PREDIMENSIONAMIENTO DE ELEMENTOS ESTRUCTURALESLOSA ALIGERADA
L (m) FACTOR
4.68 25.00 0.19
VIGASVIGA PRINCIPAL
L (m) FACTOR
7.00 10.00 0.70
B (m)0.30 SE USA EL ANCHO MINIMO PARA VIGA PRINCIPAL
LA VIGA PRINCIPAL SERA DE : 0.30m. X 0.70m.
VIGASVIGA SECUNDARIA
L (m) FACTOR
4.68 10.00 0.47
NOTA: POR DECISION PROPIA PARA EN ANALISIS SE USARA LA MISMA ALTURA DE LA VIGA PRINCIPAL
B (m)0.30 SE USA EL MISMO ANCHO QUE LA VIGA PRINCIPAL
LA VIGA SECUNDARIA SERA DE : 0.30m. X 0.70m.
COLUMNAS
PS n f'c (Kg/cm2)
92181.60 0.45 280
DETERMINACION DE LA CARGA DE SERVICIO PS
Kg/m3 Kg/m2 LONGITUD 1LOSA ALIGERADA 300.00 3.50VIGA SECUNDARIA 2400.00VIGA PRINCIPAL 2400.00ACAB. + TABIQU. 250.00 3.50COLUMNA 2400.00
ALTURA DE LOSA ALIGERADA
ALTURA DE VIGA PRINCIPAL
ALTURA DE VIGA SECUNDARIA
![Page 2: Metrado de Cargas v01](https://reader036.fdocumento.com/reader036/viewer/2022082411/563dba0e550346aa9aa2547c/html5/thumbnails/2.jpg)
SOBRECARGA 250.00 3.50
VERIFICACION DEL AREA DE COLUMNA1000cm21000cm2
ALTERNATIVA PARA ANCHO DE COLUMNAH de viga
0.70VERIFICACION DEL AREA DE COLUMNA
1000cm21000cm2
LA COLUMNA SERA DE : 0.56m. X 0.30m.
COLOCACION DE CARGASLOSA ALIGERADA
CARGA MUERTAPESO DEL LADRILLO 80.00 Kg/m2TABIQ. + ACAB. 250.00 Kg/m2
330.00 Kg/m2
0.40 m.
CARGA DISTRIBUIDA 132.00 Kg/m
CARGA VIVAS/C 250.00 Kg/m2
250.00 Kg/m2
0.40 m.
CARGA DISTRIBUIDA 100.00 Kg/m
CALCULO DEL PESO 2°,3°y 4° piso
Kg/m3 Kg/m2 LONGITUD 1
LOSA ALIGERADA 300.00 7.00VIGA PRINCIPAL 2400.00VIGA SECUNDARIA 2400.00ACAB. + TABIQU. 250.00 7.00COLUMNA 2400.00SOBRECARGA 250.00 7.00
CALCULO DEL PESO 5°PISO
ANCHO SUPERIOR DE LOSA ALIGERADA
ANCHO SUPERIOR DE LOSA ALIGERADA
![Page 3: Metrado de Cargas v01](https://reader036.fdocumento.com/reader036/viewer/2022082411/563dba0e550346aa9aa2547c/html5/thumbnails/3.jpg)
Kg/m3 Kg/m2 LONGITUD 1
