Reservorio Apoyado de 35 m3

4
HOJA DE CÁLCULO RESERVORIO CIRCULAR DE 35M3 RESUMEN DE DISEÑO RESERVORIO CILINDRICO VOL.= 35.00 ALTURA NETA TANQUE(AGUA UTIL) = 2.250 m. ESP. LOSA DE TECHO = 0.150 ALTURA TOTAL SIN LOSA TECHO = 2.650 m. ESP. LOSA DE FONDO = 0.250 ALTURA TOTAL RESERVORIO = 2.800 m. CIMIENTO ANCHO = 0.400 DIAMETRO INTERIOR = 4.500 m. CIMIENTO ALTURA = 0.600 ESPESOR DE PARED TANQUE = 0.200 m. VOLADIZO DE PROTECCION = 0.200 AREA DE ACERO HORIZ.EN PARED Fe 1/2 01 @.05 + 7 @ 0.25 +REST @ 0.30 AREA DE ACERO VERT.EN PARED Fe 1/2 SE UTILIZARA 1 Fe @ 0.35 m. 0.25 por As = TECHO DEL TANQUE Fe 1/2 SE UTILIZARA 1 Fe @ 0.30 AMBOS SENTIDOS As = EN CIMIENTO DEL TANQUE 1/2 SE UTILIZARA 1 Fe @ 0.19 m. Ast CIMIENTO(Contracción y Temp.) = 1/2 SE UTILIZARA 1 Fe @ 0.35 m. As = LOSA DE FONDO 1/2 SE UTILIZARA 1 Fe @ 0.28 AMBOS SENTIDOS DISEÑO DE RESERVORIO CILINDRICO V = 35.00 M3. LOS ELEMENTOS ESTRUCTURALES QUE CONFORMAN EL RESERVORIO SON: - PARED LATERAL DEL TANQUE - TECHO DEL TANQUE - LOSA DE FONDO Y CIMIENTOS ( SOLADOS) - CERCO PERIMETRICO DE PROTECCION. A) DIMENSIONES DEL TANQUE.- CAPACIDAD DEL TANQUE = V = 35.00 M3. RELACION DIAMETRO ALTURA = D real= 4.47 DIAMETRO DEL TANQUE = D redondeado = 4.50 M. ALTURA NETA DEL TANQUE (AGUA UTIL)= H = 2.25 M. COMPROBACION CAPACIDAD = Vn = PI/4*D^2*H 35.78 M3. BORDE LIBRE O CAM. DE AIRE MAS ALTURA LOSA DE FONDO A LA SALIDA DE AGUA = 0.40 M. LAS DIMENSIONES FINALES DEL TANQUE SERAN : DIAMETRO INTERIOR = Di = 4.50 M. ALTURA TOTAL ( SIN LOSA TECHO) = Ht = 2.65 M. B) DISEÑO DE LA PARED DEL TANQUE.- DIVIDIMOS LA ALTURA DEL TANQUE EN DOS PARTES : EL EMPUJE MAXIMO DEL AGUA = P = .5*W*H^2 LA FUERZA DE TENSION PARA CADA ANILLO (INF)= T = 11,390.63 KG. LA FUERZA DE TENSION PARA CADA ANILLO(SUP) = T = 2,847.66 KG. EMPLEANDO UN ESFUERZO DE TRACCION DEL CTO. = 210 Kg/cm2. f't = 13.82 Kg/cm2. EL ESPESOR DEL TANQUE SERA = e = T/(H/2*fct) 7.32 CM. CONSIDERAMOS UN ESPESOR DE = e = 20.00 CM. C) CALCULO DE LA ARMADURA (As=).- ESFUERZO DE TRABAJO DEL ACERO = fs = 0.45 * fy fs = 1,890.00 KG/CM2. AREA DE ACERO ANILLO INFERIOR = Asi = 6.03 CM2. ESPACIAMIENTO DE ACERO = DIAM. 1/2 1.27 23.71 CM. CHEQUEO DE ESPACIAMIENTO MAXIMO = 30.00 CM. ACERO ANILLO INFERIOR: Asi = 01 FIERRO DE 1/2 @ 23.71 CM. AREA DE ACERO ANILLO SUPERIOR = Ass = 1.51 CM2. ESPACIAMIENTO DE ACERO = DIAMETRO = 1/2 1.27 94.83 CM. CHEQUEO DE ESPACIAMIENTO MAXIMO = 30.00 CM. POR LO TANTO ACERO ANILLO SUPERIOR: Ass = 01 Fe. DE 1/2 @ 30.00 CM. REFUERZO VERTICAL.- CUANTIA DE DISEÑO = DE fy = 4200 KG/CM2. 0.0018 AREA DE ACERO VERTICAL = Asv = 3.60 CM2. USANDO FIERRO DE= 1/2 1.27 Asv = 1 @ 35 CM. * TANTO EL REFUERZO HORIZONTAL COMO EL VERTICAL SE CONTINUARAN HASTA EL EXTREMO SUPERIOR DEL TANQUE. D) CHEQUEO DEL ESPESOR ( e=).- RESISTENCIA DEL CONCRETO f'c = f'c = 210 KG/CM2. POR SER ELEMENTO SOMETIDO A TRACCION AXIAL: SUPERFICIE DE CONCRETO = Ac = 486.96 CM2. ESPESOR DE LA PARED DEL TANQUE = e = 20.00 CM.

