CONTRATO MARCO DE INGENIERÍA PARA
CAMPO RUBIALES
INGENIERÍA DE CAMPO POR ASIGNACIÓN DE
PERSONAL
HOJA DE DATOS TRANSMISOR DE FLUJO TIPO VORTEX - CALDERA
DE 700 BHP
REV FECHA DESCRIPCIÓN ELABORADO Y&V REVISADOY&V APROBADO Y&V
B1 08.Dic.11 Emitido para Comentarios del Cliente J. Insignares C. Moreno A. Campaña
0 26.Dic.11 Emitido para Construcción J. Insignares C. Moreno A. Campaña
Y&V INGENIERÍA Y CONSTRUCCIÓN 3002-15-CPF2-I-DS-1020
N°DE CONTRATO 5500001090
PACIFIC RUBIALES ENERGY RUB-CPF2-CRU-INS-DS-1020
7/29/2019 RUB-CPF2-CRU-INS-DS-1020-0
http://slidepdf.com/reader/full/rub-cpf2-cru-ins-ds-1020-0 2/4
3
CONTRATO MARCO DE INGENIERÍA PARA
CAMPO RUBIALES
INGENIERÍA DE CAMPO POR ASIGNACIÓN DE
PERSONAL
CONTENIDO
550-FIT-00401
RUB-CPF2-CRU-INS-DS-1020 Revisión 0 Pág.
3002-15-CPF2-I-DS-1020 Fecha 26.Dic.11 2 de 4
PACIFIC RUBIALES ENERGY
Y&V INGENIERÍA Y CONSTRUCCIÓN
7/29/2019 RUB-CPF2-CRU-INS-DS-1020-0
http://slidepdf.com/reader/full/rub-cpf2-cru-ins-ds-1020-0 3/4
NO.
B1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
1415
16
17
18
19
20
21
22
23
24
25
3,6 psi
Class 1, Div. 1, Gr. C, D NEMA 4X + 7
Water Vapor Steam
CONTRATO MARCO DE INGENIERÍA PARA
CAMPO RUBIALES
J.I.
VORTEX FLOW TRANSMITTER 0
DATE
5500001090
REV.
BY DESCRIPTION
26-Dic-11
Min
Line Number Line size
SHEET
3
OF
4
SPEC. No.
RUB-CPF2-CRU-INS-DS-1020
Gasket / Seal Material
SENSING
ELEMENT
FLOWMETER
BODY
Kármán vortex street
GENERAL
Multivariable
Stainless Steel
FLUID DATAMax
Flow (lb/h)
Tag Number
Viscosity (cP) 0,626 0,016
550-FIT-00401
Calibrated Flow Range, Units
Service Flujo de vapor salida de caldera de 700 BHP
Pressure (psia)Temperature (ºF)
Ambient Temperature (ºC): 20 25 30
Seal Type
Max. Allowable Diff Pressure Loss
Stainless Steel
DATE
REQ. P.O.
J.I.
26-Dic-11
BY
Emitido para Construcción
CHK'DA.C.
APPR.
2000 25000 82000114 120 180
J.I.
lb/hMax
Normal Max
08-Dic-11 Emitido p/ coment del cliente
C.M.
CONTRACT
INGENIERÍA DE CAMPO POR ASIGNACIÓN DE PERSONAL
--- ---
Area Clasification Enclosure6"6"-MPS-550-00501-A1A2-IH
Fluid Fluid StateCertification FM ó CSA
NormalMin
Type
Flowmeter StyleBody Type
Flange Material
Non-Replaceable on-lineFlanged
Stainless SteelCompression Fitting
By Manufacturer / Stainless Steel
Connection: Size
Oper Spec. GravityMin Normal
6" Class 300 RF
Fill Fluid MaterialSheeder Bar Material
Min Normal Max
Sensor TypeMeasurement PrincipleSensor Wetted Material
By Manufacturer
Raiting
350 350 380
27
28
2930
31
32
33
34
35
36
37 Max. measured error38 Flow Rate Range39
40 Insolation Manifold41 Connecting Cable Length42 Cable Glands Mounting Kit43 Local Counter & Totalizer44
Remote Indicator Style45
46
47
NOTES:
2. El transmisor debe venir adecuado para ser instalado en un soporte de tubo de 2" de diámetro.
3. La electrónica del transmisor debe estar protegida contra efectos de campos electromagneticos, descargas electricas y sobrevoltajes.
4. El proveedor es responsable de verificar la selección, materiales de construcción y condiciones de operación adecuada a los
instrumentos aquí especificados.