LOSA ALIGERADA 300.00 7.00VIGA PRINCIPAL 2400.00VIGA SECUNDARIA 2400.00ACABADOS 100.00 7.00COLUMNA 2400.00SOBRECARGA 100.00 7.00
CALCULO DEL PESO 1°PISO
Kg/m3 Kg/m2 LONGITUD 1
LOSA ALIGERADA 300.00 7.00VIGA PRINCIPAL 2400.00VIGA SECUNDARIA 2400.00ACAB. + TABIQU. 250.00 7.00COLUMNA 2400.00SOBRECARGA 250.00 7.00
DX 7.00 mDY 21.00 m
CALCULO DE LA CORTANTE BASAL
Z 0.4U 1Cx 2.5Cy 2.5S 1.4R 8
Vx 0.175
Vy 0.175
V=𝑍𝑈𝐶𝑆/𝑅 𝑋 𝑃
Vx=𝑍𝑈𝐶𝑆/𝑅 Vy=𝑍𝑈𝐶𝑆/𝑅
![Page 4: Metrado de Cargas v01](https://reader036.fdocumento.com/reader036/viewer/2022082411/563dba0e550346aa9aa2547c/html5/thumbnails/4.jpg)
FACTOR DE AMPLIFICACION SISMICA ( C )
Tx= 0.43428571429 mH 15.20
Ctx= 35Tp= 0.9
Cx 5.18092105263Cx 2.5
VX 0.175*P 122518.767 KGVY 0.175*P 122518.767 KG
NIVELES ALT ACUM. PESO ALT*PESO5 15.200 112068.600 1703442.7204 12.200 146888.700 1792042.1403 9.200 146888.700 1351376.0402 6.200 146888.700 910709.9401 3.200 147372.540 471592.128
700107.240 6229162.968
x -8.5y -1.5
Cx=2.5 𝑋 (𝑇𝑝/𝑇𝑥 ) ≤ 2.5
![Page 5: Metrado de Cargas v01](https://reader036.fdocumento.com/reader036/viewer/2022082411/563dba0e550346aa9aa2547c/html5/thumbnails/5.jpg)
0.20 m
m
SE USA EL ANCHO MINIMO PARA VIGA PRINCIPAL
0.70 m
NOTA: POR DECISION PROPIA PARA EN ANALISIS SE USARA LA MISMA ALTURA DE LA VIGA PRINCIPAL
SE USA EL MISMO ANCHO QUE LA VIGA PRINCIPAL
^
AREA DE COLUMNA
731.6 cm2
LONGITUD 2 ALTURA SECCION 1 SECCION 2 N° DE PISOS4.68 5.004.68 0.70 0.30 5.003.50 0.70 0.30 5.004.68 5.00
3.00 0.30 0.56 5.00
ALTURA DE LOSA ALIGERADA(red.)
ALTURA DE VIGA SECUNDARIA A USAR
![Page 6: Metrado de Cargas v01](https://reader036.fdocumento.com/reader036/viewer/2022082411/563dba0e550346aa9aa2547c/html5/thumbnails/6.jpg)
4.68 5.00
PS
≤ A. columna ≥ 2000cm2≤ 731.6 ≥ 2000cm2 NO PASA
% ANCHO DE COLUMNA80% 0.56 m
≤ A. columna ≥ 2000cm2≤ 1680.00 ≥ 2000cm2 OK
LA COLUMNA SERA DE : 0.56m. X 0.30m.