Transcript of Reservorio Apoyado de 35 m3

Page 1: Reservorio Apoyado de 35 m3

HOJA DE CÁLCULORESERVORIO CIRCULAR DE 35M3

RESUMEN DE DISEÑO RESERVORIO CILINDRICO VOL.= 35.00 M3.ALTURA NETA TANQUE(AGUA UTIL) = 2.250 m. ESP. LOSA DE TECHO = 0.150 m.

ALTURA TOTAL SIN LOSA TECHO = 2.650 m. ESP. LOSA DE FONDO = 0.250 m.

ALTURA TOTAL RESERVORIO = 2.800 m. CIMIENTO ANCHO = 0.400 m.

DIAMETRO INTERIOR = 4.500 m. CIMIENTO ALTURA = 0.600 m.

ESPESOR DE PARED TANQUE = 0.200 m. VOLADIZO DE PROTECCION = 0.200 cm

AREA DE ACERO HORIZ.EN PARED Fe 1/2 01 @.05 + 7 @ 0.25 +REST @ 0.30 m.

AREA DE ACERO VERT.EN PARED Fe 1/2 SE UTILIZARA 1 Fe @ 0.35 m. 0.25 por seguridadAs = TECHO DEL TANQUE Fe 1/2 SE UTILIZARA 1 Fe @ 0.30 AMBOS SENTIDOSAs = EN CIMIENTO DEL TANQUE 1/2 SE UTILIZARA 1 Fe @ 0.19 m.Ast CIMIENTO(Contracción y Temp.) = 1/2 SE UTILIZARA 1 Fe @ 0.35 m.As = LOSA DE FONDO 1/2 SE UTILIZARA 1 Fe @ 0.28 AMBOS SENTIDOS

DISEÑO DE RESERVORIO CILINDRICO V = 35.00 M3.LOS ELEMENTOS ESTRUCTURALES QUE CONFORMAN EL RESERVORIO SON:

- PARED LATERAL DEL TANQUE

- TECHO DEL TANQUE

- LOSA DE FONDO Y CIMIENTOS ( SOLADOS)

- CERCO PERIMETRICO DE PROTECCION.

A) DIMENSIONES DEL TANQUE.-CAPACIDAD DEL TANQUE = V = 35.00 M3.

RELACION DIAMETRO ALTURA = D real= 4.47

DIAMETRO DEL TANQUE = D redondeado = 4.50 M.

ALTURA NETA DEL TANQUE (AGUA UTIL)= H = 2.25 M.

COMPROBACION CAPACIDAD = Vn = PI/4*D^2*H 35.78 M3.

BORDE LIBRE O CAM. DE AIRE MAS ALTURA LOSA DE FONDO A LA SALIDA DE AGUA = 0.40 M. dato

LAS DIMENSIONES FINALES DEL TANQUE SERAN :

DIAMETRO INTERIOR = Di = 4.50 M.