1%
Remote
+ 2 % of reading
Span-Zero AdjustmentDigital Communication Std
---
1/2" NPT-F 24 VDC
lb/h
Housing Type Mounting
Electrical Connection Power Supply
Output Signals: Output (1) Output (2) Flow: Pulse (Frequency) Foundation Fieldbus
PURCHASE
YesBy Manufacturer
Manufacturer ENDRESS+HAUSER
Configurable Engineering Units
estampada con el tag,
1. Todos los instrumentos deben ser suministrados con una placa de identificación. Esta placa debe ser de acero inoxidable y
Model No. Prowirl 73 or Similar
Instrument Range:Accuracy Stability
lb/h
No
Mín 82000
Externally AdjustableFoundation Fieldbus
2" pipe mounting
Máx Unit 2000
ACCESSORIES
TRANSMITTER
The measuring range depends on the fluid and nominal diameter
Repeatability Velocity Range + 0,25 % 0,01 - 9 m/s
10 mYesYes
YesUnitsIntegral LCD display
Mín Máx Unit 1867 82000Calibration Range:
7/29/2019 RUB-CPF2-CRU-INS-DS-1020-0
http://slidepdf.com/reader/full/rub-cpf2-cru-ins-ds-1020-0 4/4
OF
4
NO. BY DATE
B1 J.I. 08-Dic-11
0 J.I. 26-Dic-11
1
2
3
4
5
6
7
8
9 Integral Blind Remote (use Remote Indicator Data Sheet)
Analog Input 3 20
Flow 1 Level Density Other __________________ Input Selector 1 20
PID Block 1 100
Remote Mount Integrator
Orifice Plate Annubar Venturi Tube Nozzle Other:
13 Transducer Block Function Block Arithmetic Block
No. Of Line Signal Characterizer3 x 17 Digits
15
16
17
19
20
21
22
23
24
i l
Sensor Reference AccuracyRangoability
Nota 4
TPE (Total Probable Error UnderProcess Conditions For 12
± 0,15 % of Span @ ± 28 °C
Diaphragm Material Ver hoja 3
Sensor Fill Fluid Ver hoja 3
Power Supply Bus powered, 2 Wires, 9 - 32 V dc
Sensor Type Ver hoja 3
18 Process DataTemperature (°F) Pressure (Psig) Impulse Plugged Line Detection
Ver hoja 3 Ver hoja 3 Statistical Process Monitoring
ADVANCED DIAGNOSTICS FUNCTIONBLOCKS
Sensor Range Ver hoja 3
Sensor Temperature Limits -
Burst Pressure Limit 10,000 Psig (69 Mpa)
Linkable Variables On Display
14 Local Display Type No. Of Points (TAG's)Liquid Crystal Display 4 Variables in Segment
11 Calculated PVE.U.:
12 Primary ElementDirect Mount
10 Primary PVRange Engineering Units (ms)
Mounting Soporte de tubo de 2" INSTANTIABLE TYPE
Indicator Funct ion Block Execution Time
Housing Color Estandar del fabricante
Location Campo Rubiales
Description Transmisor de Flujo Tipo Vortex Resource Block
Housing Stainless Steel Transducer Block
TRANSMISOR FOUNDATION FIELDBUSTag Number Ver hoja 3
DEVICE FUNCTION BLOCKS FIXED TYPEService Ver hoja 3
Enclosure Class NEMA 4X + 7 Transducer Display Block
BY CHK'D APPR.J.I. C.M. A.C.
INGENIERÍA DE CAMPO POR ASIGNACIÓN DE
PERSONAL
CONTRACT DATE5500001090 26/12/2011
REQ. P.O.
--- ---
CONTRATO MARCO DE INGENIERÍA PARA
CAMPO RUBIALES
Emitido para Construcción
REV.0
SHEET
4
SPEC. No.RUB-CPF2-CRU-INS-DS-1020
FIELDBUS INSTRUMENT DATA SHEET
DESCRIPTION
Emitido p/ coment del cliente
25
26
27
28
29
30
Remote Mount
3 Way Valve 5 Way Valve Other: Mater ial :
32
ITK Baud Rate Min. VCR Min. Links
4 31.25 Kbps 20 30 10
34
35
36
37
38
39
40
41
42
44
45
4647
Notas:1. El vendedor debe proveer los Device Descriptor, de acuerdo con la revisión del firmware del dispositivo de campo.2. Es mandatorio por el vendedor, el suministro de: "Capability Format File" para cada dispositivo.3. Todos los dispositivos deben mostrar el logo: Foundation ™ fieldbus.4. Información suministrada por el fabricante.
Special Accessories Ver hoja 3
Firmware Upgrade By H1 Bus
Manufacturer Endress+Hauser
Model No. Prowirl 73 or Similar
43Supported Foundation ™ FieldbusMethods
Transducer Block Resource Block
Calibration,Zero Trim, Sensor Trim, Factory Recall Upgrade Device, Master Reset, Alarms
Local Adjustments Yes, Internal
Configuration Write Protect Yes
L.A.S. Backup Capability Yes
Maximum Power Consumption 17.5 mA
Device Descriptors Yes
Foundation ™ Fieldbus CheckMark
Yes
Physical Communication Media Twisted Pair wires
Inverse Polarity Insensitive Yes
Integral Transient Protector Yes
Baud Rate 31.25 Kbps
33 CommunicationProtocol Minimum Schedule Entries
Foundation ™ Fieldbus H1
Electrical Connection 1/2" NPT-F
31 Manifold
Direct Mount
Process Connection:
Body Rating 2,000 Psi
Process Connection Ver hoja 3
Sensor Body Material Ver hoja 3
Connection Type Ver hoja 3
O-ring Material Nota 4