LONGITUD 2 ALTURA SECCION 1 SECCION 2 CANTIDAD
21.00 1.007.00 0.70 0.30 6.00
21.00 0.70 0.30 2.0021.00 1.00
3.00 0.56 0.30 12.0021.00
![Page 7: Metrado de Cargas v01](https://reader036.fdocumento.com/reader036/viewer/2022082411/563dba0e550346aa9aa2547c/html5/thumbnails/7.jpg)
LONGITUD 2 ALTURA SECCION 1 SECCION 2 CANTIDAD
21.00 1.007.00 0.70 0.30 6.00
21.00 0.70 0.30 2.0021.00 1.00
1.50 0.56 0.30 12.0021.00
LONGITUD 2 ALTURA SECCION 1 SECCION 2 CANTIDAD
21.00 1.007.00 0.70 0.30 6.00
21.00 0.70 0.30 2.0021.00 1.00
3.10 0.56 0.30 12.0021.00
![Page 8: Metrado de Cargas v01](https://reader036.fdocumento.com/reader036/viewer/2022082411/563dba0e550346aa9aa2547c/html5/thumbnails/8.jpg)
Tx= 0.4342857142857 mH 15.20
Ctx= 35Tp= 0.9
Cy 5.1809210526316Cy 2.5
F SISMICA X VX MTZ X F SISMICA Y VY33504.293 33504.293 35179.508 33504.293 33504.29335246.918 68751.211 37009.263 35246.918 68751.21126579.643 95330.853 27908.625 26579.643 95330.85317912.368 113243.221 18807.986 17912.368 113243.221
9275.546 122518.767 9739.323 9275.546 122518.767122518.767 122518.767
Cy=2.5 𝑋 (𝑇𝑝/𝑇𝑥 ) ≤ 2.5
![Page 9: Metrado de Cargas v01](https://reader036.fdocumento.com/reader036/viewer/2022082411/563dba0e550346aa9aa2547c/html5/thumbnails/9.jpg)
PESO PARCIAL24570.0011793.60
8820.0020475.00
6048.00
![Page 10: Metrado de Cargas v01](https://reader036.fdocumento.com/reader036/viewer/2022082411/563dba0e550346aa9aa2547c/html5/thumbnails/10.jpg)
20475.00
92181.60 Kg.
PESO PARCIAL
44100.0021168.0021168.0036750.0014515.20
25% 9187.50
146888.70 Kg. Para 2°,3°y 4°piso
factor RNE art.16.3
![Page 11: Metrado de Cargas v01](https://reader036.fdocumento.com/reader036/viewer/2022082411/563dba0e550346aa9aa2547c/html5/thumbnails/11.jpg)
PESO PARCIAL
44100.0021168.0021168.0014700.00
7257.6025% 3675.00
112068.60 Kg.
PESO PARCIAL
44100.0021168.0021168.0036750.0014999.04
25% 9187.50
147372.54 Kg.
factor RNE art.16.3
factor RNE art.16.3
![Page 12: Metrado de Cargas v01](https://reader036.fdocumento.com/reader036/viewer/2022082411/563dba0e550346aa9aa2547c/html5/thumbnails/12.jpg)
MTZ Y11726.50312336.421
9302.8756269.3293246.441
![Page 13: Metrado de Cargas v01](https://reader036.fdocumento.com/reader036/viewer/2022082411/563dba0e550346aa9aa2547c/html5/thumbnails/13.jpg)
CARGAS DE FUERZA AXIAL Kgf
EJE A-1EJE A-2EJE A-3EJE A-4EJE A-5EJE A-6
![Page 14: Metrado de Cargas v01](https://reader036.fdocumento.com/reader036/viewer/2022082411/563dba0e550346aa9aa2547c/html5/thumbnails/14.jpg)
DISTORSIONES ELASTICAS
N° DE PISOSX SY
X Y X Y1 0 0 0.00019 0.0025752 0.002019 0.000058 0.000193 0.0026123 0.001045 0.000049 0.000156 0.0022364 0.001467 0.000034 0.000116 0.0017075 0.000955 0.000017 0.000065 0.001003
LO SOLICITADO POR LA NORMA E-030 0.007
DISTORSIONES INELASTICAS
N° DE PISOSX SX
X Y X Y1 0.00000000 0.00000000 OK OK2 0.01211400 0.00034800 NO PASA OK3 0.00627000 0.00029400 NO PASA OK4 0.00880200 0.00020400 NO PASA OK5 0.00573000 0.00010200 OK OK
N° DE PISOSY SY
X Y X Y1 0.00114000 0.01545000 OK NO PASA2 0.00115800 0.01567200 OK NO PASA3 0.00093600 0.01341600 OK NO PASA4 0.00069600 0.01024200 OK NO PASA5 0.00039000 0.00601800 OK NO PASA
![Page 15: Metrado de Cargas v01](https://reader036.fdocumento.com/reader036/viewer/2022082411/563dba0e550346aa9aa2547c/html5/thumbnails/15.jpg)