ALTURA TOTAL ( SIN LOSA TECHO) = Ht = 2.65 M.

B) DISEÑO DE LA PARED DEL TANQUE.-DIVIDIMOS LA ALTURA DEL TANQUE EN DOS PARTES :

EL EMPUJE MAXIMO DEL AGUA = P = .5*W*H^2

LA FUERZA DE TENSION PARA CADA ANILLO (INF)= T = 11,390.63 KG.

LA FUERZA DE TENSION PARA CADA ANILLO(SUP) = T = 2,847.66 KG.

EMPLEANDO UN ESFUERZO DE TRACCION DEL CTO. = 210 Kg/cm2. f't = 13.82 Kg/cm2. dato

EL ESPESOR DEL TANQUE SERA = e = T/(H/2*fct) 7.32 CM.

CONSIDERAMOS UN ESPESOR DE = e = 20.00 CM. dato

C) CALCULO DE LA ARMADURA (As=).-ESFUERZO DE TRABAJO DEL ACERO = fs = 0.45 * fy fs = 1,890.00 KG/CM2.

AREA DE ACERO ANILLO INFERIOR = Asi = 6.03 CM2.

ESPACIAMIENTO DE ACERO = DIAM. 1/2 1.27 23.71 CM. dato

CHEQUEO DE ESPACIAMIENTO MAXIMO = 30.00 CM.

ACERO ANILLO INFERIOR: Asi = 01 FIERRO DE 1/2 @ 23.71 CM.

AREA DE ACERO ANILLO SUPERIOR = Ass = 1.51 CM2.

ESPACIAMIENTO DE ACERO = DIAMETRO = 1/2 1.27 94.83 CM.

CHEQUEO DE ESPACIAMIENTO MAXIMO = 30.00 CM.

POR LO TANTO ACERO ANILLO SUPERIOR: Ass = 01 Fe. DE 1/2 @ 30.00 CM.

REFUERZO VERTICAL.-

CUANTIA DE DISEÑO = DE fy = 4200 KG/CM2. 0.0018

AREA DE ACERO VERTICAL = Asv = 3.60 CM2.

USANDO FIERRO DE= 1/2 1.27 Asv = 1 @ 35 CM. dato

* TANTO EL REFUERZO HORIZONTAL COMO EL VERTICAL SE CONTINUARAN HASTA EL EXTREMO SUPERIOR

DEL TANQUE.

D) CHEQUEO DEL ESPESOR ( e=).-RESISTENCIA DEL CONCRETO f'c = f'c = 210 KG/CM2.

POR SER ELEMENTO SOMETIDO A TRACCION AXIAL:

SUPERFICIE DE CONCRETO = Ac = 486.96 CM2.

ESPESOR DE LA PARED DEL TANQUE = e = 20.00 CM.

G25
pronasar: Redondear
Page 2: Reservorio Apoyado de 35 m3

E) DISEÑO DEL TECHO DEL TANQUELOSA MACIZA ARMADA EN DOS SENTIDOS; TENDRÁ UN VOLADIZO DE PROTECCION DE LA PARED =: 20.00 CM.

PREDIMENSIONAMIENTO (h);

NO DEBE SER INFERIOR A: h1 = 11.03 CM.

NO DEBE SER INFERIOR A: h2 = 12.05 CM.

PERO EN NINGUN CASO SUPERIOR A: h3 = 13.73 CM.

ENTONCES EL ESPESOR SERA = h = 12.89 CM.

REDONDEANDO EL ESPESOR MAS FAVORABLE : h = 15.00 CM. dato

METRADO DE CARGAS(U).-

CARGA MUERTA =CM = CM = PP + PT = 460.00 KG/M2.

CARGA VIVA = CV = CV = 200.00 KG/M2. dato

CARGA ULTIMA : U = U = 984.00 KG/M2

MOMENTO ACTUANTE +M = +M = 830.25 KG-M.

CHEQUEO DEL ESPESOR e = POR DEFLEXION I = 28,125 Ùmáx = 0.86 CM.

DEFLEXION MAXIMA PERMISIBLE = Ùmáxad = 2.50 CM.

DE DONDE Ùmáx < Ùmáxad =====> OK

CALCULO DEL CORTANTE = V = 2,546.10 KG.

