
• PLANO 2 PLANTA GENERAL.
• PLANO 3 ESQUEMA UNIFILAR. DETALLES