CANTO EFECTIVO 01 = CUNT.MAX= 0.0159375 d1 = 4.12 CM.

CANTO EFECTIVO 02 = RECUB d' = 4.50 d2 = 10.50 CM.

CALCULO DEL CANTO EFECTIVO = d = 10.50 CM.

CHEQUEO POR CORTE.-

CORTANTE ACTUANTE NOMINAL = Vu = 2,427.28 vu = 2.72 KG/CM2.

CORTANTE CRITICO ( vc ) = vc = 7.68 KG/CM2.

CONSIDERANDO QUE vc > u ---------> OK

CALCULO DEL AREA DE ACERO (As =) fy = 4,200

CALCULO DE a EL MAS REAL = 0.50 a = 0.50 CM.

CALCULO DE AREA DE ACERO = 2.14 0.50 0.50 As1 = 2.14 CM2.

CHEQUEO DE AREA DE ACERO MINIMO EN TRACCION = Asm = 3.50 CM2.

AREA DE ACERO EN AMBOS SENTIDOS = As = 3.50 CM2.

USANDO FIERRO DE : 1/2 1.27 36 Y Smáx = 30 CM. dato

ENTONCES SE UTILIZARA 1 Fe. 1/2 30 CM. EN AMBOS SENTIDOS

F) DISEÑO DEL CIMIENTO CORRIDO DE LA PARED DEL TANQUE :TENDRA FORMA DE ANILLO CONCENTRICO EN LA BASE DEL TANQUE, UNA VEREDA DE PROTECCIÓN DE = 0.60 M. dato

METRADO DE CARGAS.-

CARGA MUERTA = 6.10 18.79 1.53 CM = 2,238.50 KG/ML.

CARGA VIVA = CV = 305.00 KG/ML.

CARGA TOTAL = Cu=U = 3,652.40 KG/ML.

CALCULO DEL ANCHO NECESARIO DE CIMIENTO CORRIDO.-

CONSIDERANDO UN ESFUERZO DEL TERRENO SUPUESTO DE (RESISTENCIA DEL TERRENO ) = Õt = 2.85 KG/CM2. dato

ANCHO DEL CIMIENTO = b = 0.15 M.

ANCHO MINIMO DE CIMIENTO = 0.40 =====> b = 0.40 M.

PERALTE DEL CIMIENTO - DISEÑO POR FLEXION , CALC.MOM = 0.64 0.91 M'u = 7,023.85 KG-CM2.

EL PERALTE MINIMO SERA = si m = 10.00 h mín = 4.73 CM.

DISEÑO POR CORTE = Vup = 12.32 h = 19.71 CM.

PERALTE ADOPTADO PARA EL CIMIENTO SERA = he = 30 CM.

CALCULO DEL AREA DE ACERO As = 1/2 1.27 dato

CALCULAMOS EL AREA DE ACERO CON LA CUANTIA MINIMA 14/fy = As = 6.57 CM2.

As = 01 Fe. 1/2 @ 19 CM. Ast = 1.42 CM2.

Ast = 01 Fe. 1/2 @ 35 CM.

G) DISEÑO DE LA LOSA DE FONDO:LA LOSA IRA APOYADA SOBRE UN SOLADO DE DOSIFICACION CEMENTO - HORMIGON 1:12, Y TENDRA UNA

PENDIENTE DE 1 % HACIA EL TUBO DE DESAGUE. EL ESPESOR DEL TANQUE = 25.00 CM.

AREA DE ACERO MINIMO = Asmín = 4.50 CM2.

USANDO UN FIERRO DE 1/2 Smín = 28.22 CM.

EL ESP. MAXIMO USANDO FIERRO DE 1/2 Smáx = 75.00 CM.

As = UN FIERRO DE 1/2 @ S = 28.22 CM.

SOLADO DE CONCRTO 1: 12 SEGUN EL TIPO DE SUELO = ESPESOR 10.00 CM. dato

ANCHO DE VEREDA DE PROTECCION = 0.60 M. dato

VOLADIZO DEL TECHO DEL TANQUE = 0.20 M.

FIN DEL DISEÑO RESERVORIO DE 35.00